6
SYSTEM PIPING AND UNIT
INSTALLATION – FINAL CHECK LIST
____
1. Is the unit base properly leveled and secured?
____
2. Are all lubrication points properly lubricated?
____
3. Is the shut-off valve to the pump suction open?
____
4. Is the shutoff valve to the Diaphragm Expansion
Tank line open?
____
5. Are the shutoff valves for the make-up line open?
____
6. Is the Triple Duty Valve turned to suitable operating
position?
____
7. Is the piping properly supported to prevent strains
on unit?
____
8. Is the system, including the pumps, purged of debris
and air?
ELECTRICAL WIRING AND CONTROL
SETTINGS – FINAL CHECK LIST
____
1. Does the feeder line voltage correspond to the unit
voltage? Check the unit nameplate or motor terminal
connection.
____
2. Are the feeder wires correctly sized for the load?
____
3. Have all the power terminals in the control panel
been checked for tightness? This is imperative since
stranded wires tend to “flow” and become loose
after initial installation.
____
4. Are the pressure controls correctly set? The pres-
sure switch needs to be set for proper operation.
Any subsequent change in system operating condi-
tions may require resetting the controls. For best
results, use compressed air and a continuity meter
(across the switch) to reset the controls. The legend
plate on the control indicates approximate readings
only, therefore, should be used with caution.
WARNING: Electrical shock hazard. Inspect all elec-
trical connections prior to powering the unit. Wiring
connections must be made by a qualified electrician in
accordance with all applicable codes, ordinances, and
good practices. FAILURE TO FOLLOW THESE INSTRUC-
TIONS COULD RESULT IN SERIOUS PERSONAL
INJURY, DEATH, AND/OR PROPERTY DAMAGE.
WARNING: Conduit grounds are not adequate. A
separate ground wire must be attached to the
ground lug provided in the enclosure to avoid potential
safety hazards. FAILURE TO FOLLOW THESE INSTRUC-
TIONS COULD RESULT IN SERIOUS PERSONAL
INJURY, DEATH, AND/OR PROPERTY DAMAGE.
CAUTION: Seal damage may occur. Do not run
pumps dry. Fill and vent the pump volute prior to
operation. FAILURE TO FOLLOW THESE INSTRUC-
TIONS COULD RESULT IN PROPERTY DAMAGE
AND/OR MODERATE PERSONAL INJURY.
Appendix A
Appendix B
WARNING: Electrical shock hazard. Single phase
or three phase AC power. Disconnect and lockout
power before servicing unit. FAILURE TO FOLLOW THESE
INSTRUCTIONS COULD RESULT IN SERIOUS PER-
SONAL INJURY, DEATH, AND/OR PROPERTY DAMAGE.