TESTING
above the first and/or second stage heating differential. The Y1 and/or Y2 compressor
relays will be energized and the W1 (auxiliary heat) relay will be bypassed. After
testing, reset the high balance point temperature to a normal operating range.
Adaptive Recovery is only available in programmable mode (Installer Options Menu
13:RC = ON). The Adaptive Recovery function of the T-32-TS permits the user to
program a time that a desired set temperature is required. The thermostat then
calculates the most energy efficient time to energize the equipment to reach the
setpoint at the designated time. The calculation involves a complex control algorithm
that compares the space temperature deviation from setpoint and rate of recovery
history.
ADAPTIVE RECOVERY
55