Page 12
Operation and Maintenance
Envistar Top 04-21
DSET.190501.01.EN
Continuous product development may give rise to specification changes without notice.
3.3 EcoCooler cooling unit (code TEC)
Envistar Top with EcoCooler (code TEC) size 10
The integrated cooling unit with EcoCooler (code TEC) cooling recovery
is available as an optional extra to an Envistar Top unit with a rotary heat
exchanger. Cooling recovery means that the heat exchanger starts up when the
extract air/room temperature drops below the outdoor temperature and cooling
is required.
The unit has an electronic expansion valve, rotary compressor size 04, scroll
compressor size 06-12 and reciprocating compressor size 16-21.
Compressor
Power control takes place with a speed-controlled compressor. When
increased cooling is required, the frequency inverter increases the speed of the
compressor.
Compressor protection
In the event of an alarm initiated by the frequency inverter or the safety circuit,
the compressor stops and an alarm indication is given. If the unit is equipped
with control equipment, the alarm can be read on the Climatix display.
In the event of an alarm, correct the fault and then reset the alarm. If the safety
circuit alarm trips repeatedly, an authorised refrigeration service company must
be called in.
For size 04-12
The safety circuit consists of a high pressure switch (HP), which protects by trip-
ping when there is high pressure in the system. Use the manual reset button on
the pressure switch to perform a reset.
For size 16-21
The safety circuit consists of a low pressure control and a high pressure switch
with a manual reset button. The safety circuit can trip for two different faults:
• High pressure in the system, HP (manual reset on the pressure switch)
• Low pressure in the system, LP (resets itself automatically)