background image

Summary of Contents for Advantage Actuator 2.0

Page 1: ...Industrial Process Maintenance Manual Advantage Actuator 2 0...

Page 2: ......

Page 3: ...Adjust the travel closing stop 12 Replace the spindle o rings 12 Lubrication requirements 12 Replace the actuator diaphragm and spring for fail open actuator 13 Replace the actuator diaphragm and spr...

Page 4: ...ecommended by an ITT engineer WARNING Misapplication of the valve can result in injury or property damage Select valves and valve components of the proper materials and make sure that they are consist...

Page 5: ...ication marks associated with the product Maintenance safety precautions Be aware of these safety precautions when performing maintenance on this product You must decontaminate the product if it has b...

Page 6: ...efining the actuator as follows Table 1 Actuator Code Description B Advantage actuator 2 0 Table 2 Mode of operation Code Description 1 Fail open spring to open air to close direct acting 2 Fail close...

Page 7: ...aled bonnet The non sealed bonnet has a weep hole that permits leakage of the process fluid if the diaphragm ruptures Sealed bonnet The sealed bonnet uses a special V notch vent plug which permits dia...

Page 8: ...the diaphragm tabs The molding date grade of diaphragm and valve size provide traceability to original batch records Supplier code Date code Figure 4 Elastomer diaphragm front Grade of diaphragm Valve...

Page 9: ...from the plug Replace the valve diaphragm Sealed bonnet Fluid weeping from the plug Loosen the v notch vent plug 2 3 turns to check Replace the valve diaphragm Actuator s bonnet weep hole and air por...

Page 10: ...erial Metric in lb N m in lb N m 0 50 15 1 4 M6 25 60 2 8 6 8 20 40 2 3 4 5 0 75 20 1 4 M6 50 65 5 7 9 1 20 50 2 3 5 7 1 00 25 5 16 M8 65 90 7 4 11 3 45 70 5 1 7 9 1 50 40 3 8 M10 200 225 23 25 75 130...

Page 11: ...formation see Disassemble the valve in this manual 2 If the actuator mode of operation is fail open pressurize the actuator by applying air to the upper cover slightly extending the compressor and dia...

Page 12: ...ng cushion from rotating 7 Rotate the diaphragm until hard stop or heavy resistance is achieved and additional force does not significantly rotate the diaphragm into the compressor 8 If replacing a PT...

Page 13: ...ply excessive air pressure that results in inversion of the diaphragm 11 Replace the topworks assembly on the body and tighten the bonnet fasteners For more information see Tighten the bonnet fastener...

Page 14: ...ve in this manual 4 Disassemble the actuator For more information see Replace the actuator diaphragm and spring for proper mode of operation fail open fail close or double acting in this manual 5 With...

Page 15: ...in the fixture lower plate d Place the support plate and spacer plate on the actuator top plate e Turn the fixture handwheel clockwise to remove the load from the indicator spindle f Remove the spind...

Page 16: ...24 UNC tapped hole former plug location c Turn the fixture handwheel clockwise until the stem rests on the actuator top cover d Remove all the cover to cover caps fasteners and washers e Turn the fixt...

Page 17: ...he spindle nut surface with Loctite 7649 Primer N b Apply Blue Loctite 242 to the indicating spindle c Replace the indicating spindle 9 Assemble the upper cover using care to keep the air fitting in l...

Page 18: ...6 parts List of parts 11 12 1 8 NPT 10 3 9 7 2 4 5 1 6 Figure 7 Fail open and double acting actuator 15 16 17 13 18 NPT 14 Figure 8 Low profile actuator 8 1 8 NPT Figure 9 Fail close actuator Parts Li...

Page 19: ...less Steel Cast Iron Zinc or Bronze 1 113 Diaphragm As required 1 123 Backing Cushion EPDM 1 133 O Ring FKM 1 14 Lower Actuator Cover Plastic 1 15 Bonnet Stainless Steel 1 163 O Ring FKM 2 17 Bushing...

Page 20: ...Outer Column 4 126 Spacer 1 13 Spring Pin 1 14 Lower Plate 1 15 Rod 1 16 Machine Screw 4 17 Shim Washer As required 18 Spacer Plate 1 197 Cap Screw 2 207 Bar 1 217 Inner Column 2 227 Support Plate 1...

Page 21: ......

Page 22: ...ancaster PA 17603 USA Tel 717 509 2200 Fax 717 509 2316 E mail pureflo custserv itt com Richards Street Kirkham Lancashire PR4 2HU England Tel 44 1772 682696 Fax 44 1772 686006 2009 ITT Corporation Th...

Reviews: