9
C
ARE
&
M
AINTENANCE
- Should your campfire be left out in the rain, simply light it as usual and burn until the log
set and embers have dried out and begin to glow.
- Scratches and stains on the wind guard can be buffed out using a Scotch-Brite pad. Be sure
to buff “with the grain” to restore the stainless steel’s natural luster.
- The hose assembly must be checked every time the campfire is lit. If evidence is found of
excessive abrasion or wear, or if the hose is damaged the hose must be replaced prior to
lighting. Replace with part number TPR18HRA.
- The burner assembly must be checked every time the campfire is lit. If evidence is found of
damage the burner must be replaced prior to lighting. Replace with part number
TPR18LPB.
- The burner may be removed, for cleaning or maintenance by removing the two (2)
mounting screws and lifting the burner from the campfire body.
- To clean the burner wait until the campfire has completely cooled. Gently remove the log
set and embers. CAREFULLY LIFT each log STRAIGHT UP off of the center tube and
alignment pins starting from the top down (in the reverse order shown in Figures 5-10).
Pour off and SAVE THE EMBERS. The burner may then be removed. Use a soft brush
attachment on a vacuum to clean the whole unit. Re-install the burner and refer to the
section
Log & Ember Placement
to re-install the logs and embers.
- This campfire, hose, and regulator assembly must be disconnected from the gas supply
piping system during any pressure testing of the gas supply piping system at test pressures
in excess of 1⁄2 psi (3.5kPa).
This campfire must be isolated from the gas supply piping system by closing its individual
manual shutoff valve during any pressure testing of the gas supply piping system at test
pressures in equal to or less than 1⁄2 psi (3.5kPa).
- Should carbon deposits appear on the log set simply vacuum it off using the soft brush
attachment on your vacuum.