background image

www.ismacontrolli.com

pag. 3

DBL561en | 1

st

 Issue rev. c | 03/2022

K1    K2  KC1

End point position

End point position

K3    K4  KC2

OPENING RELAY

CLOSING RELAY

DMVE

Diagnostic

The actuator is provided with a self diagnostic algorithm able to detect faulty conditions:

•  stroke calibration out of range 5-60mm;

•  unexpected stall condition (e.g. valve stuck or extra stroke due to actuator link loose);

•  voltage supply out of range.

These faulty conditions are signalled via the GREEN and RED LED on the electronic board blinking accordingly (see Diagnostic – Alarm 

Function Table).

IP65

Protection against water and solid object IP65 is guaranteed by internal seals, IP65 cable gland and the proper engineering of the 

enclosure.

One IP65 PG13,5 cable gland and one IP65 PG13,5 plug are supplied with the actuator.

ASSEMBLING

The actuator can be mounted with any orientation but never up-side down. When the fluid temperature exceed 120°C the actuator 

shall be mounted leaning 45°.

T fluid ≥ 120°C

T fluid MAX 120°C

T fluid ≥ 120°C

To mount the actuator on to a valve, position the valve stem to the bottom of its travel, slide the actuator onto the valve neck, adju-

sting with the manual override the screw jack position so the square nut on the valve spindle fits into the groove on the cross bar. 

Then slide the brace into the groove on the valve neck and secure the nuts.

See mounting instructions for full details (MVE2xx_DIM205).

Summary of Contents for MVE2 Series

Page 1: ...e range for exacting fluid control and it is able to self calibrate on a different stroke without the need of any user action this function is DIP switch selectable on the field MVE2xx 65 has intelligent behaviour and alarm functionality in case of unexpected operation feedback of alarms to the user is pro vided by LEDs GREEN and RED on the control board N B Do not use the actuator if not coupled ...

Page 2: ...nual override lever latches in position until it is raised again then board and motor will be powered again At the end of this operation the actuator moves to initial position on the basis of DIP n 1 setting then it follows the control signal When the manual override is engaged the GREEN and the RED LED are ON Manual operation handle can also be used to modify any DIP switch setting or as re set f...

Page 3: ...object IP65 is guaranteed by internal seals IP65 cable gland and the proper engineering of the enclosure One IP65 PG13 5 cable gland and one IP65 PG13 5 plug are supplied with the actuator ASSEMBLING The actuator can be mounted with any orientation but never up side down When the fluid temperature exceed 120 C the actuator shall be mounted leaning 45 T fluid 120 C T fluid MAX 120 C T fluid 120 C T...

Page 4: ...S VALVES MVE2XX 65 MVE2XXS 65 Belimo H2 X S and H3 X S with AG82 with AG82 Siemens with AG70 10 with AG70 14 Danfoss VR VF S models with AG60 07 TAC DN15 V298 with AG60 08 TAC DN15 V2XX V3XX with AG60 09 Honeywell with AG60 10 Airtek with AG60 11 with AG60 12 Johnson Controls VB7816 2111 with AG66 Johnson Controls BM 3018 3300 with AG67 MUT MK DN50 150 with AG69 Tac Venta AG70 10 for valves having...

Page 5: ...00m Y2 Close V 16 Vdc Voltage Output max 25mA AWG20 min 0 5mm2 max 1 5mm2 200m M 0V Common U 2 10Vdc Feedback Output Signal AWG20 min 0 5mm2 max 1 5mm2 200m M 0V Common Note To avoid damages to electronic components caused by the PCB bending do not press too much while fixing the terminal block GROUND CONNECTIONS Connect the ground terminal to the proper screw labelled with the ground symbol as sh...

Page 6: ...d to M 3 Selection of sequence mode control range defined by DIP n 5 4 Modulating Control 0 10Vdc DIP n 2 OFF only Modulating Control 2 10Vdc DIP n 2 OFF only 5 Sequence Control 0 5Vdc with DIP n 4 OFF only Sequence Control 2 6Vdc with DIP n 4 ON only DIP n 3 ON only Sequence Control 5 10Vdc with DIP n 4 OFF only Sequence Control 6 10Vdc with DIP n 4 ON only DIP n 3 ON only 6 Voltage Input Signal ...

Page 7: ...nst the new stroke limit then it goes back to the initial position still signalling the anomaly until it is not within 60mm The actua tor does not calibrate the stroke after 10s wrong range Valve with a stroke length longer than 60mm Remove power and power up again 3 RED Quick Blinking Unexpected stall within the calibra ted stroke range normal operation The actuator tries 5 times against the new ...

Page 8: ...ctuator arrived at the extreme point of the stroke read 2 GREEN BLINKING The actuator arrived at the intermediate point of the stroke read 3 RED GREEN BLINKING The actuator is reading the stroke or it is going to initial position 4 RED GREEN ON Manual control ON the actuators ignores the control signal ATTENTION The electronic board is electrically supplied DIMENSIONS mm 234 194 86 122 177 194 122...

Reviews: