background image

14

leakage, or other small demands. A PM pump
is  provided  to  address  this  issue.  Most
stations, but not all, include a PM pump. Door
switches are set as follows (from end of line fill
mode):

System control switch:   AUTO

All Individual Pumps switches: ON

Override/Active  switch:  ACTIVE  (Low
Discharge 

Pressure 

and 

differential

pressure faults enabled)

VFD Bypass switch: VFD

NOTE:

As  downstream  pressure  drops  to

more than 5 PSI below setpoint, the PM pump
starts  up.  It  runs  until  the  system  pressure
builds  up  to  5  PSI  above  setpoint,  and  then
shuts off.

Two  issues  can  come  into  play  here.  One  is
cycle time. This refers to the number of times
an  hour  that  the  PM  pump  starts  and  stops
(one  cycle).  If  the  amount  of  cycles  is
excessive, either the system leaks have to be
repaired, or the start/stop parameters need to
be  tuned  (normally  by  dropping  the  pressure
below  setpoint  to  start,  or  increasing  the
pressure  above  setpoint  to  stop).  Must-run
times  can  cause  the  opposite  problem.  The
PLC  determines  the  must-run  time  for  each
pump.  If  this  value  is  set  too  high,  the  PM
pump  reaches  its  "pressure  above  setpoint"
and  stops  before  the  must-run  time  setting
indicates.  This  can  lead  to  an  over-
pressurization  situation.  Address  this  problem
by lowering the must-run time.

WARNING: Excessive Run Time Hazard

Excessive  must-run  times,  stop  times,  or  stop
pressure  setting  can  cause  system  over-
pressurization,  pipe  damage,  and  potentially
cause  personal  injury.  Consult  your  service
technician  or  the  factory  if  you  are  unsure  about
any settings.

Failure  to  follow  these  instructions  could  result  in
serious  personal  injury,  death,  or  property
damage.

Normal Operation

Normal  Operation  occurs  when  heads  are
turned on, or a demand for water exists. Door
switches are set as follows (from end of line fill
mode):

System control switch: AUTO

Pump 1 switch: ON

Pump 2 switch: ON

Pump 3 switch: ON

PM Pump switch: ON

Override/Active  switch:  ACTIVE  (Low
Discharge 

Pressure 

and 

differential

pressure faults enabled)

VFD Bypass switch: VFD

When  the  pressure  drops  5  PSI  below
setpoint, the PM pump starts and continues to
run  until  the  pressure  is  5  PSI  above  the
setpoint.  When  this  pressure  is  reached,  the
PM pump turns OFF. If the pressure continues
to  drop  to  10  PSI  below  setpoint,  the  VSP
starts. Five seconds later, the PM pump turns
OFF.  This  is  the  operation  sequence  for
Combo 1.

When the  VSP  starts,  the  startup  ramp in  the
program  lowers  the  setpoint  to  2  PSI  above
the actual line pressure. The VFD adjusts the
speed of the VSP to maintain the discharge or
downstream  pressure  at  the  setpoint.  The
setpoint ramps up at the rate of 1 PSI every 4
seconds  until  the  normal  setpoint  is  reached.
As the setpoint rises, so does the speed of the
VSP.  This  feature  prevents  the  VSP  from
coming  up  to  full  speed  too  quickly  and
prevents  the  lag  pump(s)  from  starting
prematurely.  This  ramp-up  feature  allows  the
system  to  develop  a  controlled  and  smooth
startup  from  a  completely  de-pressurized
condition,  minimizing  pipe  breakage  from
water hammer. This is the operation sequence
for Combo 2.

If the VFD reaches full speed driving the main
VSP and the discharge pressure is more than
10  PSI  below  the  setpoint,  the  demand  for
water is greater than the capacity of the VSP.
An XL (across-the-line) pump starts as the lag
pump. This operation sequence occurs during
Combo 3.

When  an  XL  pump  starts,  and  the  VFD  is
driving  another  pump,  the  inverter  (VFD)
speed immediately ramps down to the inverter
“speed  when  lag  pump  starts”  setting.  This
permits  the  XL  pump  to  start  with  very  little
pressure  surge,  or  related  water  hammer.
Once  the  lag  pump  is  at  full  speed,  the  VSP
ramps  back  up  to  try  and  maintain  setpoint
pressure.

Summary of Contents for Flowtronex SIlent Storm

Page 1: ...Manual 19 001 200 Rev 0110 SILENT STORM VFD Pumping System Installation Operation Maintenance INSTALLER PLEASE LEAVE THIS MANUAL FOR THE OWNER S USE NOTE This product is not intended for use in potab...

Page 2: ...hor make no claim to these trademarks These include Microsoft Windows Windows NT ActiveX that are either registered trademarks or trademarks of Microsoft Corporation in the United States and or other...

Page 3: ...on 19 Manual Mode of Operation 19 Low Discharge Pressure 19 High Discharge Pressure 19 Low Inlet Pressure 20 Loss of Prime 20 Low Level Fault 21 Phase Failure 21 INDIVIDUAL PUMP FAULTS 21 Overload Pro...

Page 4: ...fected part of the product s Purchaser shall assume all responsibility and expense for removal reinstallation and freight in connection with the foregoing remedies The same obligations and conditions...

Page 5: ...damage All operating instructions must be read understood and followed by the operating personnel Flowtronex accepts no liability for damages or operating disorder which are the result of non complian...

Page 6: ...avy tools etc Wear other personal protective equipment to protect against hazardous toxic fluids Coupling Guards Never operate a pump without a coupling guard properly installed Never force piping to...

Page 7: ...st questions pertaining to its service Every attempt has been made to explain all facets of system operation and maintenance However should you have specific questions not addressed in this manual you...

Page 8: ...vy due to the position of the equipment Do not use component eyebolts to lift the pump station WARNING Falling Objects Hazard Eyebolts if provided are designed to lift only the components to which the...

Page 9: ...rical Code and local codes must be followed WARNING Electrical Shock Hazard Conduit grounds are not adequate A separate ground wire must be attached to the ground lug provided in the enclosure to avoi...

Page 10: ...d electrical shock Failure to follow these instructions could result in serious personal injury death or property damage Place the unit on its concrete foundation supporting it with steel wedges or sh...

Page 11: ...s properly installed it should not touch the side of the wet well Premature bearing failure or destruction of the bowl assembly can result from improper installation Figure 4 Position Head Over Access...

Page 12: ...e vertical hollow shaft motor to the top of the pump s disconnected head Refer to the Gould Pumps Model VIT Installation Operation Maintenance Instructions WARNING Falling Objects Hazard DO NOT work u...

Page 13: ...This switch position places the pump station in either Automatic VFD Bypass or Manual VFD Bypass mode of operation depending on the position of the MANUAL OFF AUTO switch In this mode the pumps will s...

Page 14: ...he screen during maintenance AUTO Causes the Lake Screen solenoid to open after the main VSP has been operating at least one minute the minimum flow requirement is met and the speed test is not trying...

Page 15: ...only apply to Combo 1 The values of 30 PSI and 90 seconds were intentionally selected since they are out of range and will never be used There are three 3 main types of auto operation line fill syste...

Page 16: ...s are set as follows from end of line fill mode System control switch AUTO Pump 1 switch ON Pump 2 switch ON Pump 3 switch ON PM Pump switch ON Override Active switch ACTIVE Low Discharge Pressure and...

Page 17: ...the inverter VFD speed immediately ramps up to the speed when lag pump stops setting This prevents the system pressure from dropping excessively due to the XL pump shutting off Once an XL pump has bee...

Page 18: ...er Adjust speed as required to maintain set point pressure NOTE When done turn OFF all pump switches and place system control switch in OFF Return Override Active switch to ACTIVE If the station can b...

Page 19: ...MUST be turned to the OFF position before selecting VFD bypass mode Operation is similar to normal automatic operation but the start stop sequences differ greatly The registers below regulate this NO...

Page 20: ...ens as required to maintain pressure As more flow is going out the PRV discharge less flow is actually being used When the flow reading drops below the flow setpoint to stop value the pumps shut down...

Page 21: ...e line communicates the downstream pressure to the PLC The PLC monitors downstream pressure to determine if the pressure is below the allowable range The standard PLC program defines low discharge pre...

Page 22: ...ng section of this manual for assistance Failure to follow these instructions could result in serious personal injury death or property damage There are two dials on the pressure switch The one on the...

Page 23: ...lears the station automatically resets and automatic operation resumes The PLC allows three 3 automatic restarts in a one hour period At the fourth occurrence in a one hour period the station shuts do...

Page 24: ...of this manual for assistance VFD Fault The VFD sends a fault signal 120 VAC directly to the PLC The display shows Inverter Fault This is normally a VFD fault To determine the nature of the problem yo...

Page 25: ...ontrol panel Black soot on or around the device indicates that it has taken a surge and needs to be replaced 3 Motor lubrication a If your motor has an oil bath thrust bearing you need to ensure that...

Page 26: ...the welds c Visually inspect the station for loose or damaged paint or areas of rust DANGER Personal Injury Hazard Pump station maintenance must be performed by properly trained and qualified personn...

Page 27: ...piping is completely drained 4 Drain all valve pilots including the sensing chamber and all pressure switches 5 Loosen valve bonnet bolts loosen the bonnet and drain the valve bonnet of water 6 Re tig...

Page 28: ...d Check the ball valve position and or blow out line System pressure transducer failure Replace the pressure transducer FlowNet One of main pump switches in OFF position All pumps not running Consult...

Page 29: ...nd clean the inlet screen Inspect probes for correct insertion depth Look for dirty or corroded probes To be performed by a qualified person only Look for broken probes probe holder or wires To be per...

Page 30: ...itor voltage set too high To be performed by a qualified person only Example monitor set at 480 V try 460 V To be performed by a qualified person only Check all input fuses One or more dead legs on a...

Page 31: ...ove MOTOR WON T START Cause Cure To be performed by a qualified person only The overload for that motor is tripped Reset adjust or replace as required Does the station have a high pump temperature opt...

Page 32: ...area of the golf course Calibration The act of or specific values used to scale the output of a measurement device to read real world values Canned turbine See vertical turbine Chemical injection The...

Page 33: ...ressure safety is an excellent choice for these systems Foot valve A device used primarily on horizontal lift applications to maintain pump prime Frequency Hz The number of oscillations per second of...

Page 34: ...in which pumps are allowed to produce more flow rate than the motor that drives them is designed for Also refers to a device in the control panel which detects this situation and stops the pump in ord...

Page 35: ...mal automatic operation Temperature switch This is a normally open or normally closed switch that changes output state when the temperature exceeds the setpoint of the switch Timed alternation One of...

Page 36: ...vent the pump volute prior to operation Failure to follow these instructions indicates a potentially hazardous situation which if not avoided may result in property damage Are the pump and driver sha...

Page 37: ...to follow these instructions could result in serious personal injury death and or property damage Are the feeder wires correctly sized for the load Is the unit properly grounded WARNING Conduit ground...

Page 38: ...BY ITT CORPORATION PRINTED IN U S A THE ITT ENGINEERED BLOCKS SYMBOL AND ENGINEERED FOR LIFE ARE REGISTERED TRADEMARKS OF ITT CORPORATION ITT Flowtronex Phone 800 786 7480 x1 service flowtronex com w...

Reviews: