background image

Installation manual: Oasis security system JA-80K  

- 20 - 

 MKE51801

 

 

 

13.3. 

Setting and unsetting (arming/disarming) the 

system 

 

The system can be set and unset from a keypad, a keyfob or 

remotely by phone or the Internet or from a PC running Comlink 
software. 

 

To set the system from a keypad: 

  Press key ABC, A or B,  

  Enter a code (or present a card) 

  If the system is partially set (section A is set), and you wish 

to extend the proportion of the system which is set, press 
the B or ABC key. If you extend the proportion of the system 
which is set, then all delayed or next-delayed detectors in 
the section(s) going to be set and in the section currently 
set, will provide an exit delay which means that if a user has 
his system partially set (e.g. night setting) and wishes to exit 
the house by walking through the sections that are still set, 
he will not need to unset the whole system before leaving 
the house and setting the whole system. The route used by 
the user to leave the house must be covered by delayed or 
next-delayed detectors to make this possible and must be 
considered at the system design stage. 

 

To unset the system from a keypad: 

  Enter a valid access code (or present a card). 

 

Operating the system from an outdoor keypad 

If the system is equipped with a JA-80H outdoor keypad or a JA-
80N external card reader then the outdoor device could either 
work the same way as an indoor keypad unit or it could be 
programmed only to operate an electric door lock (known as an 
outdoor-bypass feature), i.e. an indoor keypad would then be 
used to control the alarm system. If the outdoor-bypass feature 
is enabled then: 

 Setting and unsetting the alarm system is only possible 

using a JA-80F or JA-80E indoor keypad or a keyfob. 

  Entering a valid access code or presenting a valid card to 

the outdoor keypad or card reader will always only open the 
electric door lock. 

  If the system is set, and the door is opened via the outdoor 

keypad or reader, an entrance delay will begin. During this 
delay the system has to be unset using an indoor keypad 
unit (or keyfob). 

 

13.4. Maintenance 

Mode 

 

Maintenance mode can be entered using a master code or 
master card by entering: 

0 MC 

   where  MC = master code (card) – factory default 1234 

In maintenance mode it is possible to: 

  Test devices (an alarm cannot be triggered), 

  Display which code/card positions are currently occupied 

 Bypass individual devices (for one setting/unsetting cycle or 

indefinitely)  - see 13.4.2. 

  Program the real-time system clock – see 12.46. 

 Program the automatic setting/unsetting schedule – see 

12.43. 

  Program telephone numbers for event reports to the end user 

(see 12.6). 

 

Exit maintenance mode by pressing the

 

# key.

 

 

13.4.1.  Displaying which user/card positions are occupied 

Which positions in the range 01 to 50 are occupied by codes or 
cards can be displayed in maintenance mode as follows: 
1. The control panel must be in maintenance mode – if not then 

enter 

0 master code or card (factory default: 1234) while the 

system is totally unset. 

2. Press  key 

5

 (the display indicates “Codes 01: Code”), 

3. Using the arrow keys all user positions (01 to 50) can be 

scrolled through, with the A indicator showing whether a code 
is programmed or not, and the B indicator showing whether a 
card is programmed or not. 

4. To exit this code/card display mode press the  

key. 

5. To exit maintenance mode press the 

key

.

 

 

To change access codes and cards use sequence 

6 MC nn NC 

(see 13.2). 
The most convenient way to administer  codes is by using a PC 
running Comlink software. 

 

13.4.2. Bypassing 

devices 

In maintenance mode it is possible to bypass (disable) individual 
system devices (permanently or only for one setting/unsetting 
cycle): 
1. The control panel must be in maintenance mode – if it is not, 

then enter 

0 master code (factory default: 1234) while the 

system is totally unset. 

2. 

Press key 1, 

to display the control panel’s 

bypass menu

3. Using the arrow keys you can scroll through all the devices 

able to trigger alarms

  

4. 

To bypass 

a device use key: 

  

2

 to bypass the device for one setting/unsetting cycle (the 

triangular indicator will start flashing) 

3

 

 

to permanently bypass a device

 

(the triangular indicator 

will light continuously) 

To cancel the bypassing of a device 

use the same button 

as was originally used for bypassing (

2

 or 

3

). Using key 

4

 

will cancel all device bypasses in the system. 
5.  All the desired bypasses can be programmed by 

repeating step 3 and 4. 

6. Press 

the 

key to exit the bypass menu. Pressing 

again

 

exits maintenance mode

.

 

 

If a system with bypasses programmed is being set, then bypass 
text will be displayed on the keypad unit. 
 

13.4.3.  Protecting a car near the system 

The Oasis system can also protect a car (cars) parked in the 
proximity of the house.  
1. If the car has a built-in car alarm then an RC-85 transmitter 

unit can be connected to the car alarm output and the 
transmitter unit can be enrolled to a free address in the Oasis 
control panel. An alarm triggered in the car can be indicated 
as an Oasis panic alarm 24 hours a day whether the system is 
set or not. Note: if the car alarm confirms setting (arming) by 
siren chirps appearing on the alarm output, then these should 
be disabled to avoid false alarms. 

2. 

If the car has no built-in car alarm 

then JA-85P or JA-85B 

detectors can be installed in the car. The car detectors can be 
assigned to their own dedicated section in the system, e.g. a 
split system where section A could be for the car detectors, 
and section B for the house detectors, with no detectors 
assigned to section C, and the entry codes/cards assigned to 
section C to access the whole system. So when the user 
enters the house he can set section A to protect the car, and 
unset section B to be able to enter the house. Radio 
communication supervision should be disabled for the car 
detectors to avoid fault notifications when the car is driven 
away from the house. 

Summary of Contents for Oasis JA-80

Page 1: ...trol panel installation manual This manual is valid for control panel JA 80K version KE60108 printed on internal circuit board The control panel can be configured by a PC running ComLink software vers...

Page 2: ...WIRELESS SIREN ALARM ENABLED IW AND EW 13 12 22 AUTO BYPASS USER APPROVAL VIA THE KEY 13 12 23 FINAL DOOR DETECTORS 13 12 24 PARTIAL SETTING ARMING OR SYSTEM SPLITTING 14 12 25 AUTOMATIC SUMMER TIME D...

Page 3: ...two inputs are not used the two addresses can be used to enroll wireless devices Hard wired inputs are also provided by some wireless devices such as keypads door detectors and PIR movement detectors...

Page 4: ...e T 200 mA The control panel power supply is double insulated safety class 2 and does not incorporate a protective earth wire A double insulated power cable should be used with a minimum cross section...

Page 5: ...ered and an external warning will only follow if the entrance delay has been exceeded PGX PGY are a pair of terminals providing programmable outputs If an output is activated it switches to GND with a...

Page 6: ...r a while before pressing and holding the key the language can be selected for each individual keypad in the system i e different keypads can display different languages for example if foreigners are...

Page 7: ...siren can be activated by pressing its button A JA 80A outdoor siren can be activated for signal strength measurement by opening its cover thereby triggering its cover tamper switch Each installed dev...

Page 8: ...min 4 min 0 10s for testing PGX function 23x 7 on off 80 81 PGY function 24x x in an unsplit system 0 whole system set ABC PG on 1 any system part set PG on 2 AB set not C PG on 3 Fire alarm PG on 4 P...

Page 9: ...O NO Changes internal clock 1h on Apr 1 1h on Nov 1 Tamper signal differential indication Tamper alarm in response to an increase in the number of triggered tamper sensors 681x 6811 ignore permanently...

Page 10: ...nsplit then ABC hh hours mm minutes No action The scheduled actions will happen every day Changing the service code 5 NC NC NC new code 4 digits 8080 enter NC twice Go to maintenance mode 292 switches...

Page 11: ...led 2 6 0 disabled Factory default setting disabled Note In some places the system can be permanently or occasionally affected by radio interference e g by nearby radar stations TV transmitters etc In...

Page 12: ...ors 3 1 1 indication enabled 3 1 0 indication disabled Factory default setting indication enabled 12 15 Confirmation of intruder alarms To reduce the risk of false alarms and to comply with British st...

Page 13: ...l i e setting by keyfob does not trigger an approval request The automatic bypass of a detector will end after the detector has been de triggered for example if a door is closed If auto bypass user ap...

Page 14: ...es as two independent systems one being section A and the other section B There is also a common section C which is only set if section A and section B are set at the same time and is commonly used fo...

Page 15: ...eceive a notification earlier than a year later change the internal clock settings to the day and month you prefer before exiting Service Mode by entering 4hhmmDDMMYY and then re adjust the clock to t...

Page 16: ...ing the B key on the keypad e g setting arming the garage and the ground floor during the night ABC using the ABC key on the keypad e g to set the entire system when leaving the house In a split syste...

Page 17: ...n be enrolled instead If a device with production code xx x has already been enrolled to another address in the past and if the device is now enrolled to a new address then it will be moved to the new...

Page 18: ...the menu and then keypad text After editing keypad text using Comlink software all keypads including wireless ones must be connected to the digital bus to save the changes to the keypad units by clic...

Page 19: ...ard then it is possible to program whether both a code and card must be presented to the system for system access or whether only one of them is required see 12 37 The system does not allow the same c...

Page 20: ...mode as follows 1 The control panel must be in maintenance mode if not then enter 0 master code or card factory default 1234 while the system is totally unset 2 Press key 5 the display indicates Codes...

Page 21: ...register at www GSMLink cz 15 Basic guidance for installers 1 Create an installation plan that sufficiently covers the building to be protected 2 If the customer requests changes to the suggested conf...

Page 22: ...d and reports to the control panel Alternatively power the keypad with an AC adaptor to prevent sleep mode or install an indoor wireless siren type JA 80L to generate entrance delay beeps 17 Control p...

Reviews: