Installation Guide
ELCD 1008
Troubleshooting
When both of the ELCD 1008 LEDs are blinking, the relays need to be manually reset to a known state.
WARNING:RISK OF ELECTRIC SHOCK! More than one live circuit is present inside the
enclosure. Make certain the main circuit breaker cabinet or other readily accessible input
power disconnect device for both normal and emergency power input is locked out and
tagged out before removing the cover from this enclosure.
1. Disconnect both power supply sources and lock/tagout appropriately.
2. Loosen the four screws and remove the cover.
3. Locate the four relay switches near the
status LEDs.
4. Using a flat blade screwdriver, carefully
slide the relay switch to the left.
5. Repeat for all four relays in the ELCD 1008
enclosure.
6. Replace the cover to the enclosure.
7. Re-apply power from both sources and
retest the unit.
See Operation and Test on page 8
for
instructions on testing the unit.
Isolite Corp 31 Waterloo Ave, Berwyn PA