jablotron Oasis JA-80 Installation Manual Download Page 5

Installation manual: Oasis security system JA-80K  

- 5 - 

 MKE51801

 

 

Communicator connector

 – allows the connection of an 

optional communicator to the main board. 

Internal wiring connector 

– connects the internal wiring in the 

control panel housing. 

 

Terminals: 

AC 20V

  the transformer output is connected here. 

01, GND, 02 

are hard-wired inputs for the control panel

.  

  The reactions to triggering these inputs are determined by the 

settings of addresses 01 and 02. The factory-set natural 
reaction for these hard-wired inputs is a delayed alarm in 
section C.  

 Terminals 01 and 02 use resistors in connected double 

balanced loops to sense loop stand-by, activation or 
tampering as follows:  

o

  Connected to GND via a 

1 k

Ω

 resistor = untriggered

 input  

o

  Connected to GND via 

2 to 6 k

Ω

 = triggered input

,  

o

 Connected to GND via 

less then 700

Ω

 or more then 6 k

Ω

 

=

 tamper signal

  

o

  Stand-by (untriggered) input zone must have 1

 k

Ω

 

  

o

 Up to five normally-closed door/window contacts can be 

connected in series to enable one hard-wired input to be 
used for multiple contacts with each contact having a 1k

Ω

 

resistor in parallel (see the diagram below). 

o

 Multiple  normally-closed  tamper contacts should be 

connected in series without any parallel resistors. The 
number of  tamper contacts is unlimited and can be 
combined with trigger contacts having parallel resistors (see 
the diagram below). 

o

  For wiring examples, see the below diagram. 

 

 

 

 

 

o

 If you 

enroll a wireless device to address 01 or 02,

  the 

corresponding input terminal 

will be disabled

o

 If you do not use an input terminal and you do not enroll a 

wireless device to its address, then the terminal must be 
connected to the 

GND 

terminal via a 1

 k

Ω

 

 resistor. 

NC 

 

normally closed contact for the external warning relay. 

NO 

-

 

normally open contact for the external warning relay. 

EWC 

– common contact for the external warning relay 

max. 

relay contact rating: 1A/60V. 

The control panel also transmits 

the external warning relay signal via radio for wireless sirens.   

IW 

– internal warning (siren) output. This output is grounded 

during an internal alarm. A standard siren can be wired between 
terU and IW (

max. 0.5A

).

 

The IW output status is also 

transmitted by radio for the IW siren. 

The main difference between internal and external warning is during 
the entrance delay period. If any instant detectors are triggered during 
the entrance delay period, e.g. a child running straight to the living 
room, only an internal warning will be triggered and an external 
warning will only follow if the entrance delay has been exceeded.     

PGX, PGY 

– are a pair of terminals providing programmable 

outputs. If an output is activated it switches to GND with a 
maximum load of 0.1A/12V. The factory-default setting of PGX is 
the function ON/OFF which can be operated from the keypad by 

the instruction 

81 / 

80 or using keys 

 

). The factory-default 

function of PGY is that it will be activated if any section of the 
system is set.  The status of PG outputs is also transmitted by 
radio for AC and UC output modules. 

GND

 – common ground connection 

A,B

 – digital bus data 

+U

 – back-up power supply (10 to 14V), 1A fuse. Max. 

continuous load 0.4 A (max. intermittent load 1 A, for 15 
minutes, once an hour). If the 1A fuse is blown, the control panel 
will indicate power supply fault. 

 

5.  Wired keypad connection  

GND A B U+

IN

+U

B
A

GND

GND

control and programming

keypad  JA-80E

modular connection

cable

 

The control panel can be operated and programmed by JA-

80F wireless keypads and/or a JA-80E hard-wired keypad. A 
hard-wired keypad can be connected to the control panel either 
by flat telephone cable (max. length 10 metres) using RJ 
connectors, or via twisted-pair cable (max. length 100 metres) 
connected to the digital bus terminals (GND, A, B, +U). 

We recommend only having a single JA-80E hard-wired 

keypad in the system. 

 

6. Back-up battery 

 It is possible to use a Jablotron-brand 12V back-up battery in 

the control panel with capacities of 1.3Ah or 2.6no Ah. The 
capacity to use depends on the total power consumption of the 
system and the desired back-up period.  

 Euro-standard EN 50131-1 specifies a 12 hour minimum back-

up time for grade 2 systems. The standby consumption of all 
system devices is shown in table 1. 

Table 1-  standby consumption of system devices 

 

 With a 

1.3Ah

 back-up battery 12 hours of back-up time can be realised if 

current consumption does not exceed 

85mA

. With 

2.2Ah

 batteries 

150mA 

should not be exceeded to achieve the same. This only takes 

80% of the battery capacity into account as 20% has to be reserved for 
battery aging effects. 

