ITOH DENKI CB-016 series User Manual Download Page 5

8

9

 ●

Protective resistor should be mounted to suppress the output to be 

   

  

25mA or less, otherwise the driver card's integral transistor may be 

   

  

damaged. 

 ●

100

Ω

 resistor is built-in the driver card's output section for motor pulse 

  

signal.

8  Error Status, Reset and History

MDR's motor pulse signal is discharged from CN2-5. 

2 pulses/motor rotation, NPN open collector output.

When error arises, the error can be identified either by LED 1 (green) and LED 2 (red),

    or by the error signal discharged from CN2-4.

LED indication

7  Motor Pulse Signal Output 

155

4638

9.6〜9.9

152

4556

9.1〜9.4

145

4349

8.6〜8.9

138

4141

8.1〜8.4

131

3934

7.6〜7.9

124

3727

7.1〜7.4

110

3313

6.6〜6.9

104

3106

6.1〜6.4

97

2899

5.6〜5.9

90

2692

5.1〜5.4

83

2485

4.6〜4.9

76

2278

4.1〜4.4

69

2071

3.6〜3.9

62

1864

3.1〜3.4

55

1657

2.6〜2.9

48

1450

2.1〜2.4

41

1242

1.6〜1.9

35

1035

1.1〜1.4

28

828

0.6〜0.9

21

621

0.1〜0.4

Illuminates  

off

blinks at 1Hz  

blinks at 6Hz

O N

O F F

To reset the error status, first remove the cause of error, and then switch the 

  direction signal at CN2-2.

To restart the MDR, first remove the cause of error, and then re-inject 

  run signal at CN2-1.

Please

 

have 100ms or more intervals between each switch for ON

OFF

ON / 

 

OFF

ON

OFF / RUN

STOP

RUN to release error signal or restart MDR.

Speed dev/-3%

CN2-4 (Error signal)

Symptom/Causes

Reset 

the error signal

Restart 

the MDR

MDR

SW1-4

OFF

SW1-4

ON

Open

Discharge

n.a.

n.a.

Normal operation

Open

Open

Stop

Discharge

Open

Stop

Supply 24VDC 
power

No power

Discharge

Open

Stop

PCB damaged

Thermister 
reacted
(Thermister error)

Shut off the power
then replace the
driver card

Internal speed variation 

SW1-5

SW5

Frequency 

(Hz)

Motor speed

 (rpm)

Analog voltage

 input

LED 1

(green)

LED 2

(red)

Automatic recovery setting

MDR restarts immediately 1 minute after 
thermister recovery from cooling off

MDR restarts by injecting RUN signal followed by 
STOP signal to CN2-1 to reset the error signal then 
inject RUN signal to CN2-1 to restart, 1 minute after 
thermister recovery

MDR restarts by injecting RUN signal followed by 
STOP signal to CN2-1 to reset the error signal then 
inject RUN signal to CN2-1 to restart, 1 minute after 
thermister recovery

Inject signal 
RUN-STOP-RUN order to 
CN2-1

Inject signal 
RUN-STOP-RUN order to 
CN2-1

Restarts automatically 
in a minute

After thermister recovery, 
inject signal ON-OFF-ON 
or OFF-ON-OFF order to
CN2-2

After thermister recovery, 
inject signal ON-OFF-ON 
or OFF-ON-OFF order to 
CN2-2

Shut off the power 
then replace the 
MDR

Inject signal
ON-OFF-ON or 
OFF-ON-OFF order 
to CN2-2

Inject signal 
RUN-STOP-RUN order
 to CN2-1 to restart

Discharge

Open

Stop

Motor cable 
disconnection

Motor stall for 
4 seconds
(Stall error)

Discharge

Open

Stop

Inject signal RUN-STOP-RUN order to 
CN2-1 to reset the error and to restart

Manual recovery setting

8-1  Error History

LED of error history will not illuminate during normal operational condition, but 

   when motor stops with next error.

Please see section 8-2 for other type of error.

LED1

LED2

LED3

Motor stall error / under voltage error / thermister error 

Shows the error history since the card is powered.  See the below chart.

stall error

under voltage error

thermister error 

If thermister, motor stall or under voltage error arises while the MDR is running, 
the error status and frequency of error occurrence are identified by LED 2 and LED 3.  

Automatic recovery setting

Manual recovery setting

Secure the stable
supply voltage 18V
or over

Restarts immediately

First secure the 
stable supply 
voltage 18V or over, 
then inject signal 
ON-OFF-ON or 
OFF-ON-OFF order 
to CN2-2

Inject signal 
RUN-STOP-RUN 

order 

to CN2-1 to restart

Overload 
operation

Supply voltage
less than 18VDC
(under voltage
error)

Discharge

Open

Stop

Open

Discharge

Run

*

 Error can also be reset by shutting off the power 2 seconds or over.

green

red

orange

Error occurred at first time

Error occurred at second time
 (same error as the first one)

Error occurred at second time
 (different error from the first one)
Error occurred at third time
 (same error as the first or second one)

Error occurred at third time

 (same error in series) 

Remove the causes of overload.

First secure the stable supply voltage 18V 
or over, then inject signal RUN-STOP-RUN 
order to CN2-1 for error reset and restart

LED indication

Illuminates  

off

blinks at 1Hz  

blinks at 6Hz

see 
5 Operation Instructions

see 
5 Operation Instructions

Discharge

Open

Stop

Connector 
unplugged

Shut off the power 
and replug in the 
connector properly

see 
5 Operation Instructions

see 
5 Operation Instructions

Caution

Summary of Contents for CB-016 series

Page 1: ...he signal may stay ON or OFF in case of the CB 016 driver card failure Be sure to shut off the power before inserting or removing any connector Do not wire connector left in the CB 016 driver card Do...

Page 2: ...arks See section 5 3 Dip Switch SW1 Min Default Acceleration from RUN signal 0 sec 2 Deceleration from STOP signal 0 sec 2 5 sec 2 5 sec Min Min Potentiometer VR Model Model nomenclature To the CCW en...

Page 3: ...R shafts are adequately secured with the supplied brackets or accessories Each connector on the driver card is adequately wired and inserted Operating and environmental conditions are respected Power...

Page 4: ...Nominal Speed m min Internal speed variation input Analog voltage Speed deviation 3 1 2 3 3 3 3 3 3 5 2 Direction Setting 5 3 Acceleration and Deceleration Reverse direction by external DIR signal ca...

Page 5: ...ect signal RUN STOP RUN order to CN2 1 Inject signal RUN STOP RUN order to CN2 1 Restarts automatically in a minute After thermister recovery inject signal ON OFF ON or OFF ON OFF order to CN2 2 After...

Page 6: ...thermister error thermister error under voltage error under voltage error under voltage error first time second time 3 times thermister error under voltage error thermister error first time second ti...

Page 7: ...ww itohdenki com Asia Oceania Itoh Denki Asia Limited Phone 852 2427 2576 Fax 852 2427 2203 China Itoh Denki Shanghai Company Limited Phone 86 21 6341 0181 Fax 86 21 6341 0180 www itohdenki com cn 4 6...

Reviews: