International Thermal Research 4-1
Installing the Fuel System
4.1 Before You Begin
For efficient and safe operation of the Oasis® Zephyr™ HW, follow all
recommendations for properly installing the fuel system. Any deviations from these
must be approved in advance by ITR.
Although the Oasis® Zephyr™ HW will work with furnace oil, stove
oil, and jet fuel, it is only certified to be used with diesel #1 and #2.
DO NOT USE GASOLINE, CRANKCASE OIL, OR ANY OIL CONTAINING
GASOLINE.
Keep fuel lines away from any heat source above 100°F (38°C).
Keep gasoline and any equipment that uses gasoline away from the Oasis® Zephyr™
HW location. The Oasis® Zephyr™ HW is not rated for use in an explosive
environment.
Never share the fuel supply line to the Oasis® Zephyr™ HW with
any other fuel-burning device.
4.2
Fuel System Installation
The fuel pump in the Oasis® Zephyr™ HW has a maximum flow capacity of 32
GAL/Hr and a maximum pressure of 11.5 psi. A 10-micron fuel filter is recommended.
Select a fuel filter based on these requirements.
Recommendations for Installation
The Oasis® Zephyr™ HW’s fuel connections are accessed from the top of the heater.
The fuel inlet/outlet connections are located on the top left of the Oasis® Zephyr™
HW and consists of quick connect fittings attached to the inlet and return hoses
coming from the heater. The fuel lines are labelled for identification. Minimum
recommended size for the fuel lines is ¼” I.D. The fuel supply line and the return