4
2.0
INSTALLATION INSTRUCTIONS
Locate the Glycol Make-up unit for ease of inspec-
tion, maintenance, and service. For Glycol application
secondary containment is required to catch any leaks
or spills that could go down the drain or out a door
and cause a risk to the environment. Refer to local
codes for clarification.
FAILURE TO FOLLOW THESE INSTRUCTIONS
COULD RESULT IN SERIOUS PERSONAL INJURY,
DEATH, AND/OR PROPERTY DAMAGE.
Place the unit preferably on a concrete floor or base.
Level the steel base, on which the pump is mounted,
in both directions by placing steel shims between the
base and the anchor bolts.
A well-leveled and secured unit will result in quiet
operation as well as longevity of service.
See drawing 1FC008 for general piping requirements.
When connecting the GMU discharge line to the
make-up line of the Closed-loop system the 3/4" NPT
fitting needs to be tightened. When doing this, be
sure to use a back-up wrench on the fitting. Do not
over tighten the fitting. Inspect all visible fittings for
leaks. Tighten the fittings if any leaks are found. Be
sure to use two wrenches one to tighten the fitting
and the other to back-up the fitting. Using just one
wrench may damage the fitting. Never tighten a fitting
while there is hydraulic pressure in the fitting.
Support the discharge line independently by use of
pipe hangers or anchors. Do not attempt to spring
the discharge line into position. It is recommended
that there is a three (3) valve by-pass in the make-up
line. See drawing 1FC008 for location of valves.
IMPORTANT: Do not install and operate ITT pumps
in closed systems unless the system is constructed
with properly sized safety devices and control
devices. Such devices include the use of properly
sized and located pressure relief valves, compression
tanks, pressure controls, temperature controls and
flow controls as appropriate. If the package includes
a pressure relief valve, make sure the discharge of
the valve is directed to the floor drain before making
the unit operational.
IMPORTANT: If vibration eliminators are used, note
that unless the piping to which the vibration elimina-
tors are connected to are properly anchored to the
floor, the benefits may not be fully realized.
The power supply required for the unit is indicated on
the nameplate located inside the control panel. A
dedicated ground wire must be connected to the
unit.
Single phase motors have internal overload protec-
tion. The disconnecting means and short circuit pro-
tection are to be supplied and mounted by others.
Single phase panel remains fully energized at all
times, unless incoming power is disconnected. Do
not use the "POWER ON" light as a method to deter-
mine when the control panel is de-energized.
Section 2
DANGER: Do not lift entire unit by any components
lift eyebolts. Lift the unit with slings placed under the
unit base rails. FAILURE TO FOLLOW THESE INSTRUC-
TIONS COULD RESULT IN SERIOUS PERSONAL
INJURY, DEATH, AND/OR PROPERTY DAMAGE.
DANGER: Top of unit is heavy when it is full of fluids
and may tip if not lifted properly. FAILURE TO FOL-
LOW THESE INSTRUCTIONS COULD RESULT IN SERI-
OUS PERSONAL INJURY, DEATH, AND/OR PROPERTY
DAMAGE.
DANGER: Do not step on the top of the unit. It is
not designed to support the weight of a person. Any
fall can be serious, and may result in painful or incapacitat-
ing injury. FAILURE TO FOLLOW THESE INSTRUCTIONS
COULD RESULT IN SERIOUS PERSONAL INJURY,
DEATH, AND/OR PROPERTY DAMAGE.
WARNING: The heating of water and other fluids
causes volumetric expansion. The associated forces
may cause failure of system components and release of
high temperature fluids. This will be prevented by installing
properly sized and located pressure relief valves and com-
pression tanks. FAILURE TO FOLLOW THESE INSTRUC-
TIONS COULD RESULT IN SERIOUS PERSONAL
INJURY, DEATH, AND/OR PROPERTY DAMAGE.
WARNING: Electrical shock hazard. Inspect all
electrical connections prior to powering the unit.
Wiring connections must be made by a qualified electrician
in accordance with all applicable codes, ordinances, and
good practice. FAILURE TO FOLLOW THESE INSTRUC-
TIONS COULD RESULT IN SERIOUS PERSONAL
INJURY, DEATH, AND/OR PROPERTY DAMAGE.
WARNING: Electrical shock hazard. Turn off and
lockout all power sources prior to servicing panel.
FAILURE TO FOLLOW THESE INSTRUCTIONS COULD
RESULT IN SERIOUS PERSONAL INJURY, DEATH,
AND/OR PROPERTY DAMAGE.
CAUTION: Seal damage may occur. Do not run pump
dry. fill and vent the pump volute prior to operation.
FAILURE TO FOLLOW THESE INSTRUCTIONS COULD
RESULT IN PROPERTY DAMAGE AND/OR MODERATE
PERSONAL INJURY.
WARNING: Conduit grounds are not adequate. A
separate ground wire must be attached to the ground
lug provided in the enclosure to avoid potential safety haz-
ards. FAILURE TO FOLLOW THESE INSTRUCTIONS
CAN RESULT IN SERIOUS PERSONAL INJURY, DEATH,
AND/OR PROPERTY DAMAGE.