Page 1 of 9
07/18
iVQ-E to R Range Adjustment and Calibration Manual
1.
Modulating Control and Position Feedback Option Supplied:
This manual provides necessary information for calibrating the modulating control board and making any
fine tune adjustments to iVQ-E to R Range actuators. Each unit is shipped with initial calibration and factory
settings complete for a 0° to 90° operation.
If changes were made to the OPEN/CLOSE (CCW/CW travel) limit switches or new settings wish to be made,
the following steps must be followed for proper calibration of the unit:
1.
Confirm actuator setup via the “DIP Switch Setting Chart”.
2.
Confirm actuator performance via the “Deadband Setting Dial”.
3.
Reset the potentiometer via “Potentiometer (VR) Adjustment”.
4.
Reset the OPEN and CLOSE positions via “OPEN/CLOSE Calibration Procedure”.
5.
Also refer to the “Troubleshooting Chart” at the end of this manual for additional help.
Modulating Control and Position Feedback Board Layout
DIP Switch
VR2
Deadband Setting Dial
LED’s 1 to 9
Output Signal
Connection
Input Signal
Connection
Incoming
Power
Connection
PB - MODE
PB - DN
PB - SET
PB - UP
-/N
+/L
-
12+
11-
6-
7+