Troubleshooting

Fault

Causes

Remedies

Insufficient air capacity and insufficient 

pressure

a) Clogged pipelines and/or suction points

b) Clogged impeller

c) Overloaded filter

d) Insufficient rotation speed

e) Clogged heat exchanger

a) Pipelines and suction point cleaning

b) Impeller cleaning.

c) Filter cleaning or replacement

d) Supply voltage check if necessary, correct

e) Heat exchanger cleaning

Exchange air temperature

too cold

External air lower than to -5°C

Employ of post-heating devices

Insufficient heat exchanger

performance

Exchange vanes are dirty 

Heat exchanger cleaning

Difficult start

a) Reduced supply voltage

b) Insufficient motor static torque

a) Check motor plate data

b) Close the air locks to reach full

speed if necessary, replace the motor

Performance drop after a period of 

acceptable operation

a) Circuit leak before and/or after the fan

b) Damaged impeller

a) Circuit check and restoration of original
conditions

b)Check the impeller, if necessary replace through
an original spare part

Air pulsation

The fan capacity conditions are near 

zero - flow instability, clogging or wrong 

connection

Increase the min. speed on the electronic speed-

regulator (insufficient voltage)

Modify the circuit and/or replace the fan.

Clean and/or restore the suction duct

Excessive vibrations

Rotating parts unbalance.

Check the impeller balance: in case, restore or 

replace it. Through an original spare-part.

Other troubleshooting for unit with microprocessor control 

EVO PH/EVO D PH

Fault

Causes

Remedies

Fans alert

Failure or objects blocking the fan

Verify that anything blocks the functioning of the 

fans: in the case, proceed with removal

Filters alert

Clogged filters

Replace the filters

Probes alert

Failure

Replace probes by technicians

Display/LED OFF

Machine not powered

Check the correct connection between the control 

panel and electronic card

Communication error 

(KO communication)

Error in the wiring of the remote panel

Make the electrical connections following the 

instructions in the wiring diagram

Summary of Contents for JRHB70/450

Page 1: ...Rel 11 2013 MANUALE DI INSTALLAZIONE USO E MANUTENZIONE Unità di ventilazione meccanica controllata con recupero di calore per settore terziario Heat recovery ventilator for energy efficient tertiary buildings ƞ min 50 max 70 GUIDE FOR INSTALLATION USE AND MAINTENANCE JR H V B 70 ...

Page 2: ... ingressi Il grado di protezione dell unità è IP20 In caso di installazione all esterno collocare l unità in luogo riparato da agenti atmosferici oppure utilizzare l apposito tettuccio parapioggia se necessario congiuntamente alle apposite cuffie di protezione con rete In questo caso il grado di protezione diventa IP22 SAFETY STANDARDS AND CE MARKING Our technicians are steadily engaged in researc...

Page 3: ...seguenze negative per l ambiente e per la salute dell uomo dovute alla presenza di sostanze potenzialmente pericolose Per informazioni più dettagliate sul riciclaggio di questo prodotto contattare l ufficio comunale il servizio locale di smaltimento rifiuti o il negozio in cui è stato acquistato il prodotto In caso di smaltimento abusivo saranno applicate le sanzioni previste dalla legge vigente R...

Page 4: ...te ceiling fastening and levelling see the draw After fastening the unit in the right position carry out the connec tion to the ducting the connection to the supply mains through the terminal board boxes and the condensate discharge pipe fastening on the air exhaust side Mod JRH B 70 450 JRH B 70 900 JRH B 70 2000 JRH B 70 3000 JRH B 70 4500 JRH B 70 5600 A B C D 345 360 535 630 855 855 400 400 40...

Page 5: ...ducting connection to supply mains See the description for the horizontal configuration The steam trap is one and presettled by the manufacturer Mod A B C 400 400 600 700 900 900 640 820 1040 1270 1300 1300 740 920 1140 1370 1300 1300 SPAZI MINIMI DI MANUTENZIONE ORDINARIA in mm MINIMUN SPACES REQUIRED FOR THE ORDINARY MAINTENANCE in mm B C A 100 CONFIGURAZIONE VERTICALE vista frontale lato ispezi...

Page 6: ... INSPECCIÓN AUF DIE KONTROLLE PANEL 3 CLOSE THE INSPECTION PANEL CHIUDERE IL PORTELLO DI ISPEZIONE FERMER LE PANNEAU D INSPECTION CERRAR EL PANEL DE INSPECCIÓN SCHLIESSEN DIE KONTROLLE PANEL 2 POSITION THE WASHER INSERT THE CONDENSATE DRAIN INTO HOLE AND SCREW THE UNIT INSERIRE LO SCARICO CONDENSA NEL FORO FRAPPONENDO LA GUARNIZIONE E AVVITARE IL DADO INTRODUIRE L EVACUATEUR DE LA CONDENSATION DAN...

Page 7: ...tion as showed in the picture These accessories are equipped with male female spigots for the ducting connection and can be installed on delivery and or suction mouths of the units direct installation or in the circuit of ducts remote installation E possibile installare come opzione dei dispositivi di PRE o POST riscaldamento quali batterie ad acqua o riscaldatore elettrico nell unica posizione co...

Page 8: ...nfigurazione orizzontale JRH70 JRH70 con by pass configurazione orizzontale JRHB70 E possibile in caso di installazione all esterno dell unità posizionare un tettuccio parapioggia T per la protezione dell unità da agenti atmosferici It is recommended to protect the unit installed outside by an external weather protective canopy T ...

Page 9: ...r i filtri Sostituzione filtri variabile in funzione dell inquinamento dell aria ambiente polveri fumi Manutenzione periodica consigliata per lo scambiatore Pulizia scambiatore 1 anno di funzionamento circa Recommended periodical maintenance Filter replacement variable depending on environment air pollution dust fume Recommended periodical maintenance Exchanger cleaning 1 operation season approxim...

Page 10: ...IATORE MAINTENANCE AND CLEANING OF FILTERS AND HEAT EXCHANGER MANUTENZIONE E PULIZIA FILTRI MAINTENANCE AND CLEANING OF FILTERS 1 2 3 4 5 Con ispezione laterale With side access 1 2 3 4 6 5 Con ispezione lato inferiore With beneath access ...

Page 11: ...ino delle condizioni originali b Verificare la girante e nel caso sostituire con ricambio originale Pulsazioni d aria Ventilatore che lavora in prossimità di condizioni di portata nulla Instabilità del flusso ostruzione o cattiva connessione Modifica del circuito e o sostituzione del ventilatore Pulizia e o ripristino canalizzazione in aspirazione Intervenire nel regolatore elettronico aumentando ...

Page 12: ...on of original conditions b Check the impeller if necessary replace through an original spare part Air pulsation The fan capacity conditions are near zero flow instability clogging or wrong connection Increase the min speed on the electronic speed regulator insufficient voltage Modify the circuit and or replace the fan Clean and or restore the suction duct Excessive vibrations Rotating parts unbal...

Reviews: