Operation and Maintenance
Envistar Compact
DSEC191101.01.EN
Continuous product development may give rise to specification changes without notice.
For the standard version: To ensure correct function of the purging sector,
the negative pressure at P3 should be greater than the negative pressure at
P2 (min. diff. 25 Pa). Otherwise an ETET-TR trim damper can be used on the
extract air side in order to throttle in the correct pressure balance.
–
+
P1
P4
P3
P2
-100
-125
–
+
25 Pa
P
≈
1 atm
(101 kPa)
Trim damper
9. Check the differential pressure across the rotor. The purging sector is fac-
tory-installed, set to the maximum open position. Depending on the unit’s
pressure difference across the rotor, the purging sector may need adjust-
ment. An incorrect setting may impair the efficiency. Inspection and adjust-
ment should be carried out as follows:
- Measure and write down the differential pressure between the outdoor air
(P1) and the extract air (P3).
–
+
P1
P4
P3
P2
xx Pa
see table
below
Purging sector