3
Installation guide
Local Control Network - building controls in perfection
Installation
The transponder is supplied completely weatherproof with a 5 metre long shedded
connecting cable. Because of this, it can be installed outdoors. The hole pitch corresponds
to fixing standards (cavity wall box, outside switches, garage openers). The reader shows
its readiness for operation with its permanently lit LED. This light can be adjusted with the
command ”LED control” (brighter/darker and red/blue).
Minimum distance between two LCN-ULT transponder readers
®
to avoid them from
interfering with each other, a possible distance of 75cm should be kept between each
LCN-ULT.
Connection
LCN-ULT can be connected either directly to the I-port of
an LCN module or extended up to a distance of 50m, by using additional LCN-IV´s - see
also installation guide LCN-IV.
The operation with further I-port peripheries with bidirectional communication
(e.g.
LCN-GT4D, -GT10D or IOS-peripheries) is not permitted!
Operating the LCN-IV as pulse
counter / counter input, is not possible!
The LCN-ULT is suitable for connecting to the I-port of all LCN modules with firmware
100A06 (Oct. 2006) or after. The
Note:
LCN-ULT
®