background image

www.ismacontrolli.com

pag. 2

DBL561en | 1

st

 Issue rev. c | 03/2022

DESCRIPTION

MVE204-65 

MVE204S-65

MVE206-65 

MVE206S-65

MVE210-65 

MVE210S-65

MVE215-65 

MVE215S-65

MVE222-65 

MVE222S-65

Output V+

voltage 16Vdc ± 0,5V, max load 25mA,

Output U

voltage 2-10Vdc (0-100%), max load 2mA

Room temperature

operation -10T55°C; storage -20T55°C

Room humidity

max 90% R.H.

Protection degree

IP65

Insulation class

Standard

Emission/Immunity EMC 2014/30/UE according to EN 61326-1:2013 standard 

LVD 2014/35/UE according to EN61010-1:2010 standard

Material

housing: aluminium - cover: ABS plastic

Colour

aluminium / white

Weight [kg]

1.7 (MVE2xx-65); 1.6 (MVE2xxS-65)

OPERATION

The actuator translates the control signal (modulating or 3 point floating) from the controller into a valve position. A modern brushless

DC motor in the actuator drive a gear train and a worm gear – screw IP65 Globe Valves Actuators MVE2xx-65 jack mechanism convert 

the motor revolutions into accurate and repeatable linear movements.

Control Signal

MVE2xx-65 can be controlled by one of 2 main control types.

•  3 point floating;

•  modulating (or proportional) signal with field selectable range (e.g., 0-10Vdc, 2-10Vdc, 0-5/2-6Vdc, 5-10/6-10Vdc and 4-20mA).

Manual Override

There is a manual operation handle on the actuator. When it is lowered (manual override ON), the power supply to the motor power 

stage circuitry is cut and the motor stops. The actuator can be operated manually and the valve positioned accordingly. The manual 

override lever latches in position until it is raised again, then board and motor will be powered again. At the end of this operation 

the actuator moves to initial position (on the basis of DIP n. 1 setting) then it follows the control signal. When the manual override is 

engaged the GREEN and the RED LED are ON.

Manual operation handle can also be used to modify any DIP switch setting or as re-set function after any alarm occurrence. The 

actuator is supplied with the manual override lowered (ON).

It is not necessary to remove power supply to modify DIP switch setting, but, in this case, take care of 230Vac voltage.

Feedback Position

The actuator utilizes a 2-10V position feedback (look at DIP n. 1 setting).

Calibration

The actuator has both auto and manual stroke calibration, DIP n. 7.

In factory delivery the auto stroke calibration is enabled – manual calibration is not necessary unless maintenance is required on the 

valve or certain alarm functions are desired.

End Point Auxiliary Switches (accessory DMVE)

End point switches change over when the valve is fully open or closed. They are free contact with 24V AC/DC, 4A max voltage to 

terminals.

End point switches can be utilized to indicate valve stroke end positions and for relay control of additional plant equipment. When 

the actuators are controlled individually or in sequence, it is possible to use the end switches to toggle when the valve is fully open 

or fully closed. The auxiliary switch position according to control signal (Y) is shown in the table below.

CONTROL SIGNAL (Y)

RELAY KC1

RELAY KC2

0-0,5Vdc

KC1 to K2

KC2 to K3

0,5-9,5Vdc

KC1 to K1

KC2 to K3

9,5-10Vdc

KC1 to K1

KC2 to K4

Summary of Contents for MVE2 Series

Page 1: ...e range for exacting fluid control and it is able to self calibrate on a different stroke without the need of any user action this function is DIP switch selectable on the field MVE2xx 65 has intelligent behaviour and alarm functionality in case of unexpected operation feedback of alarms to the user is pro vided by LEDs GREEN and RED on the control board N B Do not use the actuator if not coupled ...

Page 2: ...nual override lever latches in position until it is raised again then board and motor will be powered again At the end of this operation the actuator moves to initial position on the basis of DIP n 1 setting then it follows the control signal When the manual override is engaged the GREEN and the RED LED are ON Manual operation handle can also be used to modify any DIP switch setting or as re set f...

Page 3: ...object IP65 is guaranteed by internal seals IP65 cable gland and the proper engineering of the enclosure One IP65 PG13 5 cable gland and one IP65 PG13 5 plug are supplied with the actuator ASSEMBLING The actuator can be mounted with any orientation but never up side down When the fluid temperature exceed 120 C the actuator shall be mounted leaning 45 T fluid 120 C T fluid MAX 120 C T fluid 120 C T...

Page 4: ...S VALVES MVE2XX 65 MVE2XXS 65 Belimo H2 X S and H3 X S with AG82 with AG82 Siemens with AG70 10 with AG70 14 Danfoss VR VF S models with AG60 07 TAC DN15 V298 with AG60 08 TAC DN15 V2XX V3XX with AG60 09 Honeywell with AG60 10 Airtek with AG60 11 with AG60 12 Johnson Controls VB7816 2111 with AG66 Johnson Controls BM 3018 3300 with AG67 MUT MK DN50 150 with AG69 Tac Venta AG70 10 for valves having...

Page 5: ...00m Y2 Close V 16 Vdc Voltage Output max 25mA AWG20 min 0 5mm2 max 1 5mm2 200m M 0V Common U 2 10Vdc Feedback Output Signal AWG20 min 0 5mm2 max 1 5mm2 200m M 0V Common Note To avoid damages to electronic components caused by the PCB bending do not press too much while fixing the terminal block GROUND CONNECTIONS Connect the ground terminal to the proper screw labelled with the ground symbol as sh...

Page 6: ...d to M 3 Selection of sequence mode control range defined by DIP n 5 4 Modulating Control 0 10Vdc DIP n 2 OFF only Modulating Control 2 10Vdc DIP n 2 OFF only 5 Sequence Control 0 5Vdc with DIP n 4 OFF only Sequence Control 2 6Vdc with DIP n 4 ON only DIP n 3 ON only Sequence Control 5 10Vdc with DIP n 4 OFF only Sequence Control 6 10Vdc with DIP n 4 ON only DIP n 3 ON only 6 Voltage Input Signal ...

Page 7: ...nst the new stroke limit then it goes back to the initial position still signalling the anomaly until it is not within 60mm The actua tor does not calibrate the stroke after 10s wrong range Valve with a stroke length longer than 60mm Remove power and power up again 3 RED Quick Blinking Unexpected stall within the calibra ted stroke range normal operation The actuator tries 5 times against the new ...

Page 8: ...ctuator arrived at the extreme point of the stroke read 2 GREEN BLINKING The actuator arrived at the intermediate point of the stroke read 3 RED GREEN BLINKING The actuator is reading the stroke or it is going to initial position 4 RED GREEN ON Manual control ON the actuators ignores the control signal ATTENTION The electronic board is electrically supplied DIMENSIONS mm 234 194 86 122 177 194 122...

Reviews: