IVAR UNIMIX Manual Download Page 3

UNIMIX

 is an innovation in the panorama of floor-mounted system adjustment groups. This mixing system sets the temperature of the 

fluid in the primary circuit (boiler) to the adjustable value required in the secondary circuit (heating panel).
UNIMIX is a modular group that can be connected directly and easily to our manifolds for panelled plant. Using a circulator with 130 mm 
centres allows connection to our manifolds mounted on supports with 200 mm centres, while a circulator with 180 mm centres requires 
the use of 250 mm brackets (Article AC 611).
The system can be easily powered from below or from the side by means of our angle ball valves AC 655, thereby ensuring for installa-
tion technicians convenient assembly in all possible configurations.
The versatility of this group is highlighted in the case of mixed-circuit systems: high temperature (radiator system) and low tempera-
ture (panelled heating system). 
This is the classic example in homes with floor general heating and bathroom radiators (towel warmers, etc.). To implement this 
system, simply connect to the UNIMIX inlet the new high temperature distribution kit including fill-empty cocks, delivery and return 
manifolds with simple branches for radiators, the over-pressure differential valve.
There are two different high temperature systems:
1.

High temperature kit with micrometric balancing valves and electro-thermal  heads  driven inserts with M24x1.5 or Eurokonus 
off-takes. Those kits are also available complete of  straight or angle ball valves for the connections to the primary circuit..

2.

High temperature simple distribution manifold  with M24x1.5 or Eurokonus off-takes. Those kits are available also complete 
of  straight or angle ball valves for the connections to the primary circuit.

The UNIMIX system can operate in the following two ways:
a.

with fixed-point adjustment using a thermostatic head with immersion probe and adjustable temperature (30°C - 50°C)

b.

with adjustment of the delivery temperature in relation to thermal load variations. The System can be equipped with 24 VAC 
axial movement motors (Article SRV 24) with pilot voltage of 0-10 V or with a 24 VAC 0-10V electro-thermal motor (Article TE 
3061), both of which can be piloted through the DHCC100 or the WLM2-1FS electronic adjustment control units with offsets 
for external temperature.

UNIMIX

 ist ein innovatives System, das sich gegenüber anderen Regelsystemen für Fußbodenheizungen dadurch auszeichnet, dass es 

zunächst die Temperatur des vom Heizkessel gelieferten Wassers auf einen günstigen Wert bringt, der dann im Sekundärkreis (Heiz-
platten) weiter verstellbar ist.
UNIMIX ist modular aufgebaut und kann auf einfache Weise direkt an unseren Verteilern für Heizplattenanlagen angeschlossen werden. 
Bei Verwendung einer 130-mm Umlaufpumpe ist die Montage auf den Halterungen von 200 mm Länge möglich, während 180-mm 
Umlaufpumpen die Verwendung 250 mm langer Halterungen (Art. AC 611) erfordern.
Das System kann mittels unserer abgewinkelten Kugelhahnen AC 655 sowohl von unten als auch von der Seite versorgt werden, was 
dem Montagepersonal jede gewünschte Einbaukonfiguration ermöglicht.
Die Vielseitigkeit dieser Regelgruppe erweist sich insbesondere beim Einsatz mit gemischten Systemen, bei denen ein Hochtemperatur-
kreislauf (Heizkörpersystem) mit einem Kreislauf niedrigerer Temperatur (Heizplatten einer Fußbodenheizung) in Verbindung steht.
Dies ist zum Beispiel oft in Wohnungen der Fall, in denen eine Fußbodenheizung, jedoch auch zusätzliche Heizkörper im Bad (Hand-
tuchwärmer etc.) vorhanden sind. Zur Erstellung eines solchen Systems ist am Eingang des UNIMIX einfach der neue Hochtemperatur-
Versorgungssatz mit Füll- und Ablasshähnen, Vor- und Rücklaufverteilern und Überdruckdifferenzialventil anzuschließen, der in zwei 
Versionen verfügbar ist:

1.

Hochtemperatursatz mit Mikrometer-Ausgleichventilen und motorisierbarem Absperrventil mit elektrothermischem Kopf 
und Ableitungsanschlüssen über M24x1,5-Gewinde oder Eurokonus. Für den Anschluss am Primärkreis sind gerade oder 
abgewinkelte Kugelhahnen verfügbar. 

2.

Einfache Hochtemperaturverteiler mit M24x1,5- oder Eurokonus-Verschraubungen, wobei auch hier für den Anschluss am 
Primärkreis gerade oder abgewinkelte Kugelhahnen verfügbar sind.

Das UNIMIX-System kann auf die folgenden zwei Arten betrieben werden:
a.

mit Einstellung auf einen festen Sollwert mittels eines Thermostatkopfes mit Tauchsonde, der im Temperaturbereich 30°C - 
50°C verstellbar ist,

b.

mit Einstellung der Vorlauftemperatur in Einklang mit Änderungen der Wärmebelastung. Das System kann mit 24 V AC Line-
armotoren (Art. SRV 24) mit Steuerspannung 0-10 V oder mit einem elektrothermischen Stellantrieb für 24 V AC 0-10 V (Art. 
TE 3061) ausgestattet werden. In beiden Fällen ist eine Steuerung durch die elektronischen Steuermodule DHCC100 oder 
WLM2-1FS möglich mit Ausgleich für die Außentemperatur.

IVAR_UNIMIX_E_DE.indd   3

05-11-2008   10:04:10

Summary of Contents for UNIMIX

Page 1: ...UNIMIX IVAR_UNIMIX_E_DE indd 1 05 11 2008 10 04 07 ...

Page 2: ...tat mit Tauchsonde Einstellbereich 20 60 C 14a Fest kalibrierter Sicherheitsthermostat 55 C T1 T2 Thermometer 1 three way mixing valve thermostatically operated or motor driven without having to replace the insert 1a thermostatic head with remote immersion probe adjustment field 30 50 C 1b electro thermal head 24 VAC proportional 0 10 V 1c axial servo motor 24 VAC proportional 0 10 V 2 primary byp...

Page 3: ... System das sich gegenüber anderen Regelsystemen für Fußbodenheizungen dadurch auszeichnet dass es zunächst die Temperatur des vom Heizkessel gelieferten Wassers auf einen günstigen Wert bringt der dann im Sekundärkreis Heiz platten weiter verstellbar ist UNIMIX ist modular aufgebaut und kann auf einfache Weise direkt an unseren Verteilern für Heizplattenanlagen angeschlossen werden Bei Verwendung...

Page 4: ...aturfühler temperature sensor Temperatur und Druckmessung thermo manometer Thermometer thermometer Pumpe pump Ausgleichsventil balancing valve Thermostatisch betriebenes oder motorisierbares 3 Wege Mischventil termostatically operated or motorizable 3 ways mixing valve Sicherheitsthermostat safety thermostat Fig 2a Fig 2b IVAR_UNIMIX_E_DE indd 4 05 11 2008 10 04 13 ...

Page 5: ...denen der Heizkessel für den korrekten Betrieb die Rückführung geringerer Mengen erfordert Betriebsbedingungen Höchsttemperatur im Primärkreis 90 C Maximaler Betriebsdruck 10 bar Principle of operating Unimix is a mixing system involving the hydraulic circuit shown in Figure 2a 2b The group is distinguished by completeness all neces sary accessories for correct adjustment and optimal operation are...

Page 6: ...edrige Temperatur werden ohne Pumpe und ohne Verteiler geliefert Mixing kits are supplied without a pump and without distribution manifolds for low temperature Verteilerbausätze für hohe Temperatur High temperature distribution kits Hochtemperatur Verteiler für UNIMIX mit abgewinkelten Kugelhahnen und Thermometern für den Anschluss am Primärkreislauf von unten Hochtemperatur Verteiler für UNIMIX m...

Page 7: ...le micrometric adjustment on delivery and cut out val ves on return Angle ball valves for low level connec tion to the primary circuit High temperature manifold for UNIMIX with double micrometric adjustment on delivery and cut out val ves on return Straight ball valves for lateral connec tion to the primary circuit Art Nr Code Anschlussverbindungen Offtakes Kugelhahnen Ball valves 500635 M 24 x 1 ...

Page 8: ... mit Anschlüssen für Verteiler AC 666 Einstellbereich 0 2 0 6 bar Art Nr 500126 für 200 mm Verteiler Art Nr 500126L für 250 mm Verteiler Differential bypass valve with terminals for manifold AC 666 Adjustment range 0 2 0 6 bar Code 500126 for manifolds with centres 200 mm Code 500126L for manifolds with centres 250 mm Vorverdrahtete Sicherheitsthermostate Pre wired safety thermostats Art Nr 580000...

Page 9: ...re kit To ensure correct installation it is advisable to fit ball valves with a G male terminal joint on the input and output of the UNIMIX system in order to facilitate eventual maintenance work These Valves red and blue are already included in the kits with code 500438S code 500438D Make sure the delivery and return are connected correctly as shown Figure A Example B mixed radiant and flooring h...

Page 10: ...fied person nel IMPORTANT if a traditional fixed speed or three speed pump is used it is strongly advi sed to fit a differential overpressure bypass to the secondary circuit Article AC 666 for example can be easily installed as a terminal on the distribution manifolds Take great care as regards the assembly direction of the bypass valve the kit must be positioned so that the black knob is on the r...

Page 11: ...ung auf einen festen Sollwert mittels des Thermo statkopfes und eine modulierte Regelung bei Verwendung eines Antriebs Der Thermostat kopf oder elektrothermische oder elektromechanische Antrieb ist wie in Abbildung M gezeigt auf dem 3 Wege Kolbenmischventil 1 zu montieren Hierzu muss die weiße Schutzkappe entfernt und an ihrer Stelle der Kopf oder Antrieb angeschlossen werden Die Muffe ist hierbei...

Page 12: ...spiel B Die Vorlauftemperatur liegt unter der projektierten Einstellwert In diesem Fall ist der Bypass 3 im Sekundär kreis langsam zu schließen ist bis sich die Vorlauftemperatur auf den projektierten Einstellwert stabilisiert Beispiel C Die Vorlauftemperatur ist höher als der projektierte Einstellwert In diesem Fall ist die Temperatureinstellung des Heizkessels wenn möglich zu senken und die Kali...

Page 13: ...put required in maximum load conditions Two different situations are outlined where the drop in pressure on the mixer valve and the secondary balance bypass are respectively 100 mbar and 150 mbar By adding this value to the losses of load in the worst case loop it is possible to calculate the minimum head of the circulation pump In order to select the most appropriate pump add the capacity head an...

Page 14: ...sition mit einem x markieren Abb Q2 4 Den Schraubenzieher auf das x ausrichten und dann einige Umdrehungen öffnen Abb Q3 wie in der Grafik p Q des Sekundär Bypass ersichtlich ACHTUNG Die Anzahl der Umdrehungen entspricht denjenigen des Verriegelungsstiftes 5 Dann die große Schraube bis zum Anschlag losschrauben Abb Q4 Die Voreinstellung ist nun durchgeführt und ändert sich nicht auch nicht nach wi...

Page 15: ...en haben einen Hilfskontakt zur Abschaltung der Umlaufpumpe Sind sie alle parallel geschaltet so schalten sie die Pumpe ab wenn alle Bereiche zufrieden stellend versorgt wer den An ihrer Stelle können auch elektrothermische Köpfe für 24 V AC mit zwei Leitern Art Nr 501524 mit einem Wiring Centre ZC 100 Art Nr 580004 verwendet werden die bei einer Schließung aller Bereiche die Pumpe abschalten Die ...

Page 16: ...ectly to the instruction booklet included in the packaging of the heads modulating adjustment TAB B it is advised to fit the conditioning adjustment control units in a vertical position to reduce overall dimensions In this case fit electro thermal heads to the return manifolds with two leads with power supply 230 VAC consent to switch off the secondary pump is given directly by the control panel t...

Page 17: ...IVAR_UNIMIX_E_DE indd 17 05 11 2008 10 04 53 ...

Page 18: ...IVAR_UNIMIX_E_DE indd 18 05 11 2008 10 04 57 ...

Page 19: ...IVAR_UNIMIX_E_DE indd 19 05 11 2008 10 04 58 ...

Reviews: