Fire Alarm Input

0–10V Auxiliary Output

Installation

Mounting and Conduit

ELCD 1008 Outline Drawing

Installation  Guide
ELCD 1008

Isolite Corp  31 Waterloo Ave, Berwyn PA

3

The Fire Alarm Input allows power transfer to the emergency power source (if emergency power is present) 
when triggered by an external system.

Note:

This transfer is activated even when normal power is still present.

The contact input can be configured for normally open or normally closed operation using switch settings on the 
control board. Normally open and normally closed refer to the normal operational state of the external circuit, 
not to the de-energized state of the external relay.

When the contact input is triggered, the unit will transfer to the emergency power source.

When the contact input trigger is removed, the unit will transfer back to the normal power source, if present, 
or will remain on emergency power until normal power is restored

.

Note:

The fire alarm input functions with up to 1,000ft (300m) of 18AWG wire connected between the
input and the switch. Fire Alarm Inputs of up to 10 ELCD 1008 units can be wired together using a 
single normally open or normally closed contact.

 See Fire Alarm Input on page 7 for details.

The 0– 10V Auxiliary Output provides an additional single pole relay that opens when the unit is in the 
emergency state. This allows connection of 0– 10V or DALI ballasts that need the removal of the 
control signal in order to illuminate at full in an emergency state.

Using the mounting holes in the bottom of the 
enclosure, secure the ELCD 1008 enclosure to 
a flat surface using four 1/4-20 mounting bolts or 
screws (provided by others).
Four knockouts are provided on the side of the 
enclosure.  Install  conduit  fittings  (provided  by 
others).

The  ECLD1008 enclosure can be 
r o t a t e d   9 0 ° ,   t o   c h a n g e   t h e  
orientation  as  needed  for  the 
installation. 
The  front  cover  has  a  legend 
printed  on  both  sides  to  insure 
correct  indication  of  status  LEDs 
and Test Switch. 

Note:

8.00

9.00

8.50

9.50

4x mounting holes

4x conduit
entry

Summary of Contents for ELCD 1008

Page 1: ...Systems Article 702 Optional Standby Systems Section 518 3 C Assembly Occupancies Section 520 7 Theatres and Similar Locations Section 540 11 C Motion Picture Projection Rooms REMOTE TEST NORMAL POWER...

Page 2: ...ms in accordance with Article 300 of the National Electrical Code NFPA70 NEMA Type1 Enclosure suitable for installation location that conforms to the following ambient environment 0 40 C 5 95 non cond...

Page 3: ...l power is restored Note The re alarm input functions with up to 1 000ft 300m of 18AWG wire connected between the input and the switch Fire Alarm Inputs of up to 10 ELCD 1008 units can be wired togeth...

Page 4: ...can accommodate installations that utilize 0 10V Auxiliary Output control and for use with either normally open or normally closed operation WARNING Before you begin pulling and terminating wire to t...

Page 5: ...wire and the jumper fork terminal c Terminate the hot wire to the NORMAL 5H hot terminal and secure the terminal screw onto the wire and the jumper fork terminal 5 Terminate emergency power wires a R...

Page 6: ...ch terminal screw onto the wire 3 Install a jumper wire between SENSE 4N neutral and Normal 6N neutral 4 Terminate normal power wires a Run a neutral and a hot wire through conduit from the normal pow...

Page 7: ...V wire typically purple between 0 10V ballast and the 0 10V terminal 9 in the ELCD 1008 and secure the terminal onto the wire 3 Run a common wire typically gray between the 0 10V controller and the 0...

Page 8: ...wer to the unit 7 Test the operation of the ELCD 1008 as described in Operation and Test below Operation and Test It is important to test the ELCD 1008 regularly because it is a life safety device NFP...

Page 9: ...l you release the PUSH TO TEST button If emergency power is not present for the test the ELCD1008 will remain in normal mode Test Button Fuse Replacement Directing a laser pointing device at the REMOT...

Page 10: ...is locked out and tagged out before removing the cover from this enclosure 1 Disconnect both power supply sources and lock tagout appropriately 2 Loosen the four screws and remove the cover 3 Locate t...