Filter replacement
1. Shut down the unit via the service switch in the control equipment, safety
switch in the 0 position.
NB:
The safety switch is not designed for starting/stopping the unit. Always
use the service switch in the control equipment to start and shut down
the unit.
2. Wait until the fans have stopped, then open the inspection door.
WARNING!
Positive pressure inside the unit, risk of personal injury. Allow
the pressure to drop before you open the inspection doors.
3. Release the eccentric rails.
4. Remove the old filter by pulling it towards you.
5. Clean the filter cabinets.
6. Install the new filter, press in the eccentric rails to engage them and close
the inspection door.
7. Reset the FLC filter control function via the Climatix display, refer to sepa-
rate Climatix control documentation. (Only applicable to the Home Concept
version of the unit with carbon filter and integrated control equipment (code
MX).)
8. Start the unit.
Eccentric rails inside the unit