IAI3002B-01
Page 7 of 9
07/18
Position Feedback Instructions
For this option, the following steps need to be performed:
1)
Confirm the required output signal via the DIP switch settings below:
DIP Switch Setting Chart for D1
1
2
3
4
5
6
Default
OFF
ON
OFF
OFF
OFF
OFF
0-20mA
ON
OFF
OFF
OFF
OFF
OFF
4-20mA
OFF
ON
OFF
OFF
OFF
OFF
0-5V
OFF
OFF
ON
OFF
OFF
OFF
1-5V
OFF
OFF
OFF
ON
OFF
OFF
0-10V
OFF
OFF
OFF
OFF
ON
OFF
2-10V
OFF
OFF
OFF
OFF
OFF
ON
DIP Switch Setting Chart for D2
2)
To enter the setting mode, press and hold ‘PB1’ and ‘PB2’ simultaneously, ‘LED CCW OPEN’ and ‘LED CW
CLOSE’ will begin to flicker.
3)
Operate the actuator to the fully CCW OPEN position and press ‘PB2’, ‘LED CCW OPEN’ will flicker rapidly
for about 2 seconds. The fully CCW OPEN position is now set.
4)
Check output signal at terminals 8 & 9 or terminals 8 & 10 depending on the DIP Switch setting selected.
5)
Operate the actuator to the fully CW CLOSE position and press ‘PB1’, ‘LED CW CLOSE’ will flicker rapidly
for about 2 seconds. The fully CW CLOSE position is now set.
6)
Check output signal at terminals 8 & 9 or terminals 8 & 10 depending on the DIP Switch setting selected.
7)
Press and hold ‘PB1’ and ‘PB2’ simultaneously to exit the setting mode.
1
2
3
Default
OFF
OFF
OFF
0-20mA/4-20mA
OFF
OFF
OFF
0-5V/1-5V
ON
ON
OFF
0-10V/2-10V
ON
OFF
ON
OFF
ON
ON
OFF