Isolite ELCD 1008 Installation Manual Download Page 2

Installation Requirements

Note:

Ambient Environment

Electrical Specification

Normal and Emergency Rated Operational Voltage Input

Load Rating

Transfer Initiation

Short Circuit Current Rating

Installation  Guide
ELCD 1008

Isolite Corp  31 Waterloo Ave, Berwyn PA

2

Install the ELCD 1008 in a location that is accessible by qualified personnel for testing of the transfer function 
using either a laser pointer (or similar) or the on board test switch. 

The  ELCD  1008  installs  to  a  flat  surface,  has  four  conduit  entry  locations,  and  has  four  mounting  holes. 
Mounting and conduit hardware are provided by others.

Suitable for use in other spaces used for environmental air (plenums) in accordance with 
Article 300 of the National Electrical Code (NFPA70).

NEMA Type1 Enclosure suitable for installation location that conforms to the following ambient environment:

0–40°C, 5%–95% non–condensing humidity 

Note:

Continuous load current not to exceed 100% of the switch rating.Use copper wire only, minimum
75°C conductors.

120–277 VAC +/-10%, 50/60Hz

Supports  a  continuous  load  of  up  to  20A  for  tungsten  and  resistive  load  types,  and  supports 
electronic ballast loads of up to 16A (80% of the switch rating)

   Continuous load current not to exceed 100% of the switch rating

When normal power is lost, meaning the voltage drops below 85VRMS, the unit transfers the output 
load to the emergency power source.

When normal power is restored, meaning the voltage rises above 90VRMS, the unit transfers the 
output load to the normal power source.

Short circuit capacity of 10kA

Summary of Contents for ELCD 1008

Page 1: ...Systems Article 702 Optional Standby Systems Section 518 3 C Assembly Occupancies Section 520 7 Theatres and Similar Locations Section 540 11 C Motion Picture Projection Rooms REMOTE TEST NORMAL POWER...

Page 2: ...ms in accordance with Article 300 of the National Electrical Code NFPA70 NEMA Type1 Enclosure suitable for installation location that conforms to the following ambient environment 0 40 C 5 95 non cond...

Page 3: ...l power is restored Note The re alarm input functions with up to 1 000ft 300m of 18AWG wire connected between the input and the switch Fire Alarm Inputs of up to 10 ELCD 1008 units can be wired togeth...

Page 4: ...can accommodate installations that utilize 0 10V Auxiliary Output control and for use with either normally open or normally closed operation WARNING Before you begin pulling and terminating wire to t...

Page 5: ...wire and the jumper fork terminal c Terminate the hot wire to the NORMAL 5H hot terminal and secure the terminal screw onto the wire and the jumper fork terminal 5 Terminate emergency power wires a R...

Page 6: ...ch terminal screw onto the wire 3 Install a jumper wire between SENSE 4N neutral and Normal 6N neutral 4 Terminate normal power wires a Run a neutral and a hot wire through conduit from the normal pow...

Page 7: ...V wire typically purple between 0 10V ballast and the 0 10V terminal 9 in the ELCD 1008 and secure the terminal onto the wire 3 Run a common wire typically gray between the 0 10V controller and the 0...

Page 8: ...wer to the unit 7 Test the operation of the ELCD 1008 as described in Operation and Test below Operation and Test It is important to test the ELCD 1008 regularly because it is a life safety device NFP...

Page 9: ...l you release the PUSH TO TEST button If emergency power is not present for the test the ELCD1008 will remain in normal mode Test Button Fuse Replacement Directing a laser pointing device at the REMOT...

Page 10: ...is locked out and tagged out before removing the cover from this enclosure 1 Disconnect both power supply sources and lock tagout appropriately 2 Loosen the four screws and remove the cover 3 Locate t...

Reviews: