**Consult with your local contractor and local building codes for foundation.
An example would be, for normal soil conditions a simple foundation would be a 30-
inch diameter footing, 3’-0” deep
(in the ground), reinforced with (6) #7 (grade 60) vertical rebar equally spaced around the perimeter. Three inches
of clear distance between rebar and bottom/side edges of the foundation, 2-inches at top. Concrete minimum 28-
day compressive strength is 4,000 psi. Pole connecting anchor rods should have minimum 12-inches of
embedment.
Optional:
35000-79W-CFPA
j-hook kit can be purchased to
be used in footing. Kit will help
keep the proper spacing
needed to bolt pole to
concrete.
Baseplate
mount pattern.