Settings
6 720 645 172 (2010/07) en
22
In
Own heat
curve
Own heat curve
Actual v.
:
Set point
:
Settings
>
Own heat curve
P:
I:
Deviation
:
Pump
:
Display
0 °C
0
0
0 K
Off
Winter
,
Summer
,
Off
,
On
E21
B
Set the heat curve that shall apply for the unit in
Set point curve
.
B
Set appropriate values for P and I.
B
Set the temperature deviation that shall cause an alarm
Accessory x temp. deviation
(
Æ
Chapter 5.6.51, page 36).
B
Enter pump function.
Winter
means that the accessory circulation pump is in operation during winter
operation.
The unit uses an externally connected sensor to control a 0-10V connected mixing valve to maintain
the set point value according to settings in
Set point curve
.
In
E11 heat
curve
E11 heat curve
Actual v.
:
Offset
:
Settings
>
E11 heat curve
P:
I:
Deviation
:
Pump
:
Display
0 K
0
0
0 K
Off
Winter
,
Summer
,
Off
,
On
E21
B
Set appropriate values for P and I.
B
Set the temperature deviation that shall cause an alarm
Accessory x temp. deviation
(
Æ
Chapter 5.6.51, page 36).
B
Enter pump function.
Winter
means that the accessory circulation pump is in operation during winter
operation.
The unit uses an externally connected sensor to control a 0-10V connected mixing valve to maintain
the set point value according to the heat curve for E11.T1.
In
Fixed sp
cooling
Fixed sp cooling
Actual v.
:
Set point
:
Settings
>
Fixed sp cooling
P:
I:
Deviation
:
Pump
:
Display
0 °C
0
0
0 K
Off
Winter
,
Summer
,
Off
,
On
E21
B
Set the fixed set point value that must apply.
B
Set appropriate values for P and I.
B
Set the temperature deviation that shall cause an alarm
Accessory x temp. deviation
(
Æ
Chapter 5.6.51, page 36).
B
Enter pump function.
Summer
means that the accessory circulation pump is in operation during
summer operation.
The unit uses an externally connected sensor to control a 0-10V connected mixing valve to maintain
the stated fixed set point value.
Setting
Factory
Range
HP
Tab. 37 Accessory
Summary of Contents for Rego 5101
Page 1: ...Installation Manual Rego 5101 ok 6 720 641 739 37 1I 6 720 645 172 2010 07 en...
Page 38: ......
Page 39: ......
Page 40: ......