Flush Wall Finish Detail
STANDARD Series fireplaces are designed to be installed so that the rough front face of the firebox and smoke dome sit flush to
the room face of the rough framing members that create the room wall finish. (Figure 24)
CAUTION:
Do not frame a wall in front of the Standard Series firebox / smoke dome assembly, as shown in figure 25
Wall framing must not be placed across the front face of the fi rebox and smoke dome assembly.
Clearance to Drywall:
Drywall can be placed directly in contact with the front of the firebox and smoke dome. (Figure 24)
Drywall can be hung on the framing members and pass across the face of the smoke dome and in contact with it. If necessary, the
drywall can be affixed to the face of the Standard Series fireplace with drywall screws, maximum length 1” - do not use nails.
The drywall must be cut back a minimum of 2” from the sides of the firebox opening and 8” back from the top of the
firebox opening.
These drywall cut back areas must be filled with grout in conjunction with the installation of the required fire brick lining of the
firebox and with the application of code required noncombustible finish facing material.
FIGURE 24
FIGURE 25
FRAMING PROTRUDES
PAST FIREBOX FRONT
DRYWALL FLUSH
WITH FIREBOX
FRONT