3.1.3. CLEARANCE FROM COMBUSTIBLE MATERIALS
MINIMUM CLEARANCE WITH COMBUSTIBLE MATERIALS
Glass doors to opposite walls
- All models
42" (107 cm)
Vent to walls - All models
3" (8 cm) for the first 8 ft. of vent
(unless protected by a firewall) and 1"
(25.4 mm) for the rest of the vent.
Top of fireplace to ceiling
- All models
21¼" (54 cm)
Back of fireplace to adjacent material
- Models: LOO, MISTRAL, AUSTER
MOUSSON, and SIROCCO
0" (0 mm)
WARNING
A combustible surface located above the visible faces of the fireplace must not overhand these
faces by more than 3/4” (2 cm). A surface exceeding this limit is considered a mantle and must
comply with the requirements on shelves described in section 3.1.5 of this manual.