background image

The SD-503ST stand-alone combined smoke and heat detector 

MLW5550

3

 

The SD-503ST Stand-alone combined smoke and heat 

detector 

The SD-503ST is used to detect fire hazards in the interior of 

residential or commercial buildings. The detector can be installed in 

mobile homes or caravans. The product is not designed to be installed 

in industrial premises. 

 

 The detector indicates a fire hazard using the built-in LED indicator 

and acoustic signalling.  

The SD-503ST consists of two independent detectors –  an optical 

smoke detector and a heat detector. The optical smoke detector works 

on the principle of scattered light. It is very sensitive to large dust 

particles which are present in dense smoke. It is less sensitive to 

smaller particles generated by the combustion of liquids such as 

alcohol. That is why the fire detector also contains a built-in heat detector 

which has a slower reaction but is much better at detecting fire which 

generates only a small amount of smoke.

 

 

Detector range and location 

The smoke detector must be installed so that any smoke easily drifts 

into the detector owing to natural thermal currents, e.g. on the ceiling. It 

is suitable for residential buildings but not suitable for free spaces, 

outdoor environments or interiors with extremely high ceilings (above 

5 m) where fire by-products can disperse over a large area –  the 

smoke would not reach the detector position.

 

The detectors should be installed by a trained technician with a valid 

manufacturer’s certificate. 

Detectors should be installed in the building according to the project 

documentation. If such documentation is not available, the detector 

positions should comply with the effective standards for fire alarm 

signalling systems.

 

The detector must always be placed in the section leading to the exit 

of the building (escape route), see

  Fig. 1

. If the building has a floor 

area greater than 150 m

2

, installation of an additional detector in some 

other suitable place is required, see 

Fig.2

 

1. kitchen, 
2. living room, 
3. – 6. bedrooms

 

/

 /

 

basic 

coverage

 

 

 / 

 

recommended 

coverage

 

Fig 1 

Fig 2 

Fig 3 

In multi-storey flats and family houses the detector should be 

installed above the stairs. It is recommended to place additional 

detectors in rooms where people sleep. See 

Fig 3

.  

 Installation on level ceilings 

Place the detector in the centre of the room if possible. 

The detector 

must not be recessed into the ceiling

 due to the possible existence 

of a cool air layer on the ceiling.

  Never place the detector in the 

corner of the room 

(always keep at least 0.5 m distance from the 

corner  -  see Fig 4). There is an insufficient circulation of air in the 

corners. 

 

Installation on sloping ceilings 

If the ceiling is not suitable for mounting on a level surface (e.g. a 

room under a roof ridge), the detector can be installed as in Fig. 5. 

 

Fig. 4 

Fig. 5 

 centre of the room, best location 

 acceptable location 

 Walls, partitions, barriers and lattice ceilings 

The SD-503ST detector must not be installed closer than 0.5 m 

from any wall or partition. 

A narrow room with a width of less than 1.2 m 

requires the detector(s) to be placed at a distance of at least one third of the 

room’s width away. In a case when a room is separated into sections with 

furniture, racks or semi partition walls which do not reach the ceiling, the 

space is considered to be fully separated if the gap between the top of 

these and the ceiling does not exceed 0.3 m

.

 A free space of at least 0.5 m 

is required under and around the detector. Any irregularities of the ceiling 

(e.g. girders) exceeding 5 % of the ceiling height should be considered a wall 

and the above mentioned limitations should apply. 

 

Ventilation and air circulation 

The detectors must not be installed directly by ventilation or air 

conditioning vents.

  In the case of air being supplied through a 

perforated ceiling, each detector must be placed so that no perforation 

hole occurs within 0.6 m of the detector.

 

Avoid installing the detector in the following locations:

places with poor air circulation (niches, corners, apexes of A-

shaped roofs, etc.)

places exposed to dust, cigarette smoke or steam

places with over-intense air circulation (close to ventilators, heat

sources, air conditioning outlets, etc.)

in kitchens and other cooking places (because steam, smoke or oily

fumes can cause false alarms or reduce detector sensitivity).

beside fluorescent lights or energy-saving light bulbs (electrical

interference can cause a false alarm)

in areas with lots of small insects

Warning: 

Most false alarms are caused by improper detector 

location.

 

See CEN/TS 54-14 standards for detailed installation guidelines.

 

Installation 

When installing the detector, abide by the procedures recommended 

in the previous paragraphs. 

Fig. 6: 

1– detector cover opening; 2 – detector cover closing; 3 – optical status 

signalling (red LED); 4 – arrow showing where to insert the detector;  

5 – configuration terminals; 6 – battery holders;

   

 

1.

Open the detector cover, by turning it anti-clockwise (1)

2.

Attach the plastic base to the selected place using screws

3.

Use the terminals (5) to set the required detector function 

see the table below

Reviews: