Page 36
Operation and Maintenance
Envistar Top 04-21
DSET.190501.01.EN
Continuous product development may give rise to specification changes without notice.
Filter data
For filter data, refer to
under Documentation at
. Actual filters are shown in Technical data (see
the page Material specification) and Spare part list under order unique
documentation at
.
Filter replacement
WARNING!
Risk of harmful dust when changing filter.
Use a dust mask to avoid inhaling dust.
1. Shut down the unit via the service switch in the control equipment, safety
switch in the 0 position.
NB:
The safety switch is not designed for starting/stopping the unit. Always
use the control equipment to start and shut down the unit.
2. Wait until the fans have stopped, then open the inspection door.
WARNING!
Positive pressure inside the unit, risk of personal injury. Allow
the pressure to drop before you open the inspection doors.
3. Loosen the eccentric rails.
4. Remove the old filter by pulling it towards you. Discarded filters should be
disposed of correctly. The carbon filters are combustible in their entirety.
5. Clean the filter cabinets.
6. Install the new filter, press in the eccentric rails to engage them and close
the inspection door.
7. Reset the FLC filter control function via the Climatix display, refer to separate
Climatix control documentation. (Only applicable to the Home Concept ver-
sion of the unit equipped with carbon filter and integrated control equipment
(code MX).)
8. Start the unit.
Example eccentric rails