STEP 4 - Control Wiring

• To prevent electrical shock, turn off the electrical power before making electrical connections.

• This low water cut-off must be installed in series with all other limit and operating controls installed on the 

boiler. After installation, check for proper operation of all of the limit and operating controls, before leaving 
the site.

• All work must be performed by qualified personnel trained in the proper application, installation, and 

maintenance of plumbing, steam, and electrical equipment and/or systems in accordance with all applicable 
codes and ordinances.

Failure to follow this warning could cause electrical shock, an explosion and/or fire, which could result in 
property damage, personal injury or death.

!

WARNING

OFF

ON

a.

Turn off all power to boiler and boiler controls.

b.

Electrical Conduit Connection

• Connect electric conduit using knockouts provided.

• Follow accepted electrical practices when installing fittings and making connections.

• Refer to and follow local codes and standards when selecting the types of electrical fittings and conduit.

c.

Based on the Boiler’s Control Circuit voltage and the required input voltage of the LWCO, select proper

wiring diagram and proceed to that page.

Boiler manufacturer schematics should always be
followed. In the event that the boiler manufacturer’s
schematic does not exist, or is not available from
the boiler manufacturer, refer to the schematics
provided in this document.

!

IMPORTANT

To prevent an electrical fire or equipment damage,
electrical wiring must have a rating of 167˚F (75˚C) if the 
liquid's temperature exceeds 180˚F (82˚C).
Failure to follow this warning could cause property 
damage, personal injury or death.

!

WARNING

Models with Red (low water) and Amber Lights (test)

Models with Red (low water) and Green (power) Lights

LWCO Model

Boiler Circuit Voltage

Page

LWCO Model

Boiler Circuit Voltage

Page

PS-802-24

24V using Harness

7

PS-802-24

24V using Harness

7

PS-802-24

24V using Terminals

7

PS-802-24

24V using Terminals

7

PS-852-24

24V using Harness 

7

PS-852-24

24V using Harness

7

PS-852-24

24V using Terminals

7

PS-852-24

24V using Terminals

7

Do not use "manual reset" models with electric automatic water feeders.

Failure to follow this caution can cause flooding and property damage.

!

CAUTION

Summary of Contents for McDonnell & Miller PS-802 Series

Page 1: ...in series with all other limit and operating controls installed on the boiler After installation check for proper operation of all of the limit and operating controls before leaving the site We recom...

Page 2: ...arm or automatic water feeder Control Voltage 24 VAC HZ 50 60 Probe Sensitivity For models with red low water and amber test lights 3 000 ohm For models with red low water and green power lights 7 000...

Page 3: ...iler manufacturers instructions to determine suitable tapping for the probe For Hot Water Boilers 1 Refer to boiler manufacturers instructions to determine suitable tapping for the probe 2 Locate prob...

Page 4: ...following steps 1 Using a level draw a horizontal line at the location and mark two positions 1 1 4 31 75 mm apart on the horizontal line 2 Drill a 0 113 dia hole 1 2 13 mm deep in each position on t...

Page 5: ...of the probe and tighten the wing nut to 1 2 ft lb 65 N m 3 Using a flathead screwdriver attach a suitable green 16 AWG wire not provided to the green ground screw X provided at the base of the probe...

Page 6: ...s of electrical fittings and conduit c Based on the Boiler s Control Circuit voltage and the required input voltage of the LWCO select proper wiring diagram and proceed to that page Boiler manufacture...

Page 7: ...internal wiring Connect plug A of wiring harness to receptacle B Check to make sure factory supplied jumper is installed between terminals H and C PS 802 852 using Harness Connection PS 802 852 using...

Page 8: ...e amber LED BB glows dimly the water level is above the probe 2 If the amber LED BB is off the water level may be below the probe or the water is too pure and may require the addition of boiler water...

Page 9: ...r with a manual reset low water cut off Manually Testing Control For Series PS 802 PS 802 M with Red Low Water and Green Power Lights a Before filling the system turn on the electric power to the boil...

Page 10: ...Red light will remain ON The burner will remain OFF Testing Control Using Test Button continued b Now fill the boiler with water For Series PS 852 auto reset units only 1 When water touches the probe...

Page 11: ...ting Control Using Test Button e Depressing test button with water on probe manual reset units only Must depress and hold test button for more than 2 seconds to activate test cycle 1 When test cycle i...

Page 12: ...ensure adequate conductance Troubleshooting Replace Probe if Teflon insulator is cracked or worn Probe is loose Failure to follow this caution could cause property damage personal injury or death CAU...

Reviews: