The SD-503ST stand-alone combined smoke and heat detector 

MLW5550

3

 

ON 

Memory disabled 

OFF 

Smoke (EN 14604) or heat 

(EN 54-5) 

OFF 

Memory enabled 

OFF 

ON 

Heat only (EN 54-5) (no 

smoke) 

OFF 

OFF 

Smoke only (EN 14604) 

(no heat) 

ON 

ON 

Smoke and heat at the 

same time (both conditions 

concurrently) 

ON 

When the detector is installed in caravan trailers, use only the “smoke 

only“ or “both smoke and heat” settings. 

4.

Insert the batteries (3 X AA, alkaline 1.5 V)

5.

Close the detector cover.

 The detector can be inserted into the

plastic base in one position only.  The correct position is marked

with arrows on both plastic parts (4).

Note: 

Detector cover closing is blocked unless all 3 batteries are 

inserted! 

The  mounting  base  must  not  be replaced  by  bases  meant  for 

detectors without the test button consisting of pressing the body 

of the detector.

 

Fire alarm 

A fire alarm 

is signalled both acoustically and optically. 

When the conditions for fire alarm triggering are met (smoke is 

detected in the room, the alarm temperature is reached, or both), the 

detector signals the danger by sounding the siren and quickly flashing 

the LED indicator (3). 

    

Silencing the siren during an alarm:

 The siren can be silenced 

by pressing the detector body against the base. The siren is then silent 

for 10 minutes. If the detector still detects smoke or heat then, the 

siren is reactivated. 

When the need arises (e.g. in the case of a detector failure), it is 

possible to postpone siren reactivation by up to 12 hours. This can be 

done by pressing the detector again for 5 s after silencing the siren. 

When the detector chirps, you have to release the pressure within 1s. 

The switchover to the postponed siren mode is confirmed with 5 

chirps. The detector LED flashes all the time during the postponement. 

Alarm memory: 

  If it is enabled, alarm indication continues even 

when the smoke clears or when the temperature decreases. The slow-

flashing  indication lasts 24 hours unless it is terminated by pressing 

the detector body. 

Detector testing 

The detector should be tested at least once per month.

 To test 

the detector press its body against the base and wait until the LED 

indicator starts flashing. The LED flashing signals switchover to test 

mode. The LED flashes for the whole duration of the test. When the test 

is complete, the LED switches off. The detector then signals the result. If 

the detector chirps once, no problems have been detected. If a fault is 

discovered, the LED flashes three times.  The detector flashes once 

without acoustic indication if the  test is finished and a  low battery is 

detected. If the battery is low, there is no acoustic signalling

 

The complete function of the detector can be tested with a testing 

spray (e.g.. SD- TESTER) or hot air (e.g a hair dryer).

 

Warning: never test the detector with fire.

 

 

Fault indication 

The detector checks its functioning. If it discovers a fault, it beeps 

and flashes three times simultaneously, and then flashes three times 

every 30 s.  

A detector test can be carried out when a fault is signalled. To test the 

detector, press its whole body against the base. During test the detector 

checks whether the fault still exists.  The LED flashes during the testing. 

When the test is completed, the LED stops flashing and then signals the 

result. A persistent fault is signalled by 3 flashes and 3 beeps. If the fault 

has been removed, the detector chirps briefly. 

If you have not managed to repair the fault, the detector must be sent to 

a service centre. 

Battery replacement 

The detector checks the battery status and if the batteries are 

running low, the detector signals that they need replacing by short 

flashes every 30 s. Replace the batteries as soon as possible. Always 

replace all three batteries with the same type and manufacturer. 

Note

: For the best possible operation we strongly recommend using 

only batteries supplied by Jablotron’s  authorized distribution (avoid 

usage of so called no-name batteries). 

 

Do not throw used batteries into ordinary household waste. 

Deposit them at authorized collection points.

 

Technical specifications 

Power 

3 x 

alkaline batteries AA (LR6) 1.5 V 

Please note: Batteries are not included

 

Typical battery lifetime 

approx. 3 years 

Smoke detection 

optical light scattering 

Smoke detector sensitivity 

 m = 0.11 - 0.13 dB/m pursuant to EN 14604:2005 

Heat detection 

class A1 according to EN 54-5 

Alarm temperature 

+60 °C to +65 °C 

Operating temperature range 

-10 °C to +65 °C 

Dimensions, weight  

diameter 126 mm, height 52 mm, 150 g 

Conformity 

EN 50130-4, EN 55022 

14 

1293-CPR-0390

1293 

JABLOTRON ALARMS a.s. hereby declares that the SD-503ST detector is in compliance 

with the essential requirements and other relevant provisions of Regulation 2011/305/EU, 

2011/65/EU and Directive 2004/108/EC.  The original of the conformity assessment can be 

found at 

www.jablotron.com

 - Technical Support section

  

Note:

  Although this product does not contain any harmful materials we 

suggest you return the product to the dealer or directly to the producer after 

use. For more detailed information visit 

www.jablotron.com

.

 

Reviews: