IAI3002B-01
Page 2 of 9
07/18
DIP Switch Setting Chart (Factory Setting is shown in RED)
Switches 1 and 2 correspond to the input signal setting, switches 3, 4, and 5 correspond to the output
signal setting, and switches 6, 7, and 8 correspond to the actuator command settings. If any changes are
made, turn OFF power and restart to activate the changes.
DIP Switch Setting Options
1
2
3
4
5
6
7
8
Functions
ON
OFF
4-20mA Signal Input
OFF
OFF
1 -5V Signal Input
OFF
ON
2-10V Signal Input
OFF
ON
OFF
4-20mA Signal Output
ON
OFF
ON
2-10V Signal Output
OFF
Direct Acting Mode (See graph)
ON
ON
Stay in place on Loss of Input Signal
OFF
ON
CW on Loss of Input Signal
ON
OFF
CCW on Loss of Input Signal
ON
Reverse Acting Mode (See graph)
ON
ON
Stay in place on Loss of Input Signal
OFF
ON
CCW on Loss of Input Signal
ON
OFF
CW on Loss of Input Signal
Direct Acting
Reverse Acting
20mA
20mA
Sign
al
Sign
al
4mA
4mA
0°-(CW)
(CCW)-90°
0°-(CW)
(CCW)-90°