background image

13

AUTOMATIC OPERATION

Overview

The  primary  benefit  of  Variable  Speed
Pumping  (VSP)  Systems  is  to  ensure  surge-
free  starts  and  stops  while  maintaining  a
constant  down-stream  line  pressure  with  no
mechanical  pressure-regulating  valve.  This
minimizes pipeline failures due to surges and,
not  incidentally,  reduces  the  utility  bill  for  the
station.

Automatic operation is selected by the system
control  switch.  In  automatic  operation,  all
pump  activity  is  determined  by  the  PLC.  The
position of the individual pump switch lets the
PLC know whether or not it is available to run.
In  most  cases,  all  pump  switches  are  in  the
ON  position.  When  a  pump  or  a  motor  is
removed  from  the  system,  turn  the  pump
switch  OFF,  and  the  PLC  will  not  try  to  run
that pump.

The  PLC  brings  one  pump  on  at  a  time  in
order  to  satisfy  the  start  criteria  (usually
setpoint 

pressure). 

Some 

stations 

are

designed  to  start  and  stop  the  pumps  based
on remote start signals, level probe signals, or
other  criteria.  The  standard  start  and  stop
sequence is as follows:

Pressure below setpoint to start
Combo 1

5 PSI

Delay time to start Combo 1

0 SEC

Pressure above setpoint to stop
Combo 1

5 PSI

Delay time to stop Combo 1

5 SEC

Pressure below setpoint to start
Combo 2

10 PSI

Delay time to start Combo 2

0 SEC

Pressure above setpoint to stop
Combo 2+

30 PSI

Delay time to stop Combo 2+

90 SEC

Pressure below setpoint to start
Combo 3+

5 PSI

Delay time to start Combo 3+

10 SEC

NOTE:

The  criteria  for  Combo  4  and  above

are the same as Combo 3.

The  "pressure  above  setpoint  to  stop"  and
"delay  time  to  stop"  parameters  only  apply  to

Combo  1.  The  values  of  30  PSI  and  90
seconds were intentionally selected since they
are out of range and will never be used.

There  are  three  (3)  main  types  of  auto
operation  –  line  fill,  system  charging,  and
normal operation.

Line Fill Mode

Line  Fill  Mode  is  used  when  downstream
pressure  is  significantly  below  setpoint,  such
as  during  the  initial  startup,  or  when  leaks  in
the lines are repaired. Operation is as follows
(performed in order):

System control switch: OFF

All Individual Pump switches: ON

Override/Active  switch:  LDP  Override
(Low Discharge Pressure fault disabled)

VFD Bypass switch: VFD

System control switch: AUTO

As soon as the system control switch is turned
to  the  AUTO  position,  the  VSP  (Variable
Speed  Pump)  with  the  lowest  run  time  starts
at a reduced speed. When the VSP starts, the
startup  ramp  in  the  program  lowers  the
setpoint 

to 

PSI 

above 

the 

actual

downstream  pressure.  The  VFD  adjusts  the
speed  of  the  VSP  to  reach  the  desired
setpoint. The  setpoint  ramps  up  at  the  rate  of
1  PSI  every  4  seconds  until  the  normal
setpoint is reached.

This feature prevents the VSP from coming up
to full speed too quickly, and prevents the lag
pump(s) from starting prematurely. This ramp-
up  feature  allows  the  system  to  develop  a
controlled  and  smooth  start  up  from  a
completely 

de-pressurized 

condition,

minimizing pipe breakage from water hammer.
Once  the  pressure  above  setpoint  value  is
reached,  the  VSP  shuts  down.  The  pump
switches  can  be  left  in  ON  and  the  system
control 

switch 

left 

in 

AUTO. 

The

Override/Active  switch  should  be  returned  to
the  ACTIVE  position.  The  station  is  now  in
system "charging" mode.

System Charging Mode

If  there  are  no  heads  open,  and  the  pressure
is  within  the  defined  range  of  operation,
pressure  may  slowly  drop  due  to  system

Summary of Contents for Flowtronex SIlent Storm

Page 1: ...Manual 19 001 200 Rev 0110 SILENT STORM VFD Pumping System Installation Operation Maintenance INSTALLER PLEASE LEAVE THIS MANUAL FOR THE OWNER S USE NOTE This product is not intended for use in potab...

Page 2: ...hor make no claim to these trademarks These include Microsoft Windows Windows NT ActiveX that are either registered trademarks or trademarks of Microsoft Corporation in the United States and or other...

Page 3: ...on 19 Manual Mode of Operation 19 Low Discharge Pressure 19 High Discharge Pressure 19 Low Inlet Pressure 20 Loss of Prime 20 Low Level Fault 21 Phase Failure 21 INDIVIDUAL PUMP FAULTS 21 Overload Pro...

Page 4: ...fected part of the product s Purchaser shall assume all responsibility and expense for removal reinstallation and freight in connection with the foregoing remedies The same obligations and conditions...

Page 5: ...damage All operating instructions must be read understood and followed by the operating personnel Flowtronex accepts no liability for damages or operating disorder which are the result of non complian...

Page 6: ...avy tools etc Wear other personal protective equipment to protect against hazardous toxic fluids Coupling Guards Never operate a pump without a coupling guard properly installed Never force piping to...

Page 7: ...st questions pertaining to its service Every attempt has been made to explain all facets of system operation and maintenance However should you have specific questions not addressed in this manual you...

Page 8: ...vy due to the position of the equipment Do not use component eyebolts to lift the pump station WARNING Falling Objects Hazard Eyebolts if provided are designed to lift only the components to which the...

Page 9: ...rical Code and local codes must be followed WARNING Electrical Shock Hazard Conduit grounds are not adequate A separate ground wire must be attached to the ground lug provided in the enclosure to avoi...

Page 10: ...d electrical shock Failure to follow these instructions could result in serious personal injury death or property damage Place the unit on its concrete foundation supporting it with steel wedges or sh...

Page 11: ...s properly installed it should not touch the side of the wet well Premature bearing failure or destruction of the bowl assembly can result from improper installation Figure 4 Position Head Over Access...

Page 12: ...e vertical hollow shaft motor to the top of the pump s disconnected head Refer to the Gould Pumps Model VIT Installation Operation Maintenance Instructions WARNING Falling Objects Hazard DO NOT work u...

Page 13: ...This switch position places the pump station in either Automatic VFD Bypass or Manual VFD Bypass mode of operation depending on the position of the MANUAL OFF AUTO switch In this mode the pumps will s...

Page 14: ...he screen during maintenance AUTO Causes the Lake Screen solenoid to open after the main VSP has been operating at least one minute the minimum flow requirement is met and the speed test is not trying...

Page 15: ...only apply to Combo 1 The values of 30 PSI and 90 seconds were intentionally selected since they are out of range and will never be used There are three 3 main types of auto operation line fill syste...

Page 16: ...s are set as follows from end of line fill mode System control switch AUTO Pump 1 switch ON Pump 2 switch ON Pump 3 switch ON PM Pump switch ON Override Active switch ACTIVE Low Discharge Pressure and...

Page 17: ...the inverter VFD speed immediately ramps up to the speed when lag pump stops setting This prevents the system pressure from dropping excessively due to the XL pump shutting off Once an XL pump has bee...

Page 18: ...er Adjust speed as required to maintain set point pressure NOTE When done turn OFF all pump switches and place system control switch in OFF Return Override Active switch to ACTIVE If the station can b...

Page 19: ...MUST be turned to the OFF position before selecting VFD bypass mode Operation is similar to normal automatic operation but the start stop sequences differ greatly The registers below regulate this NO...

Page 20: ...ens as required to maintain pressure As more flow is going out the PRV discharge less flow is actually being used When the flow reading drops below the flow setpoint to stop value the pumps shut down...

Page 21: ...e line communicates the downstream pressure to the PLC The PLC monitors downstream pressure to determine if the pressure is below the allowable range The standard PLC program defines low discharge pre...

Page 22: ...ng section of this manual for assistance Failure to follow these instructions could result in serious personal injury death or property damage There are two dials on the pressure switch The one on the...

Page 23: ...lears the station automatically resets and automatic operation resumes The PLC allows three 3 automatic restarts in a one hour period At the fourth occurrence in a one hour period the station shuts do...

Page 24: ...of this manual for assistance VFD Fault The VFD sends a fault signal 120 VAC directly to the PLC The display shows Inverter Fault This is normally a VFD fault To determine the nature of the problem yo...

Page 25: ...ontrol panel Black soot on or around the device indicates that it has taken a surge and needs to be replaced 3 Motor lubrication a If your motor has an oil bath thrust bearing you need to ensure that...

Page 26: ...the welds c Visually inspect the station for loose or damaged paint or areas of rust DANGER Personal Injury Hazard Pump station maintenance must be performed by properly trained and qualified personn...

Page 27: ...piping is completely drained 4 Drain all valve pilots including the sensing chamber and all pressure switches 5 Loosen valve bonnet bolts loosen the bonnet and drain the valve bonnet of water 6 Re tig...

Page 28: ...d Check the ball valve position and or blow out line System pressure transducer failure Replace the pressure transducer FlowNet One of main pump switches in OFF position All pumps not running Consult...

Page 29: ...nd clean the inlet screen Inspect probes for correct insertion depth Look for dirty or corroded probes To be performed by a qualified person only Look for broken probes probe holder or wires To be per...

Page 30: ...itor voltage set too high To be performed by a qualified person only Example monitor set at 480 V try 460 V To be performed by a qualified person only Check all input fuses One or more dead legs on a...

Page 31: ...ove MOTOR WON T START Cause Cure To be performed by a qualified person only The overload for that motor is tripped Reset adjust or replace as required Does the station have a high pump temperature opt...

Page 32: ...area of the golf course Calibration The act of or specific values used to scale the output of a measurement device to read real world values Canned turbine See vertical turbine Chemical injection The...

Page 33: ...ressure safety is an excellent choice for these systems Foot valve A device used primarily on horizontal lift applications to maintain pump prime Frequency Hz The number of oscillations per second of...

Page 34: ...in which pumps are allowed to produce more flow rate than the motor that drives them is designed for Also refers to a device in the control panel which detects this situation and stops the pump in ord...

Page 35: ...mal automatic operation Temperature switch This is a normally open or normally closed switch that changes output state when the temperature exceeds the setpoint of the switch Timed alternation One of...

Page 36: ...vent the pump volute prior to operation Failure to follow these instructions indicates a potentially hazardous situation which if not avoided may result in property damage Are the pump and driver sha...

Page 37: ...to follow these instructions could result in serious personal injury death and or property damage Are the feeder wires correctly sized for the load Is the unit properly grounded WARNING Conduit ground...

Page 38: ...BY ITT CORPORATION PRINTED IN U S A THE ITT ENGINEERED BLOCKS SYMBOL AND ENGINEERED FOR LIFE ARE REGISTERED TRADEMARKS OF ITT CORPORATION ITT Flowtronex Phone 800 786 7480 x1 service flowtronex com w...

Reviews: