20

down.  Once  the  high  pressure  condition
clears,  the  station  automatically  resets,  and
automatic operation resumes. The PLC allows
three  (3)  automatic  restarts  in  a  one-hour
period. At the fourth occurrence in a one-hour
period,  the  station  shuts  down  (hard  fault).
The red station fault light on the control panel
door  comes  on,  and  the  display  indicates  an
"Alarm  Shutdown  Alert."  Go  to  "Alarms,"  and
the  display  should  show  that  a  "High
Discharge Pressure fault" has occurred.

NOTE:

At  this  point,  shut  the  station  down,

and  determine  what  the  problem  is.  Consult
the Troubleshooting section of this manual for
assistance.

To clear the fault, press the Reset button.

Low Inlet Pressure

This  optional  safety  is  usually  used  on
flooded-suction booster pump applications.

Normally, a pressure  switch monitors the inlet
pressure  on  the  "suction"  side  of  the  pump.
This switch is located in a box on the lower left
side of the control cabinet. The switch is used
in  conjunction  with  a  relay  to  inform  the  PLC
that  it  is  unsafe  to  run.  Setting  the  low  inlet
pressure 

condition 

is 

accomplished 

by

physically  adjusting  the  pressure  switch.
There is a 20 second time delay in the PLC.

Once  the  inlet  pressure  drops  below  the
switch  pressure  setting,  all  pumps  shut  down
after  a  20  second  delay.  Once  the  low  inlet
pressure 

condition 

clears, 

the 

station

automatically  resets  and  automatic  operation
resumes.  The  PLC  allows  three  (3)  automatic
restarts  in  a  one-hour  period.  At  the  fourth
occurrence  in  a  one-hour  period,  the  station
shuts  down  (hard  fault).  The  red  station  fault
light on the control panel door comes on, and
the  display  indicates  an  "Alarm  Shutdown
Alert." Go to "Alarms," and the display should
show  that  a  "Low  Inlet  Pressure  fault"  has
occurred.

  WARNING: Low Inlet Pressure – Station
  Shutdown Hazard

At this point, shut the station down, and determine
what  the  problem is.  Consult  the  Troubleshooting
section of this manual for assistance.

Failure  to  follow  these  instructions  could  result  in
serious  personal  injury,  death,  or  property
damage.

There  are  two  dials  on  the  pressure  switch.
The  one  on  the  top  is  the  correct  adjustment.

Turn  clockwise  to  increase  the  pressure
setpoint, counter-clockwise to decrease.

CAUTION: Delta Pressure Setting Hazard

Do  not  adjust  the  bottom  dial.  This  is  a  delta
pressure  setting,  and  is  not  used.  This  dial  must
be  adjusted  fully  counter-clockwise  (0  position). If
you  are  having  trouble  with  your  pressure  switch,
always verify that this dial is in the 0 (fully counter-
clockwise position) before adjusting the top dial.

Failure  to  follow  these  instructions  indicates  a
potentially  hazardous  situation,  which,  if  not
avoided, may result in property damage.

  WARNING: Minimum Pressure Setting
  Hazard

The  pressure  setting  is  based  on  the  minimum
pressure that the pump can safely operate. Do not
lower  the  pressure  switch  setting  without
consulting the factory

.

Failure  to  follow  these  instructions  could  result  in
serious  personal  injury,  death,  or  property
damage.

Loss of Prime

This  optional  safety  is  usually  used  on  end-
suction centrifugal pump applications.

A level probe is placed in the suction piping at
a  predetermined  level.  This  probe  works  in
conjunction with a relay to inform the PLC that
it  is  unsafe  to  run.  Fault  usually  signifies  a
malfunctioning foot valve.

After a second or two, all pumps shut down. If
the  loss  of  prime  condition  clears,  the  station
automatically  resets,  and  automatic  operation
resumes.  The  PLC  allows  three  (3)  automatic
restarts  in  a  one-hour  period.  At  the  fourth
occurrence  in  a  one-hour  period,  the  station
shuts  down  (hard  fault).  The  red  station  fault
light on the control panel door comes on, and
the  display  indicates  an  "Alarm  Shutdown
Alert."  Go  to  "Alarms"  and  the  display  should
show  that  a  "Loss  of  Prime  fault"  has
occurred.

NOTE:

At  this  point,  shut  the  station  down,

and  determine  what  the  problem  is.  Consult
the Troubleshooting section of this manual for
assistance.

To clear the fault, press the Reset button.

Summary of Contents for Flowtronex SIlent Storm

Page 1: ...Manual 19 001 200 Rev 0110 SILENT STORM VFD Pumping System Installation Operation Maintenance INSTALLER PLEASE LEAVE THIS MANUAL FOR THE OWNER S USE NOTE This product is not intended for use in potab...

Page 2: ...hor make no claim to these trademarks These include Microsoft Windows Windows NT ActiveX that are either registered trademarks or trademarks of Microsoft Corporation in the United States and or other...

Page 3: ...on 19 Manual Mode of Operation 19 Low Discharge Pressure 19 High Discharge Pressure 19 Low Inlet Pressure 20 Loss of Prime 20 Low Level Fault 21 Phase Failure 21 INDIVIDUAL PUMP FAULTS 21 Overload Pro...

Page 4: ...fected part of the product s Purchaser shall assume all responsibility and expense for removal reinstallation and freight in connection with the foregoing remedies The same obligations and conditions...

Page 5: ...damage All operating instructions must be read understood and followed by the operating personnel Flowtronex accepts no liability for damages or operating disorder which are the result of non complian...

Page 6: ...avy tools etc Wear other personal protective equipment to protect against hazardous toxic fluids Coupling Guards Never operate a pump without a coupling guard properly installed Never force piping to...

Page 7: ...st questions pertaining to its service Every attempt has been made to explain all facets of system operation and maintenance However should you have specific questions not addressed in this manual you...

Page 8: ...vy due to the position of the equipment Do not use component eyebolts to lift the pump station WARNING Falling Objects Hazard Eyebolts if provided are designed to lift only the components to which the...

Page 9: ...rical Code and local codes must be followed WARNING Electrical Shock Hazard Conduit grounds are not adequate A separate ground wire must be attached to the ground lug provided in the enclosure to avoi...

Page 10: ...d electrical shock Failure to follow these instructions could result in serious personal injury death or property damage Place the unit on its concrete foundation supporting it with steel wedges or sh...

Page 11: ...s properly installed it should not touch the side of the wet well Premature bearing failure or destruction of the bowl assembly can result from improper installation Figure 4 Position Head Over Access...

Page 12: ...e vertical hollow shaft motor to the top of the pump s disconnected head Refer to the Gould Pumps Model VIT Installation Operation Maintenance Instructions WARNING Falling Objects Hazard DO NOT work u...

Page 13: ...This switch position places the pump station in either Automatic VFD Bypass or Manual VFD Bypass mode of operation depending on the position of the MANUAL OFF AUTO switch In this mode the pumps will s...

Page 14: ...he screen during maintenance AUTO Causes the Lake Screen solenoid to open after the main VSP has been operating at least one minute the minimum flow requirement is met and the speed test is not trying...

Page 15: ...only apply to Combo 1 The values of 30 PSI and 90 seconds were intentionally selected since they are out of range and will never be used There are three 3 main types of auto operation line fill syste...

Page 16: ...s are set as follows from end of line fill mode System control switch AUTO Pump 1 switch ON Pump 2 switch ON Pump 3 switch ON PM Pump switch ON Override Active switch ACTIVE Low Discharge Pressure and...

Page 17: ...the inverter VFD speed immediately ramps up to the speed when lag pump stops setting This prevents the system pressure from dropping excessively due to the XL pump shutting off Once an XL pump has bee...

Page 18: ...er Adjust speed as required to maintain set point pressure NOTE When done turn OFF all pump switches and place system control switch in OFF Return Override Active switch to ACTIVE If the station can b...

Page 19: ...MUST be turned to the OFF position before selecting VFD bypass mode Operation is similar to normal automatic operation but the start stop sequences differ greatly The registers below regulate this NO...

Page 20: ...ens as required to maintain pressure As more flow is going out the PRV discharge less flow is actually being used When the flow reading drops below the flow setpoint to stop value the pumps shut down...

Page 21: ...e line communicates the downstream pressure to the PLC The PLC monitors downstream pressure to determine if the pressure is below the allowable range The standard PLC program defines low discharge pre...

Page 22: ...ng section of this manual for assistance Failure to follow these instructions could result in serious personal injury death or property damage There are two dials on the pressure switch The one on the...

Page 23: ...lears the station automatically resets and automatic operation resumes The PLC allows three 3 automatic restarts in a one hour period At the fourth occurrence in a one hour period the station shuts do...

Page 24: ...of this manual for assistance VFD Fault The VFD sends a fault signal 120 VAC directly to the PLC The display shows Inverter Fault This is normally a VFD fault To determine the nature of the problem yo...

Page 25: ...ontrol panel Black soot on or around the device indicates that it has taken a surge and needs to be replaced 3 Motor lubrication a If your motor has an oil bath thrust bearing you need to ensure that...

Page 26: ...the welds c Visually inspect the station for loose or damaged paint or areas of rust DANGER Personal Injury Hazard Pump station maintenance must be performed by properly trained and qualified personn...

Page 27: ...piping is completely drained 4 Drain all valve pilots including the sensing chamber and all pressure switches 5 Loosen valve bonnet bolts loosen the bonnet and drain the valve bonnet of water 6 Re tig...

Page 28: ...d Check the ball valve position and or blow out line System pressure transducer failure Replace the pressure transducer FlowNet One of main pump switches in OFF position All pumps not running Consult...

Page 29: ...nd clean the inlet screen Inspect probes for correct insertion depth Look for dirty or corroded probes To be performed by a qualified person only Look for broken probes probe holder or wires To be per...

Page 30: ...itor voltage set too high To be performed by a qualified person only Example monitor set at 480 V try 460 V To be performed by a qualified person only Check all input fuses One or more dead legs on a...

Page 31: ...ove MOTOR WON T START Cause Cure To be performed by a qualified person only The overload for that motor is tripped Reset adjust or replace as required Does the station have a high pump temperature opt...

Page 32: ...area of the golf course Calibration The act of or specific values used to scale the output of a measurement device to read real world values Canned turbine See vertical turbine Chemical injection The...

Page 33: ...ressure safety is an excellent choice for these systems Foot valve A device used primarily on horizontal lift applications to maintain pump prime Frequency Hz The number of oscillations per second of...

Page 34: ...in which pumps are allowed to produce more flow rate than the motor that drives them is designed for Also refers to a device in the control panel which detects this situation and stops the pump in ord...

Page 35: ...mal automatic operation Temperature switch This is a normally open or normally closed switch that changes output state when the temperature exceeds the setpoint of the switch Timed alternation One of...

Page 36: ...vent the pump volute prior to operation Failure to follow these instructions indicates a potentially hazardous situation which if not avoided may result in property damage Are the pump and driver sha...

Page 37: ...to follow these instructions could result in serious personal injury death and or property damage Are the feeder wires correctly sized for the load Is the unit properly grounded WARNING Conduit ground...

Page 38: ...BY ITT CORPORATION PRINTED IN U S A THE ITT ENGINEERED BLOCKS SYMBOL AND ENGINEERED FOR LIFE ARE REGISTERED TRADEMARKS OF ITT CORPORATION ITT Flowtronex Phone 800 786 7480 x1 service flowtronex com w...

Reviews: