B4.1.2. WITH WATER TEMPERATURE MONITORING
- DPC.HCE320
Off
The device is controlled via home automation. The unit starts as soon as there is a
0-5/5-10V control signal and the set water temperature has been reached.
The unit starts as soon as the water temperature is >
28 ̊C and the control signal is 0-5V.
The unit starts as soon as the water temperature is <
24°C and the control signal is 5-10V.
Off
All functions are disabled until the user switches on
the unit via the control panel.
Activator speed in function of the incoming control
signal.
Max
Min
1
5
0
10
BMS (V)
curve : Speed versus 0-5 / 5-10V control signal
B4.2. OPTION : THERMO-ELECTRICAL MOTOR
–
Valve opens in heating mode as soon as there is a 0-5V control signal.
–
Valve opens in cooling mode as soon as there is a 5-10V control signal.
–
Valve closed in off mode or when the control signal is 5V.