9. Product description

The universal dimmer is suitable for the reliable operation of high-
voltage lamps, magnetic transformers, electronic transformers, ESL 
and LED retrofit lamps. There are 2 separate dimmer outputs avai-
lable, each of which can be loaded with 700W. By configuration and 
parallel connection of the outputs the dimmer can be loaded with 
1x1400W.  Each  channel  can  be  parameterized  separately  to  the 
corresponding load type (leading edge or trailing edge mode). The 
dimmer automatically checks the connected load by carrying out a 
short test after the operating voltage has been applied for the first 
time to see whether the connected load can be operated with the 
desired setting. The dimmer works with an internal dimming resolu-
tion of 16 bit and thus meets the highest demands. The properties 
already predefined in the factory, such as dimming curves, minimum 

and maximum limits, can still be changed and optimized by the user 
himself. ISYGLT users can parameterize the functions as usual in 
the  ProgramDesigner.  A  free  software  tool  is  available  for  stand-
alone or DMX users. With this tool, the dimmer can be optimized 
per parameter via USB or RS-485 data connection and internal data 
such as temperatures, voltages, peak currents and power can be 
displayed. In addition, an oscilloscope function is also integrated as 
a new feature. This is the first time that the user has a tool for dis-
playing the current load - and this without dangerous measurements 
on  the  mains  voltage!  A  check  of  unknown  illuminants  -  such  as 
new retrofit lamps - is thus possible without any additional measu-
ring equipment. All you need is the connected UD-700-X2 dimmer, 
a USB cable (USB Type A to Micro B m/m) and our free software.

Inputs / Outputs

• 

2 dimmer outputs 700W

• 

2 control inputs 0-10V or 1-10V for „emergency operation“ or „stand-alone operation“

Design

• 

plastic housing black, can be snapped onto 35mm DIN rail, 6 HP

Function displays in ISYGLT operating mode

LED state

Meaning

1 x LED (red)

OFF

No operating voltage

ON

Operating voltage, no error

steady blinking

Too high mains voltage (>400Vs)

3x blinking

No valid ISYGLT parameters available

1 x LED (yellow)
Operating voltage /
BUS

OFF

No BUS signal detected

ON

BUS signal detected, own address is not 

detected

steady blinking

BUS signal and own module address detected

2 x LED (green)

OFF

Output „OFF“, no error

ON

Output „ON“, no error

steady blinking

Overtemperature

1x blinking

Overload

2x blinking

Overvoltage

3x blinking

Failure of communication with dimmer processor

Connections

• 

1 voltage connection 230V, 45-65Hz

• 

2 outputs 0-230V, max. 700W/VA each or 1x1400W/VA (both channels coupled) 

• 

2 control inputs 0-10V or 1-10V für „emergency operation“ or „stand-alone operation“

• 

1 connection for the subnet (BUS A and B, RS-485)

Summary of Contents for 80026503

Page 1: ...cher GmbH www seebacher de Phone 49 0 80 41 77 77 6 Marktstrasse 57 83646 Bad Tölz info seebacher de Fax 49 0 80 41 77 77 2 1 Technical Data Instruction Manual UD 700 X2 Article no 80026503 Universal Dimmer ...

Page 2: ...be handed over to the device operator The operator will store the documents so that they can be made available if necessary 1 2 Symbols used Observe the following safety and other instructions in the manual Handling instruction The hand indicates that you should carry out an act Danger Immediate danger to life Attention General notes useful information and special features Directory of Content 1 N...

Page 3: ...errors 2 Safety instructions Observe the following general safety instructions when installing and commissioning the device Assembly and installation of the ISYGLT module may only be carried out by a qualified electrician Other activities in connection with the ISYGLT module such as assembly and installation of system com ponents with tested standard plug connections as well as operation and confi...

Page 4: ... screws Assembly site The product can be installed in any position in a casing to be deter mined by the electrician distribution box switch cabinet Observe maximum ambient temperature Assembly steps Read completely before assembly Mount the device in a suitable casing Make the electrical connections according to the wiring diagram Configure the DIP switches according to your requirements Only afte...

Page 5: ... temperatures voltages peak currents and power can be displayed In addition an oscilloscope function is also integrated as a new feature This is the first time that the user has a tool for dis playing the current load and this without dangerous measurements on the mains voltage A check of unknown illuminants such as new retrofit lamps is thus possible without any additional measu ring equipment Al...

Page 6: ... the set address are not transmitted telegram too short or data format is wrong RS 485 test set address or data format is wrong 1Hz blinking Communication processor receives data 2 x LED green OFF Output OFF no error ON Output ON no error 1Hz blinking Warning switch off at too high temperatures Communication processor 65 C 75 C MOSFET housing 95 C 105 C 1x blinking break 1 5s Signal at overload 1 ...

Page 7: ...start address 331 Address 0 to 511 Mode Channel 1 2 coupled Channel 1 2 seperated C Address bit 0 1 2 3 4 5 6 7 8 1 1 2 0 DMX 512 8 bit 1 1 2 1 DMX 512 16 bit 1 2 3 4 5 6 7 8 O N A B D 1 2 3 4 5 6 7 8 O N Mode U inputs 1 10V Channel 1 2 coupled 1 button dimmer Reserve U inputs 0 10V Channel 1 2 separately Analog 0 1 10V Reserve 1 2 3 4 5 6 7 8 O N U inputs 1 10V U inputs 0 10V C A B D C A B D Dimm...

Page 8: ...or ESL General in PC program UD 700 X2 Type designation UD 700 X2 Article no 80026503 Mains supply 230V 45 to 65 Hz Mains fuse 1 x 230V automatic or GL fuse 10A Output 2 x 230V short circuit proof 10W 700W per channel Power loss 0 5 6W Stand by full load per channel total 12W at 2x700W load Please ensure that the switch cabinet or housing is sufficiently ventilated 1 0 10V Sink current at 1 10V 0 ...

Page 9: ...utput LD2 emergency function 10V Power supply for external potentiometer s Reserve Reserve GND Reference potential Ground for the voltage inputs 0 10V and BUS RS 485 A ISYGLT subnet BUS RS 485 B ISYGLT subnet BUS RS 485 10 1 Pin assignment Terminal Internal connections Meaning LD1 Dimmer 1 load output 0 230V max 700W VA leading edge trailing edge LD2 Dimmer 2 load output 0 230V max 700W VA leading...

Page 10: ...e Phone 49 0 80 41 77 77 6 Marktstrasse 57 83646 Bad Tölz info seebacher de Fax 49 0 80 41 77 77 2 10 Sample views of PC program Oscillogram of retrofit LEDs in trailing edge mode Tab General Tab Special functions Custom dim curves ...

Page 11: ...03 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 OFF ON ISYGLT L N GND BUS A BUS B LD1 LD2 N UE1 UE2 GND 10V 005 e g ISYGLT Adr 5 low voltage magnetic transformer low voltage electronic transformer dimmable ECG high voltage halogen Suited for trailing or leading edge leading edge trailing edge trailing or leading edge trailing or leading edge Sample controlled by ISYGLT 2x700W external voltage control e g emerg...

Page 12: ...80026503 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 OFF ON ISYGLT L N GND BUS A BUS B LD1 LD2 N UE1 UE2 GND 10V 005 Sample controlled by ISYGLT 1x1400W trailing or leading edge Suited for trailing or leading edge leading edge trailing edge low voltage magnetic transformer low voltage electronic transformer dimmable ECG high voltage halogen e g ISYGLT Adr 5 external voltage control e g emergency function max ...

Page 13: ...GND BUS A BUS B LD1 LD2 N UE1 UE2 GND 10V trailing or leading edge trailing or leading edge low voltage magnetic transformer low voltage electronic transformer dimmable ECG high voltage halogen Suited for trailing or leading edge leading edge trailing edge external voltage control e g emergency function 0V 0 1 10V 0 1 10V Sample controlled by DMX512 8 16 Bit e g 8 Bit DMX start adr 261 for more DI...

Page 14: ...5 6 7 8 1 2 3 4 5 6 7 8 OFF ON ISYGLT L N GND BUS A BUS B LD1 LD2 N UE1 UE2 GND 10V DIP switches please use the datasheet trailing or leading edge trailing or leading edge high voltage halogen Suited for trailing or leading edge leading edge trailing edge low voltage magnetic transformer low voltage electronic transformer dimmable ECG Option 1 button dimmer Sample 1 10V and 1 button dimming max 70...

Page 15: ...ISYGLT L N GND BUS A BUS B LD1 LD2 N UE1 UE2 GND 10V A E S 10kOhm A E S 10kOhm Sample Potentiometer 10kOhm trailing or leading edge trailing or leading edge high voltage halogen Suited for trailing or leading edge leading edge trailing edge low voltage magnetic transformer low voltage electronic transformer dimmable ECG DIP switches please use the datasheet max 700W max 700W option potentiometer 1...

Reviews: