High pressure switch alarm
If the high pressure switch has tripped, “Cooling unit alarm: Alarm” is displayed.
Since the inverter loses all power when the high pressure switch is tripped, a
communication error alarm is also displayed, “Com.Modbus alarm Danfoss:
Alarm”.
Alarm reset
• Manually reset alarms caused by a tripped high pressure switch by pressing
the red button on the pressure switch.
• Reset alarms from the inverter or the compressor by turning off the power to
the unit (inverter) for at least 1 minute.
Reset button for
pressure switch