FIGURE 27
FIGURE 26
Required Clearances (when sheathing protrudes beyond front of firebox)
18
The STANDARD Series Isokern fireplace is tested and listed for 1 1/2” clearance to un-insulated wood framing material
at the firebox sides, back and at the smoke dome front, sides and back. However installation and use practices that are beyond the
control of the manufacturer* can create situations where a zero clearance installation can jeopardize the safety of combustibles in
contact with the Isokern surfaces resulting in fire damage to property, personal injury or loss of life.
*The manufacturer is not responsible for installation and use practices that are beyond the scope of the product as defined
in the product listing and in the installation manual.
WARNING: Do not pack or fill the air spaces with insulation or other material. No material is allowed in these areas.
The manufacturer strongly recommends that wherever possible, all combustible framing materials be kept a minimum of
1-1/2” clearance from the Isokern fireplace unit at the side walls and back walls. It is the responsibility of the General Contractor
to insure that listed clearances to combustible framing and to insulation are maintained throughout the construction of the project
subsequent to the installation of the Isokern unit.
FIGURE 28