J2 615/580 UPS
Specifications
Hardware
To install and use the J2 UPS module:
1: Remove the power supply adaptor from the base of the unit.
2: Install the UPS module where the power supply was mounted.
3: Connect the power output jack of the UPS to the power in jack of the unit.
4: Connect the Serial cable of the UPS to the serial port you wish to use. *
5: Connect the power supply adaptor to the UPS power in jack.
6: Connect the power supply adaptor to the mains power. **
7: Configure the Windows UPS drive as shown.
* The serial port connection is not needed for Windows CE.
** When first installed the mains power should be applied for 5 hours to fully charge the
batteries. The unit may be running during this time but will take longer to charge.
Batteries Run Time
1.5 hours for the standard J2 615, run time will vary
depending on the application loading
Power In
19 Volts DC
Power Out
13-16.8 Volts DC, 8 amps maximum
Data Interface
RS232 cable, RJ45 connector
Batteries Type
2 – 4 18650 cell Li-Ion pack with protection circuit
Battery Life
500 full discharge cycles
Charge Time
5 hours from full discharge
Charger Type
Smart Microcontroller based
Software
XP Standard Generic UPS driver
Size
6” x 3.1” x 1.7” (152mm x 79mm x 43mm)