background image

5

3.0 

PUTTING THE UNIT INTO SERVICE

GMU30  is  designed  for  systems  requiring  up  to 
30-psi,  drawing  water  or  water-glycol  mixture  up  to
10-gpm  from  the  55-gallon  tank  and  automatically
servicing the closed-loop system. 

GMU60  is  designed  for  systems  requiring  up  to 
60-psi,  drawing  water  or  water-glycol  mixture  up  to
5-gpm from the 55-gallon tank and automatically ser-
vicing the closed-loop system. 

When  pressure  in  the  closed-loop  system  decreases
to the cut-in pressure the pump will start.  The pump
runs  until  the  pressure  switch  reaches  the  cut-out
pressure.  The  pressure  switch  factory  default  cut-in
setting  for  GMU-30  is  5-psi,  and  the  cut-out  setting 
is  21-psi.  The  pressure  switch  factory  default  cut-in
setting  for  GMU-60  is  30-psi,  and  cut-out  setting  is
50-psi.

3.1 

ADJUSTMENTS AND SETTINGS

3.1.1 

Pressure Switch

Electrical equipment should be serviced only by qual-
ified electrical maintenance personnel. 

The  pressure  switch  is  piped  to  the  discharge  line.
There are two adjusting screws located on the top of
the  switch  control.  This  adjustment  must  be  made
before operating the system.

Adjust pressure switch as follows:

a)  Cut-In  (Turn  nut  clockwise  for  higher  pressure  or 

counterclockwise for lower pressure).

b)  Cut-Out (Turn nut clockwise for higher pressure or 

counterclockwise for lower pressure). 

c)  Check switch operation after resetting.

d)  See above picture for adjustment nut locations.

3.1.2 

Triple Duty Valve

The Triple Duty Valve is piped to the discharge of the
pump  and  is  used  as  a  non-slam  check  valve,  cali-
brated  balance  valve  and  shutoff  valve  for  this  unit.
The valve stem is located on the top of the valve. The
Triple  Duty  Valve  has  a  calibrated  nameplate  on  the
valve  stem  for  rough  system  balance  and  position
indication.  Prior  to  placing  GMU  into  operation,
installer must adjust the Triple Duty Valve.     

3.1.2.1  Adjust Triple Duty Valve

a)  Never turn the valve stem in excess of 100% open 

when  system  is  pressured.  At  this  position  the 
valve does not act as a check valve. It is a gravity 
flow valve. 

b)  Never  turn  the  valve  stem  to  the  closed  position 

when operating the system. This position provides 
positive shutoff.

c) Adjust the valve between 20% to100% open.    

3.1.3 

Diaphragm Expansion Tank

Diaphragm expansion tank factory pre-charge is 40-psi.
Adjust  pre-charge  to  equal  incoming  pressure.  Refer
to  the  specific  IOM  #V58303  that  was  shipped  with
the tank for installation and operating instructions.

3.1.4 

Low Water Cut Off Switch

When the water or water-glycol mixture in the 55-gallon
reservoir falls below the low level point, the low water
cut-off  switch  will  turn  the  pump  off.  An  alarm  light
will illuminate. 

3.1.5 

Sequence of Operation

When  pressure  in  the  system  decreases  to  the  mini-
mum  allowable  fill  pressure,  the  pressure  reducing
valve opens.

The  Glycol  stored  in  the  pressure  tank  flows  to  the
system,  when  pressure  supplied  to  the  pressure
reducing valve reaches the pump cut-in pressure, the
GMU pump will start.

Pump runs until pressure switch reaches the cut-out
pressure.

Should  the  Glycol  solution  in  the  55-gallon  reservoir
fall below the low level point in the reservoir, the low
level  switch  will  turn  pump  off,  an  alarm  light  will  be
signaled.

Section 3

WARNING:  Electrical  shock  hazard.  Single  phase 
or  three  phase  AC  power.  Disconnect  and  lockout

power before servicing unit. FAILURE TO FOLLOW THESE
INSTRUCTIONS  COULD  RESULT  IN  SERIOUS  PER-
SONAL INJURY, DEATH, AND/OR PROPERTY DAMAGE.

CAUTION: Prevent subsequent damage. A unit show-
ing  symptoms  of  possible  problems  (noise,  leaks,

vibration,  and/or  continual  operation)  must  be  corrected
immediately.  FAILURE  TO  FOLLOW  THESE  INSTRUC-
TIONS  COULD  RESULT  IN  PROPERTY DAMAGE
AND/OR MODERATE PERSONAL INJURY.

Adjust for cut-in point

Adjust for cut-out

PRESSURE SWITCH

WARNING:  Electrical  shock  hazard.  Disconnect  and
lockout power before servicing the unit. FAILURE TO

FOLLOW  THESE  INSTRUCTIONS  COULD  RESULT  IN
SERIOUS PERSONAL INJURY, DEATH, AND/OR PROP-
ERTY DAMAGE.

WARNING: Setting the Triple Duty Valve in excess of
100% open within the range labeled gravity flow can

allow  backward  flow  of  glycol  into  the  55-gallon  tank  and
overfill it. Adjustment must be made before placing the unit
into operation. Follow the instructions that are supplied with
the  unit.  FAILURE  TO  FOLLOW  THESE  INSTRUCTIONS
COULD  RESULT  IN  PROPERTY  DAMAGE  AND/OR
MODERATE PERSONAL INJURY.

Summary of Contents for Bell & Gossett GMU-30

Page 1: ...s When used the safety alert symbol means ATTENTION BECOME ALERT YOUR SAFETY IS INVOLVED FAILURE TO FOLLOW THE INSTRUCTION MAY RESULT IN A SAFETY HAZARD Glycol Make up Unit DESCRIPTION Single pump uni...

Page 2: ...ained in this manual is intended to assist operating personnel by providing information on the char acteristics of the purchased equipment It does not relieve the user of the responsibility to adhere...

Page 3: ...ptible to failure if operated in ambient temperatures outside of its rat ing The OPERATING temperature range for this unit is 32 to 105 F The relative humidity should not exceed 95 non condensing The...

Page 4: ...A dedicated ground wire must be connected to the unit Single phase motors have internal overload protec tion The disconnecting means and short circuit pro tection are to be supplied and mounted by ot...

Page 5: ...tion when operating the system This position provides positive shutoff c Adjust the valve between 20 to100 open 3 1 3 Diaphragm Expansion Tank Diaphragm expansion tank factory pre charge is 40 psi Adj...

Page 6: ...ing condi tions may require resetting the controls For best results use compressed air and a continuity meter across the switch to reset the controls The legend plate on the control indicates approxim...

Page 7: ...No power Restore if there is no power 2 Pressure switch not adjusted properly Refer to pressure switch setting section 3 1 1 DANGER Troubleshooting live control panels ex poses personnel to hazardous...

Page 8: ...CUT OFF SWITCH Y STRAINER PUMP 2 OPENING TANK 55 GALLONS TRIPLE DUTY VALVE PRESSURE SWITCH PRESSURE GAUGE SYSTEM OUTLET 3 4 NPT DIAPHRAGM EXPANSION TANK BY OTHERS PRESSURE REDUCING VALVE GATE VALVE G...

Page 9: ...9 Appendix E Wiring Diagram 1GMU01...

Page 10: ...IL 60053 Phone 847 966 3700 Fax 847 966 9052 www bellgossett com Copyright 2010 ITT Corporation Printed in U S A 4 10 THE ITT ENGINEERED BLOCKS SYMBOL AND ENGINEERED FOR LIFE ARE REGISTERED TRADEMARKS...

Reviews: