Isolite DTH2 SERIES Installation And Operating Instructions Manual Download Page 3

Before installing unit, disconnect power at breaker panel

3. The spider plate assembly will be provided with the transformer mounted and the lead
     wires strain relieved by the cable clamp (as shown below).  Connect lead wires to feed 
     wires in junction box as per local code.  

Figure 4: Lead wire connections to transformer

Black lead for 120V OR 
Orange lead for 277V 
White lead for neutral
Green Lead for Ground
(CAP UNUSED LEAD)

Secondary wires

to Exit Sign

routed through center

hole on spider plate

Transformer

Green
Ground

White
Neut

Black
120V

Orange
277V

Cap unused
primary wire

Protected Earth 
Ground Screw

Cable clamp 
(strain relief)

spider plate

4. Determine which directional indicators are to be removed. Remove light guide assembly
and set aside. Support front cover as shown below and knock out desired directional indicator(s).

Figure 5: Removing the directional indicators (chevrons)

Knock out desired directional
indicators (chevrons) supporting 
the front panel as shown.

Z410138 Rev B

Page 3