15
Wire diameter [mmq]
input
output
battery
kVA
L1/L2/L3/N
PE
L1/L2/L3/N
+/-
60
35
16
35
50
80
35
16
35
50
100
50
25
50
70
120
50
25
50
70
160
70
25
70
95
200
70
25
70
95
250
95
25
95
120
300
120
25
120
150
350
150
25
150
185
400
185
25
185
240
Check connections
After connecting the INPUT/OUT and terminal wires to the terminals of the UPS and before repositioning the
switch covers panel, check to make sure that:
all the input/output terminals are tightly screwed;
all fuse holders have a fuse inserted and are in the closed position;
the input/output protection wire (yellow/green earth wire) is correctly connected
the internal panel panel is connected to the yellow/green uni-potential cable coming from the earth bar
located on the base of the equipment.