 The average

 back-up battery lifetime 

is

 up to 5 years 

after which it must 

be replaced. The back-up battery is automatically charged and its 
condition is monitored by the system. If the system is being run on only 
the back-up battery a technical alarm occurs when the battery is 
nearly discharged. If the voltage gets too low the battery will be 

Device mA 

Note 

Control panel JA-80K 

50 

No communicator 

Keypad JA-80E 

30 

 

Keypad JA-80H (N) 

60 

Including a WJ-80 interface  

Communicator JA-80Y 

35 

 

Communicator JA-80V 

30 

 

Wireless devices are not powered from the control panel. 

Summary of Contents for Oasis JA-80

Page 1: ...trol panel installation manual This manual is valid for control panel JA 80K version KE60108 printed on internal circuit board The control panel can be configured by a PC running ComLink software vers...

Page 2: ...WIRELESS SIREN ALARM ENABLED IW AND EW 13 12 22 AUTO BYPASS USER APPROVAL VIA THE KEY 13 12 23 FINAL DOOR DETECTORS 13 12 24 PARTIAL SETTING ARMING OR SYSTEM SPLITTING 14 12 25 AUTOMATIC SUMMER TIME D...

Page 3: ...two inputs are not used the two addresses can be used to enroll wireless devices Hard wired inputs are also provided by some wireless devices such as keypads door detectors and PIR movement detectors...

Page 4: ...e T 200 mA The control panel power supply is double insulated safety class 2 and does not incorporate a protective earth wire A double insulated power cable should be used with a minimum cross section...

Page 5: ...ered and an external warning will only follow if the entrance delay has been exceeded PGX PGY are a pair of terminals providing programmable outputs If an output is activated it switches to GND with a...

Page 6: ...r a while before pressing and holding the key the language can be selected for each individual keypad in the system i e different keypads can display different languages for example if foreigners are...

Page 7: ...siren can be activated by pressing its button A JA 80A outdoor siren can be activated for signal strength measurement by opening its cover thereby triggering its cover tamper switch Each installed dev...

Page 8: ...min 4 min 0 10s for testing PGX function 23x 7 on off 80 81 PGY function 24x x in an unsplit system 0 whole system set ABC PG on 1 any system part set PG on 2 AB set not C PG on 3 Fire alarm PG on 4 P...

Page 9: ...O NO Changes internal clock 1h on Apr 1 1h on Nov 1 Tamper signal differential indication Tamper alarm in response to an increase in the number of triggered tamper sensors 681x 6811 ignore permanently...

Page 10: ...nsplit then ABC hh hours mm minutes No action The scheduled actions will happen every day Changing the service code 5 NC NC NC new code 4 digits 8080 enter NC twice Go to maintenance mode 292 switches...

Page 11: ...led 2 6 0 disabled Factory default setting disabled Note In some places the system can be permanently or occasionally affected by radio interference e g by nearby radar stations TV transmitters etc In...

Page 12: ...ors 3 1 1 indication enabled 3 1 0 indication disabled Factory default setting indication enabled 12 15 Confirmation of intruder alarms To reduce the risk of false alarms and to comply with British st...

Page 13: ...l i e setting by keyfob does not trigger an approval request The automatic bypass of a detector will end after the detector has been de triggered for example if a door is closed If auto bypass user ap...

Page 14: ...es as two independent systems one being section A and the other section B There is also a common section C which is only set if section A and section B are set at the same time and is commonly used fo...

Page 15: ...eceive a notification earlier than a year later change the internal clock settings to the day and month you prefer before exiting Service Mode by entering 4hhmmDDMMYY and then re adjust the clock to t...

Page 16: ...ing the B key on the keypad e g setting arming the garage and the ground floor during the night ABC using the ABC key on the keypad e g to set the entire system when leaving the house In a split syste...

Page 17: ...n be enrolled instead If a device with production code xx x has already been enrolled to another address in the past and if the device is now enrolled to a new address then it will be moved to the new...

Page 18: ...the menu and then keypad text After editing keypad text using Comlink software all keypads including wireless ones must be connected to the digital bus to save the changes to the keypad units by clic...

Page 19: ...ard then it is possible to program whether both a code and card must be presented to the system for system access or whether only one of them is required see 12 37 The system does not allow the same c...

Page 20: ...mode as follows 1 The control panel must be in maintenance mode if not then enter 0 master code or card factory default 1234 while the system is totally unset 2 Press key 5 the display indicates Codes...

Page 21: ...register at www GSMLink cz 15 Basic guidance for installers 1 Create an installation plan that sufficiently covers the building to be protected 2 If the customer requests changes to the suggested conf...

Page 22: ...d and reports to the control panel Alternatively power the keypad with an AC adaptor to prevent sleep mode or install an indoor wireless siren type JA 80L to generate entrance delay beeps 17 Control p...

Reviews: