Information/Alarms
6 720 645 172
(2010/07) en
31
5.6.8
Failure on sensor T10 (B)
Failure on sensor T11 (B)
Function:
The sensor's value is indicated with NaN in the
control unit.
Heat pump:
All.
B
Check the installation of the sensor.
B
Check the connection, measure the resistance and
compare with the resistance table.
B
Replace the sensor if necessary.
5.6.9
Operating error compressor (B)
Function:
No operation response from the compressor.
E21: Additional heat permitted to start.
Heat pump:
All.
B
Use the relevant wiring diagram for the heat pump
and follow the operation response signal from the
control unit via connected components.
B
Identify where the signal is interrupted incorrectly.
5.6.10 Operating error add. heat (B)
Function:
With internal electric additional heat, the
overheat protection has tripped. With external
additional heat, thermostat E71.E1.B31 has not given a
signal within 30 minutes of additional heat operation.
Heat pump:
E21.
B
Check additional heat and overheat protection/
thermostat.
5.6.11 Operating error pump G2 (B)
Operating error pump G3 (B)
Function:
The compressor is stopped. Activated when
the SSM signal from the circulation pump has been
broken for more than 3 minutes. E21: Internal electric
additional heat is permitted to start at operating error
G3.
Heat pump:
All.
B
Interrupt the current for at least 5 seconds to reset
the alarms (
Æ
Chapter Resetting the pump alarm in
the installation guide for the heat pump).
B
Check that the circulation pump can operate.
B
Check the connection for the 0-10V signal.
B
Vent the heating system if necessary.
5.6.12 High temp. T6 hot gas (B)
Function:
The compressor is stopped because T6 shows
more than 125 °C. Restart is permitted when T6 shows
less than 115 °C. E21: Additional heat permitted to start.
Activated when the corresponding category C-alarm has
occurred more than once during the last 120 minutes.
Heat pump:
All.
B
Check that the sensor shows a reasonable value.
B
Check the connection, measure the resistance and
compare with the resistance table.
B
At correct sensor, check that the refrigerant circuit
can dispose of the heat.
5.6.13 Tripped high pressure switch (B)
Function:
The compressor is stopped. E21: Additional
heat permitted to start.
Activated when the corresponding category C-alarm has
occurred more than once during the last 120 minutes.
The alarm can also be caused by a faulty system
configuration.
Heat pump:
All.
B
Check the particle filter and clean if necessary.
B
Check the valves.
B
Check the heating system pressure, vent if necessary.
B
Check the flow over the condenser.
B
Check the pressure switch and its connections.
B
Check heat carrier pump G2.
B
Ensure that there is no risk of large sudden
temperature increases across the heat pump.