DESCRIPTION
Nettuno
is an electronic device, employing inverter-based technology, which controls electric pump stopping and starting functions.
Thanks to the particular type of technology used, it can modulate the frequency (Hz) of the motor’s input current to adjust the speed (rpm)
according to the water demand by the system.
This way, the value of the pressure reaching the user appliances is maintained constant all the time and the motor's absorption is always
proportional to the actual system requirements, resulting in notable energy savings over time.
SPECIFICATIONS
NETTUNO 3P-13A
NETTUNO 3P-9A
NETTUNO 3P-6A
Power mains supply:
three-phase, 400Vac ±10% - 50/60Hz
Motor output
three-phase, 400Vac
Maximum motor power
7.5 kW – 10 HP
5.5 kW – 7.5 HP
3.7 kW – 5 HP
Maximum motor phase current
13 A (rms)
9 A (rms)
6 A (rms)
Cooling
Forced air ventilation
Air
Analogue inputs
4÷20mA (pressure sensor) + 0÷10V (aux.)
Digital inputs
3 inputs (enable, error, 2nd set point )
Digital outputs
2 programmable relays (24V – 2A max.)
Degree of protection
IP 44
Weight
6.430 Kg
Dimensions
213x263x191 mm
Type of action
1.Y (according to EN 60730-1)
Operating ambient temperature
+0° C to +40° C
+0° C to +45° C
FEATURES
Constant pressure due to electric pump speed regulation
Energy savings due to less pump absorption
Gradual pump start and stop reduces hammering
Protection against dry running in the event of water shortage during intake
Automatic reset in the event of dry running, with autonomous clearing of error condition
Efficient leakage monitoring to protect pump in the event of repeated restarts
Anti-seize function
Intelligent overload cut-out management for a longer duration of the inverter
Digital display of pressure, current, voltage and frequency
Operation/error status signalling via LEDs and on-screen alerts
Auxiliary inputs and outputs for remote control and status signalling
Possibility of interfacing more devices as part of the pressurisation units (two to eight)
PROTECTIONS
Dry running
Overpressure
Power supply under-voltage
Power supply over-voltage
Unbalanced load
Output terminal short circuit
Amperometric sensor on motor output
Internal overheating in inverter (ambient temperature and IGBT temperature)
Significant leakage with continuous motor pump restarts
EMC
This product has been tested according to the standards stated in the EC declaration of conformity in one of the typical conditions of use,
using shielded cables both on input and output (motor cable 15 metres, without auxiliary connections). However, experience has shown
that significant variations in the level of EMC disturbance can occur when the type and length of cable used is changed, as well as their
position, type of motor used etc.
If other equipment is subject to disturbance, contact the manufacturer to assess additional solutions to reduce electromagnetic disturbance.