18
Modscan
setting
When you open Modbus,please set the following option
:
a
、
display start address is set to 0001
b
、
display data length is set to 51
c
、
the Device id of Modbus is set to 1
d
、
click drop-down menu options 04
:
INPUT REGISTER
MODBUS
address data query table
0
Main power input frequency Fin
Word(2Byte)
HT-L0
0.1Hz
1
Main power input line voltage Vrs
Word
HT-L0
0.1V
2
Main power input line voltage Vst
Word
HT-L0
0.1V
3
Main power input line voltage Vtr
Word
HT-L0
0.1V
4
Main power input phase voltage Vr
Word
HT-L0
0.1V
5
Main power input phase voltage Vs
Word
HT-L0
0.1V
6
Main power input phase voltage Vt
Word
HT-L0
0.1V
7
Rated charging current A
Word
HT-L0
A
8
Main power input phase capacity Sin
Word
HT-L0
0.01kVA
9
AC output frequency
Fr
Word
HT-L0
0.1Hz
10
AC output line voltage Vrs
Word
HT-L0
0.1Hz
11
AC output line voltage Vst
Word
HT-L0
0.1Hz
12
Output line voltag Vwu
Word
HT-L0
0.1V
13
AC output phase voltage Vr
Word
HT-L0
0.1V
14
AC output phase voltage Vs
Word
HT-L0
0.1V
15
AC output phase voltage Vt
Word
HT-L0
0.1V
16
AC output phase current Ir
Word
HT-L0
0.1A
17
AC output phase current Is
Word
HT-L0
0.1A
18
AC output phase current It
Word
HT-L0
0.1A
19
Output phase capacity Su
Word
HT-L0
0.1kVA
20
Output phase capacity Sv
Word
HT-L0
0.1kVA
21
Output phase capacity Sw
Word
HT-L0
0.1kVA
22
Total output capacity Stotal
Word
HT-L0
0.1kVA
23
Output capacity percentage PSr
Word
HT-L0
0.1
24
Output capacity percentage PSs
Word
HT-L0
0.1
25
Output capacity percentage PSt
Word
HT-L0
0.1