Installation manual: Oasis security system JA-80K
- 9 -
MKE51801
other intruder detector within 40 minutes, an alarm will be
triggered. If the first triggered detector has a DEL reaction and
it is not confirmed by any other detector, it will not trigger an
alarm after the entrance delay has expired.
is set (armed).
Exit delay beeps
33x
331 = YES 330 = NO
YES
The last 5 s faster
Exit delay beeps while partially arming
34x
341 = YES 340 = NO
NO
The last 5 s faster
Entrance delay beeps
35x
351 = YES 350 = NO
YES
Setting (arming) confirmation by wired-siren chirp
36x
361 = YES 360 = NO
NO
IW terminal only
Siren always sounds during audible alarms
37x
371 = YES 370 = NO
YES
NO = siren only
sounds if the system
is completely set
(armed)
Wireless-siren alarms enabled (IW & EW)
38x
381 = YES 380 = NO
YES
Auto-bypass user approval via the
∗
key
If a detector is active during setting (arming), the system will
automatically bypass it (them), immediately (390), or after
keying in
∗
(391)
39x
391 = YES 390 = NO
NO
to confirm auto-
bypass while exiting
Service mode press #
twice
Final-door detectors
If this function is used, then Exit & Entrance delay settings are
multiplied by 30s. A triggered final-door detector extends the
exit delay, de-triggering of the last final-door detector ends the
exit delay.
65x
0=none, 1=detectors 01 to 05,
2=detectors 46 to 50
x = 0
If multiple F. door
detectors are used,
then triggered
state=any of them,
non triggered state=all
of them
Partial setting (arming) or system splitting
66x
0 = unsplit system
1 = partial setting (A, AB, ABC)
2 = split system A, B & common
section C (set if A & B are set)
unsplit
Automatic Summer Time (Daylight Saving Time)
680x
6801 = YES 6800 = NO
NO
Changes internal
clock + 1h on Apr.1 &
-1h on Nov.1
Tamper-signal differential indication -
Tamper alarm in response to an increase in the
number of triggered tamper sensors
681x
6811 =
ignore permanently
triggered tamper sensors, i.e.
only react to an increase in
the number of triggered
tamper sensors
6810 =
react with a tamper
alarm to all triggered tamper
sensors
X = 0
Suppresses the
indication of
permanently triggered
tamper sensors
Operating the PG outputs using
∗
8 and
∗
9
682x
6821 = YES 6820 = NO
YES
if yes then arrow keys
can also operate PGX
Permanent alarm status display for a set system
683x
6831 = YES 6830 = NO
NO
suppresses the 3min.
display timeout
Tamper alarm if unset
(disarmed)
684x
6841 = YES 6840 = NO
NO
Recording PG output activation to memory
685x
6851 = YES 6850 = NO
YES
Engineer reset
668x
6851 = YES 6850 = N0
NO
Annual check requirement display
If enabled then 12 months after exiting Service Mode an
annual technical check request is displayed on the keypad unit
(mobile phone & ARC notification optional)
690x
6901 = YES 6900 = NO
NO
Only single alarm indication
If enabled then another intruder alarm can not be triggered
during an intruder alarm currently in progress.
691x
6911 = YES 6910 = NO
NO
Setting (arming) by service code
692x
6921 = YES 6920 = NO
NO
only with the master
code holder’s
approval
Audible panic alarm
693x
6931 = YES 6930 = NO
NO
Higher control-panel receiver-sensitivity
Extends the communication range if there is no RF
interference
694x
6940 = normal 6941 = higher
normal
Access by Code plus
Card
If enabled and there is a code and card assigned to the same
user, then both of them must be presented for setting (arming)
control (in any order).
695x
6951 = Code+Card
6950 = Code or Card
code or
card
Audible 24h intruder alarm
696x
6961 = YES 6960 = NO
YES
Service mode only with S Master code
697x
6971 = YES 6970 = NO
NO