Wire Terminations
Termin al
W ire Ran ge
St rip
Len g t h
To rq u e
Rat ing
10–18 A W G (copper w ire
3/8”
Line / Load / Term inals 1–8
10 in–lbs
solid/st randed)
(10m m )
Control (signal) / Term inals 9–12
10–20 A W G (copper w ire
st randed only)
1/ 4”
(6m m )
4 in–lbs
6–14 A W G (copper w ire
3/8”
Eart h Ground
35 in–lbs
solid/st randed)
(10m m )
Wire and Terminal Specifications
Installation Guide
ELCD 1008
Isolite Corp 31 Waterloo Ave, Berwyn PA
4
The ELCD 1008 can accommodate installations that require a
Simple Transfer
of normal and
emergency power or more complex installations that utilize a
Dimmed or Switched Load
. See the
related instruction for your installation type. Additionally, the unit can accommodate installations that
utilize
0–10V Auxiliary Output
control and for use with either normally open or normally-closed
operation.
WARNING: Before you begin pulling and terminating wire to the ELCD 1008 BCELTS
enclosure, make sure the main circuit breaker cabinet or other readily accessible input power
disconnect device for both normal and emergency power input is locked out and tagged out.
Enclosures installed without an accessible input power disconnect device cannot be serviced
or operated safely. Follow all local codes and restrictions. When the disconnect device is not
located near the installed enclosure, the disconnect must allow for proper lockout/tagout.
Power Supply
Power Supply
Emergency Input
Connections
Normal Input
Connections
Sense Circuit
Connections
Load Output
Connections
Earth Ground
Fire Alarm (contact input)
0-10V (relay)