jablotron Oasis JA-80 Installation Manual Download Page 7

Installation manual: Oasis security system JA-80K  

- 7 - 

 MKE51801

 

 

control panel twice but to two different addresses with different 
features –see 12.40.

  

  Only a single device can be enrolled to each address. 

 When indicator A lights, it means the displayed address is 

occupied and therefore no more devices can be enrolled to 
this address.  

  If a device has already been enrolled to an address, and it is 

then re-enrolled to another address, the device’s address 
assignment will change from the original address to the new 
one. 

 If a device cannot be enrolled to the control panel, either it 

does not have a good wireless connection to the control panel 
possibly due to excessive distance or it could be too close to 
the control panel (closer than 2 meters is not permitted),  

 To re-enroll a device, first disconnect its battery. Then wait 

about 10 seconds or, to save time, press and release its 
tamper switch to quickly discharge any remaining energy. 

 A 

sub-control panel

 can be 

enrolled

 to a 

master control 

panel 

by keying in the sequence 

299

 on the keypad of the sub 

control panel which must be in 

Service mode

. (see 12.10), 

 If you intend to use final-door detectors in the system, they 

must be enrolled to addresses 01 to 05 or 46 to 50 (see 
12.23).  

 

 

11.3. 

Testing enrolled devices 

 

1.  The control panel must have its antenna connected and be 

in Service mode.  If not in Service mode, then key in 

service code  (factory-default 8080). To enter Service mode 
the control panel must be initially unset (disarmed). 

2. 

Trigger the device

 to be tested (if it is a detector close its 

cover first and then wait until it is ready for testing). 

3.  The keypad will beep and display a description of the signal 

received from the device under test (the keypad cover 
should be flipped open). We recommend technicians to 
carry the wireless keypad around while testing to ease the 
process. 

 

Notes: 

 Motion detectors JA-80P and JA-85P can be tested for a 

maximum of 15 minutes after closing their covers. After this 
period the detector will ignore frequent movements (see 
detector manuals for details). 

  Devices can also be tested in maintenance mode – see 13.4. 

 

11.4. 

Measuring signal strength  

1.  The control panel must have its antenna connected and be 

in Service Mode. If it is not, then enter 

0 service code 

(factory default: 8080). The control panel must be unset 
(disarmed) to enter Service Mode.  

2. Key in

 298

, and the lowest enrolled address will be 

displayed.  

3. 

Trigger the device

 enrolled to the displayed address. The 

keypad display will show the received signal strength  on a 
scale of 1/4 to 4/4. Keep the keypad cover flipped open 
while measuring  signals. 

4.  Other addresses for devices can be selected using the 

arrow keys to measure their signals too.  

5.  Exit signal measuring by pressing the 

key

.

  

 

Notes: 

 Motion detectors JA-80P and JA-85P can be tested for a 

maximum of 15 minutes after closing their covers. After this 
period the detector will ignore frequent movements (see 
detector manuals for details). 

 Measuring the signals from a JA-80L internal siren can be 

activated by pressing its button. A JA-80A outdoor siren  can 
be activated for signal strength measurement by opening its 
cover thereby triggering its cover tamper switch.  

  Each installed device should have a minimum signal strength 

of 2/4. If the signal is too weak, the device should be relocated 
or a higher control panel sensitivity can be selected. (see 
12.36) Alternatively the control panel can be equipped with an 
external antenna (see 10). 

 This measurement shows the quality of the signal received 

from the device at the control panel. 

 The wireless keypad can be carried during installation or 

testing by disabling its tamper contact via the jumper near the 
tamper contact – do not forget to re-enable the tamper before 
finishing the installation – Note: the keypad usually has a 
slightly shorter working range than the detectors. Therefore, if 
carried to more-distant detectors the triggering of the 
detectors might not be shown. 

  The most convenient way of measurement is via a computer 

running ComLink SW. 

 

11.5. 

Erasing enrolled devices  

 

1.  The control panel must be in Service Mode. If it is not, then 

enter 

0 service code (factory default: 8080). The control 

panel must be unset (disarmed) to enter Service Mode. 

2.  Key in “1” to enter enrollment mode and using the arrow 

keys select the desired address of the device you wish to 
erase. 

3. 

Press and hold 

the

 “2” key 

until a 

beep 

is heard and the

 A 

indicator 

turns off. 

4.  After all the desired devices have been erased, press 

#.

   

 

Notes: 

 To erase all wireless devices, press and hold the “4” key in 

enrollment mode.  

  If a wireless keypad is erased,  it will stop communicating with 

the control panel and must be re-enrolled before being used 
again. (see 7.1).  

  

11.6. 

Enrolling the control panel to UC and AC 

modules 

 

If you wish to use UC and AC modules to output PGX and PGY 
signals, you must enroll the control panel to these modules as 
follows:  
1.  The control panel must be in Service Mode. If it is not, then 

enter 

0 service code (factory default: 8080). 

2.  On the UC or AC module, enter the desired enrollment 

mode  (see the manual of the particular module) 

3. Key 

in 

299

  on the control panel keypad and check that all 

LEDs on the module flash a few times to confirm successful 
enrollment. 

 

Notes: 

 Because the UC and AC modules have rather short 

enrollment-period timeouts, we recommend locating the 
module close to the control panel during enrollment. 
Alternatively you could carry the wireless keypad close to the 
module to perform enrollment. 

 The control panel can be enrolled to the desired number of 

UC/AC modules to control multiple PG outputs in an 
installation. 

  Each UC and AC module has 2 relays, X and Y which have to 

go through enrollment separately. The X relay reacts to PGX 
signals from an enrolled control panel and the Y relay reacts 
to PGY signals from an enrolled control panel. The control 
panel’s PGX signal can be enrolled to the X relay and the 
control panel’s PGY signal can be enrolled to the Y relay. 
Therefore, the enrollment procedure has to be done twice if 
both relays are to be controlled by the control panel’s PG 
signals. 

  Only one control panel can be enrolled to a UC or AC receiver 

because a control panel repeats its PG signals every 9 

Summary of Contents for Oasis JA-80

Page 1: ...trol panel installation manual This manual is valid for control panel JA 80K version KE60108 printed on internal circuit board The control panel can be configured by a PC running ComLink software vers...

Page 2: ...WIRELESS SIREN ALARM ENABLED IW AND EW 13 12 22 AUTO BYPASS USER APPROVAL VIA THE KEY 13 12 23 FINAL DOOR DETECTORS 13 12 24 PARTIAL SETTING ARMING OR SYSTEM SPLITTING 14 12 25 AUTOMATIC SUMMER TIME D...

Page 3: ...two inputs are not used the two addresses can be used to enroll wireless devices Hard wired inputs are also provided by some wireless devices such as keypads door detectors and PIR movement detectors...

Page 4: ...e T 200 mA The control panel power supply is double insulated safety class 2 and does not incorporate a protective earth wire A double insulated power cable should be used with a minimum cross section...

Page 5: ...ered and an external warning will only follow if the entrance delay has been exceeded PGX PGY are a pair of terminals providing programmable outputs If an output is activated it switches to GND with a...

Page 6: ...r a while before pressing and holding the key the language can be selected for each individual keypad in the system i e different keypads can display different languages for example if foreigners are...

Page 7: ...siren can be activated by pressing its button A JA 80A outdoor siren can be activated for signal strength measurement by opening its cover thereby triggering its cover tamper switch Each installed dev...

Page 8: ...min 4 min 0 10s for testing PGX function 23x 7 on off 80 81 PGY function 24x x in an unsplit system 0 whole system set ABC PG on 1 any system part set PG on 2 AB set not C PG on 3 Fire alarm PG on 4 P...

Page 9: ...O NO Changes internal clock 1h on Apr 1 1h on Nov 1 Tamper signal differential indication Tamper alarm in response to an increase in the number of triggered tamper sensors 681x 6811 ignore permanently...

Page 10: ...nsplit then ABC hh hours mm minutes No action The scheduled actions will happen every day Changing the service code 5 NC NC NC new code 4 digits 8080 enter NC twice Go to maintenance mode 292 switches...

Page 11: ...led 2 6 0 disabled Factory default setting disabled Note In some places the system can be permanently or occasionally affected by radio interference e g by nearby radar stations TV transmitters etc In...

Page 12: ...ors 3 1 1 indication enabled 3 1 0 indication disabled Factory default setting indication enabled 12 15 Confirmation of intruder alarms To reduce the risk of false alarms and to comply with British st...

Page 13: ...l i e setting by keyfob does not trigger an approval request The automatic bypass of a detector will end after the detector has been de triggered for example if a door is closed If auto bypass user ap...

Page 14: ...es as two independent systems one being section A and the other section B There is also a common section C which is only set if section A and section B are set at the same time and is commonly used fo...

Page 15: ...eceive a notification earlier than a year later change the internal clock settings to the day and month you prefer before exiting Service Mode by entering 4hhmmDDMMYY and then re adjust the clock to t...

Page 16: ...ing the B key on the keypad e g setting arming the garage and the ground floor during the night ABC using the ABC key on the keypad e g to set the entire system when leaving the house In a split syste...

Page 17: ...n be enrolled instead If a device with production code xx x has already been enrolled to another address in the past and if the device is now enrolled to a new address then it will be moved to the new...

Page 18: ...the menu and then keypad text After editing keypad text using Comlink software all keypads including wireless ones must be connected to the digital bus to save the changes to the keypad units by clic...

Page 19: ...ard then it is possible to program whether both a code and card must be presented to the system for system access or whether only one of them is required see 12 37 The system does not allow the same c...

Page 20: ...mode as follows 1 The control panel must be in maintenance mode if not then enter 0 master code or card factory default 1234 while the system is totally unset 2 Press key 5 the display indicates Codes...

Page 21: ...register at www GSMLink cz 15 Basic guidance for installers 1 Create an installation plan that sufficiently covers the building to be protected 2 If the customer requests changes to the suggested conf...

Page 22: ...d and reports to the control panel Alternatively power the keypad with an AC adaptor to prevent sleep mode or install an indoor wireless siren type JA 80L to generate entrance delay beeps 17 Control p...

Reviews: