Italtherm CITY BASIC Instruction Handbook Manual Download Page 24

24

3.  wait at least 10 seconds

 and verify that the measured pressure corresponds to the MAX value 

indicated in the Burner Pressure table (see page 26), with regard to the boiler model and gas type;

4. 

extract one of the connectors

 4

  that  supply  the 

modulation  coil;  verify  that  the  measured  pres-

sure corresponds to the MIN value indicated in the 

Burner Pressure table (see page 26), with regard to 

the boiler model and gas type;

5. 

reinsert the connector

 4 

;

6. 

if it is necessary to adjust the regulation, proceed 

as it follows, referring to the figure:

 

• take off the protection cap

 C 

 

• adjust MAX pressure acting on the nut

 B

 (10 mm). 

Turn clockwise to increase pressure, counterclock-

wise to decrease pressure;

 

• extract again one of the connectors

 4 

;

 

• adjust MIN pressure acting on the screw

 A

 (with 

a 4 mm screwdriver), paying attention not to con-

temporarily  move  the  nut

 B 

.  Turn  clockwise  to 

increase pressure, counterclockwise to decrease 

pressure;

 

• reinsert the connector

 4

 and check that MAX pressure is not changed;

 Important: LOCK THE ADjUSTMENT DEvICE AFTER ANY SETTING OPERATION.

 

• mount the cap

 C 

;

7. 

screw the pressure tapping point screw for gas outlet

 1

 and 

verify that there is no gas leak

 .

8. 

To switch the burner off, turn the Summer/Winter knob

 

 to the

 position.

Max heating power adjustment

The maximum heating power output must be set in accordance with the system requirements (stated 

in the project). Once you know the power suitable for the heating system, refer to the "Burner pressure 

tables" on page 26 and find the burner pressure for the boiler model and for the type of gas used.

The  adjustment  will  be  performed  through  the  boiler’s  controls,  following  a  special  procedure  that 

avoids accidental activations by the User:

1. 

Loosen (2-3 turns) the screw of pressure tapping point for gas outlet

 1

 of the gas valve and insert 

the manometer sensor. Do not use the tapping point “Vent”

 3

 that 

must always be closed

;

2. 

supply the boiler and turn the Summer/Winter knob   to Summer position   ;

3. 

ensure that there are NOT domestic hot water requests (no open taps); if the room thermostat is 

installed, make so that it requires the heating (e.g. raise the requested room temperature manu-

ally);

 

• turn the Hot Water knob

   

on 

service

 position: on the display will appear a flashing number 

from 00 to 99 that indicates the current set point of the value of heating power, where the value 

00 

corresponds to the minimum setting of the gas valve

 

and the value 

99 

corresponds to the 

maximum;

 

• wait (approximately five seconds) that the display shows 

“PO”

 (POwer) flashing (moreover, both 

the 

GREEN

 and 

RED 

indicators flash to short “pulses”).

Pressure tapping points:

outlet

inlet

equalization (VENT) 

(not used in natural 

draught models)

Summary of Contents for CITY BASIC

Page 1: ...CITY BASIC Instruction Handbook for use adjustment maintenance installation 24 C ...

Page 2: ...aller 12 Dimensions and connections 13 Pump capacity diagram 13 Specifications for inlet air 13 Domestic water supply characteristics 14 Protection against freezing 14 Positioning and fastening 14 Hydraulic system DHW and heating 16 Advices and suggestions to avoid vibrations and noises in the system 16 Cleaning and preservation of the systems 16 Heating system 16 Heating system filling and pressu...

Page 3: ...ibility for any damage arising from wrong installation wrong use and non observance of current laws and instructions given by the manufacturer himself f f Important this gas boiler is used to heat the water at a temperature lower than the boiling one at atmospheric pressure it must be connected to an heating system and or to a domestic hot water system in accordance with its features and power f f...

Page 4: ...Personnel in charge of installation Place here all necessary advices according to national rules about WORK SAFETY of Personnel in charge of installation An example follows Law number 192 of 19 August 2005 and further revisions Title of the law or brief description Always proceed with caution when handling the boiler and carrying out installation mainte nance work as metal parts may cause injuries...

Page 5: ...d also when the gas boiler is located inside a closed space with suitable characteristics The User must not touch sealed items nor break the seals Only specialized technicians and the official technical service can break the seals of sealed items The boiler is fitted with a safety flue flow detection device that should never be bypassed or put out of order If the pressure switch must be replaced u...

Page 6: ...sion must be car ried out by qualified technicians in accordance with the Norms and Laws in force Maintenance operations must be carried out in compliance with the manufacturer prescriptions and in compliance with the laws and rules presently in force for what is not mentioned in this handbook we advice to perform them at least once a year to maintain the boiler s performance Appliance booklet or ...

Page 7: ...arms boiler block on page 30 4 service Indication on the display for the Technician usually not displayed 5 2 digit number on the display Normally it indicates in C the temperature of the water going out of the boiler heat ing or domestic During the adjustment of the heating system temperature rotating the knob 12 along the scale or domestic hot water rotating the knob 13 along the scale it shows ...

Page 8: ...h use is reserved to the technician Do not turn the knob 13 on these positions 16 Commands on the lower side 17 System pressure gauge 18 System filling and pressure restoring cock 19 GAS cock Commands outside the boiler Externally the boiler suitably positioned in the building generally by the installer or by the electrician two devices that the user should access to are present The presence and t...

Page 9: ...eat is sent by means of the system vector liquid to the heating elements of the building If in the mean time a Domestic Hot Water request takes place this latter has the priority for the whole request time Since the DHW requests are usually limited in time they generally don t have any effect on the room heating Temperature adjustment Note correct adjustment leads to creating the conditions for en...

Page 10: ...used by the incorrect wrong or unreasonable use of not original materials The burner doesn t turn on f f if the room thermostat or programmable room thermostat or similar is installed check that it is really requiring the room heating f f check that the electrical power supply is present and that the Summer Winter knob isn t posi tioned on stand by but on Summer or Winter The GREEN light should be...

Page 11: ...cep tional cases of mechanical lock due to the inactivity in presence of water and scale The anti locking function can t work in Safety shut off mode because of the lack of electrical supply Before re igniting the boiler have a technician check that the pump is not blocked due to inac tivity for the technician unscrew the plug in the centre of the cap to access the rotor shaft and turn it with a s...

Page 12: ...tion does not protect the sanitary circuit outside the boiler and especially in areas where the heating system doesn t reach For this reason we recommend that you empty the cold and hot sanitary water from the parts of the system that are at risk of freezing Installation Law and regulation prescriptions for the installer Note for the translator writer Place in this paragraph all the recommendation...

Page 13: ...ing kit upper view front view hydraulic connections on the boiler left side view hydraulic connec tions on the boiler Pump capacity diagram 0 1 2 3 4 5 6 0 200 400 1000 1200 600 800 1400 00023 A 00 pressure m H 2 O water flow l h speed 3 of the pump speed 2 of the pump City Basic 24 C The graph is referred to the capacity available to the system Specifications for inlet air Air must be withdrawn f...

Page 14: ...e systems Protection against freezing Thanks to its antifreeze system inner components could never reach a temperature lower than 5 C This system is activated when the boiler is supplied by the electrical and gas lines provided that the pressure in the heating system is correct In case of boiler installation in rooms where temperature can drop down to 0 it is advisable to fill the heating circuit ...

Page 15: ...ted in the figure A for the plugs and B for the open hooks f f Fix up the connections and all ducts for heating flow and return cold water hot water gas and electrical cables predisposing them in the holes of the metal jig or respecting the measures in the paragraph Di mensions and connections on page 13 The upper edge of boiler s body is represented by the dotted line C in the figure f f Remove t...

Page 16: ...al like welding drops slag hemp mastic mud rust and other dirt from pipes and radiators Otherwise these substances could enter the boiler and damage the internal compo nents pump etc f f In case of old or very dirty systems to wash them use specific proven efficiency products in the suitable quantity and following the instructions of its manufacturer f f If the water on boiler inlet is harder than...

Page 17: ...nsequent gas leaks Using LPG it is absolutely necessary to install a pressure reducer upstream the boiler Failure to do this the gas valve of the boiler will get damaged The gas connection as generally the boiler installation must be done by qualified personnel as prescribed by the regulation in force because a faulty gas connection could lead to fire explosion and other very serious damages to pe...

Page 18: ...stall the new cable proceeding in the reverse way When connecting the cable to the boiler it s mandatory to leave the Earth wire about 2 cm longer than the other Live and Neutral wires to lock the cable upstream the terminals by means of the suitable fastening device Electrical safety of the appliance is only achieved when it is well connected to an efficient earth ing system executed as indicated...

Page 19: ...xication permanent damage and death If the flue thermostat must be replaced use the original spare part only In case of repeated interventions of the device and consequent boiler locks check that the air supply room ventilation system and the Flue Products Outlet System are efficient and made according to the laws in force After whatever servicing of the flue thermostat perform a functional test o...

Page 20: ...un angolo rientranza parete dell edificio H 300 500 600 I terminali sotto un balcone praticabile devono essere collocati in posizione tale che il percorso dei fumi dal punto di uscita del terminale al loro sbocco dal perimetro esterno del balcone compresa l altezza dell eventuale parapetto di protezione se chiusa non sia minore di 2000 mm Per una corretta computazione del percorso dei fumi vedere ...

Page 21: ...21 Notes ...

Page 22: ...cribed For information purposes only we explain that further to a request of domestic hot water this position activates the gas boiler at the minimum output set for this function First starting up All boilers are tested and factory set during manufacture however it is advisable during the first start ing up to perform the following checks and only if necessary the adjustments that could be necessa...

Page 23: ...at must always be closed 2 Activate the boiler to its maximum output not modulated using the Chimney sweeper function Proceed as follows supply the boiler and turn the Summer Winter knob to Summer position provide that Room Thermostat contact is closed activated or open an hot water tap the heat produced by the boiler will be drained consequently turn the Hot Water knob to the position Chimney swe...

Page 24: ...ition Max heating power adjustment The maximum heating power output must be set in accordance with the system requirements stated in the project Once you know the power suitable for the heating system refer to the Burner pressure tables on page 26 and find the burner pressure for the boiler model and for the type of gas used The adjustment will be performed through the boiler s controls following ...

Page 25: ...mer Winter knob for about 30 seconds until the number on the dis play stops flashing also the green indicator stops flashing and stays on During this time check that the pressure displayed on the manometer remains stabilized on the correct value If further pressure adjustment should be needed turn the knob and wait again 30 seconds and the end of flashing to confirm and save the setting turn the H...

Page 26: ... 31 9 325 MAX 23 0 19780 99 12 3 125 27 5 281 35 0 357 Soft ignition Soft ignition pressure is automatic and it needs no adjustment The ignition is achieved by means of a burst of electrical sparks while the burner is supplied with gas initially to the MIN pressure set on the valve gas then pressure increases gradually soft igni tion ramp until the ignition takes place The flame is detected by the...

Page 27: ...he factory setting depends on the gas type arranged in factory for the boiler To change the type of gas supply it is necessary to follow the complete instructions described in the paragraph Gas conversion on page 28 SW2 OFF In City Basic Boilers it must be OFF Factory setting SW3 It determines the delay of 3 minutes before the new ignition of the burner after the over coming of the heating set tem...

Page 28: ...that the gas flow is sufficient to guarantee the appliance correct work 4 Remove the pipe between the gas valve and the injectors bar 5 Remove injectors bar and replace the nozzles with the ones suitable for the available gas type using a 7 mm spanner see figure The nozzles number and diameter is stated in the table Technical data on page 34 6 Reassemble injectors bar and pipe replacing gaskets Ch...

Page 29: ...out 5 seconds that the display shows SE SErvice flashing moreover GREEN lamp flashes with short pulses when the display shows SE flashing turn the Hot Water knob on the scale The indica tion service appears on the display and the burner ignites at the maximum output not modulated the YELLOW light turns on f f make the checks and measurements f f switch off the burner by turning the Summer Winter k...

Page 30: ...signals are listed their most probable causes and the suggested solutions Each alarm code is complete of the status of the RED light indicator on blinking flashing with pulses off Some alarms are signalled with a combination of two or more lights in this case the light colours are explicitly reported close to the relevant status Operations accompanied by the symbol are always reserved to the Techn...

Page 31: ...y pieces of furniture against the wall or by other objects It is however normal that the outlet is realized behind a radiator The outlet must be of the dimension prescribed by the law and must be cleaned inside some types have an anti insects net which could have been dirtied by dust or by spider webs Call a Qualified Technician when it is necessary Interferences with air supply room ventilation I...

Page 32: ...he electric diagram page 37 and check the integrity of the wirings especially the eventual short cable jumpers between two contacts of the same connector on the cabling connections to the electronic board 35 RED YELLOW Unexpected flame the control elec tronic has detected the flame on the burner when this one should be off Wait for the boiler automatic reset 5 minutes or reset it manually by turni...

Page 33: ...r pre scriptions and with the laws and rules presently in force for the parts not mentioned in this handbook Natural draught C models must be subjected to maintenance at least once a year A careful servicing is always a guarantee of safety and energy saving Normally it will be necessary to execute the following operations f f Remove any possible oxidization from burners and electrodes f f Remove t...

Page 34: ...tion in force Technical data TECHNICAL DATA U M City Basic 24 C Gas type G20 G30 G31 CE certification 0694 CM 3400 Class II2H3 Type B11 BS Max heat input kW 25 7 25 7 Min heat input kW 9 9 9 9 Max heat output kW 23 1 23 1 Min heat output kW 8 6 8 6 NOX Class 2 1 1 CO at 0 O2 Qn ppm 54 4 124 60 3 CO2 at nominal input 4 3 5 4 5 0 Flue temperature Qn C 101 101 101 Flue mass flow rate Qn kg h 86 6 79 ...

Page 35: ...ption W 110 Level of protection IP X4D DIMENSIONS Width Height Depth mm see Dimensions and connections on page 13 Weight kg 29 CONNECTIONS Hydraulic and gas connections see Dimensions and connections on page 13 Flue types lengths and diameters see Chimney connections on page 18 GAS SUPPLY PRESSURE Nominal pressure mbar 20 29 37 Inlet pressure min max mbar 17 25 28 30 G30 35 40 G31 Injectors number...

Page 36: ...l 5 Ignition electrode 6 DHW temperature sensor 7 Flame sense electrode 8 Electronic igniter 9 Automatic venting device incorporated in the pump 10 Safety valve 3 bar 11 Gas valve 12 System pressure gauge 13 Priority flow switch with filter 14 Filling valve 15 Drain valve 16 Loss of water pressure switch 17 Pump 18 Heating circuit temperature sensor 19 Burner 20 Bithermic exchanger ...

Page 37: ...ve modulation control 11 2 Gas valve opening control 13 Priority flow switch 16 Loss of water pressure switch 17 Pump 18 Heating circuit temperature sensor 25 Display board 27 Fuse F2A 2A fast Optional external devices 28 Room thermostat Voltage free Contact for Room Thermostat or Chronothermostat for trade working at safety extra low voltage SELV Closed contact heating request Remote control Term...

Page 38: ... 16 14 R M C F G 1 Flue thermostat 2 Flue hood 3 Safety thermostat for max water temperature 4 Expansion vessel 6 DHW temperature sensor 10 Safety valve 3 bar 11 Gas valve 13 Priority flow switch with filter 14 Filling valve 16 Loss of water pressure switch 17 Pump 18 Heating circuit temperature sensor 19 Burner 20 Bithermic exchanger 29 By pass automatic R Heating return M Heating flow C Hot wate...

Page 39: ...ontrol cable coming out of the boiler by means of a suitable bipolar terminal See also Electrical diagram on page 37 Note The Remote Control link is not polarized 4 power supply the boiler turn the boiler s Summer Winter knob on Summer otherwise the Remote Control doesn t work and the boiler goes into alarm 31 described below 5 check the correct work of the device The electronics should recognize ...

Page 40: ...960000001_08_ENG 05 03 2015 ITALTHERM Srl declines any responsibility for eventual printing and or transcription errors in the present manual In order to constantly improve its products the company has the right to change features and data written in the present manual at any time and without notice www italtherm it UNI EN ISO 9001 2008 ...

Reviews: