Isolite ELCD 1008 Installation Manual Download Page 4

Wire Terminations

Termin al

W ire Ran ge

St rip

Len g t h

To rq u e

Rat ing

10–18 A W G (copper w ire

3/8”

Line / Load / Term inals 1–8

10 in–lbs

solid/st randed)

(10m m )

Control (signal) / Term inals 9–12

10–20 A W G (copper w ire

st randed only)

1/ 4”

(6m m )

4 in–lbs

6–14 A W G (copper w ire

3/8”

Eart h Ground

35 in–lbs

solid/st randed)

(10m m )

Wire and Terminal Specifications

Installation  Guide
ELCD 1008

Isolite Corp  31 Waterloo Ave, Berwyn PA

4

The  ELCD  1008  can  accommodate  installations  that  require  a 

Simple  Transfer 

of  normal  and 

emergency power or more complex installations that utilize a 

Dimmed or Switched Load

. See the 

related instruction for your installation type. Additionally, the unit can accommodate installations that 
utilize

  0–10V  Auxiliary  Output

  control  and  for  use  with  either  normally  open  or  normally-closed 

operation.

WARNING:  Before  you  begin  pulling  and  terminating  wire  to  the  ELCD  1008  BCELTS 
enclosure, make sure the main circuit breaker cabinet or other readily accessible input power 
disconnect device for both normal and emergency power input is locked out and tagged out. 
Enclosures installed without an accessible input power disconnect device cannot be serviced 
or operated safely. Follow all local codes and restrictions. When the disconnect device is not 
located near the installed enclosure, the disconnect must allow for proper lockout/tagout.

Power Supply

Power Supply

Emergency Input
Connections

Normal Input
Connections

Sense Circuit
Connections

Load Output
Connections

Earth Ground

Fire Alarm (contact input)

0-10V (relay)

Summary of Contents for ELCD 1008

Page 1: ...Systems Article 702 Optional Standby Systems Section 518 3 C Assembly Occupancies Section 520 7 Theatres and Similar Locations Section 540 11 C Motion Picture Projection Rooms REMOTE TEST NORMAL POWER...

Page 2: ...ms in accordance with Article 300 of the National Electrical Code NFPA70 NEMA Type1 Enclosure suitable for installation location that conforms to the following ambient environment 0 40 C 5 95 non cond...

Page 3: ...l power is restored Note The re alarm input functions with up to 1 000ft 300m of 18AWG wire connected between the input and the switch Fire Alarm Inputs of up to 10 ELCD 1008 units can be wired togeth...

Page 4: ...can accommodate installations that utilize 0 10V Auxiliary Output control and for use with either normally open or normally closed operation WARNING Before you begin pulling and terminating wire to t...

Page 5: ...wire and the jumper fork terminal c Terminate the hot wire to the NORMAL 5H hot terminal and secure the terminal screw onto the wire and the jumper fork terminal 5 Terminate emergency power wires a R...

Page 6: ...ch terminal screw onto the wire 3 Install a jumper wire between SENSE 4N neutral and Normal 6N neutral 4 Terminate normal power wires a Run a neutral and a hot wire through conduit from the normal pow...

Page 7: ...V wire typically purple between 0 10V ballast and the 0 10V terminal 9 in the ELCD 1008 and secure the terminal onto the wire 3 Run a common wire typically gray between the 0 10V controller and the 0...

Page 8: ...wer to the unit 7 Test the operation of the ELCD 1008 as described in Operation and Test below Operation and Test It is important to test the ELCD 1008 regularly because it is a life safety device NFP...

Page 9: ...l you release the PUSH TO TEST button If emergency power is not present for the test the ELCD1008 will remain in normal mode Test Button Fuse Replacement Directing a laser pointing device at the REMOT...

Page 10: ...is locked out and tagged out before removing the cover from this enclosure 1 Disconnect both power supply sources and lock tagout appropriately 2 Loosen the four screws and remove the cover 3 Locate t...

Reviews: