ManagerIQEasy_UM_9752103002_GB_V3_1
141
Fieldbus “
IP Address
”
indicates 0.0.0.0.
Fieldbus no address entered. Give the Fieldbus module a
valid network address. See
Section 6.31.2.2.
Network cable not connected.
Connect the network cable and
restart the Manager IQ Easy.
Fieldbus address has been
entered. There may be an
address conflict.
Check whether a duplicate
address has been assigned in
the network.
The Fieldbus “
IP
Address
” does not match
the actual address.
The DHCP server has
assigned a new IP address
to the Fieldbus module.
Close and restart the Manager
IQ Easy.
After starting up, the
message “
Invalid
shutdown
” is always
shown on the screen.
Operator error.
The Manager IQ Easy is
switched off in the wrong way.
See Section 6.16 for the correct
procedure.
The HMI software has
unexpectedly closed.
Check if you are using the
latest software version.
Update to the latest software
version otherwise contact your
Simco-Ion agent.
Data is not saved onto the
USB flash drive.
USB stick is not recognised. Power down / power up with
USB in the Manager.
TODO_RF: I don’t understand
this action.
The connection cable between
the HMI and the Backplane
has been disconnected.
Check the connection cable
between the HMI and the
Backplane.
The USB is formatted with
a file system that is not
supported by the HMI.
Provide a USB stick with FAT16
file format.
Folder “log files” is not
present in the root path of
the USB stick
Create a folder “log files”
directly in the root path
TODO_RF: The folder is
created automatically.
Message on the screen
“
USB IS UPDATE USB
”.
Remove the folder “Update”
from the root of the USB stick.
Format the USB stick.
Use a different USB stick.
FTP address is not
opened in the browser
Cabling error.
Check the cabling and/or RJ45
connectors.
Address displayed in settings
is an outdated address.
Make sure the Manager IQ
Easy is connected to the network,
power down, power up and
read the IP address again.
Enter this address in the browser.
FTP client cannot connect
to the Manager IQ Easy.
Wrong IP address used.
Enter the correct IP address of
the Manager IQ Easy in the
FTP client.
Wrong username or
password used.
Enter the correct username and
password in the FTP client.